How to Calculate Transmission-Line Power Loss for HSC Physics

Learn how to calculate transmission-line power loss from delivered power, voltage, and resistance. Follow worked examples involving transformers, voltage drops, and challenging HSC-style questions with full solutions.

A workshop receives 3.0 kW of electrical power through a pair of long cables. The equipment works normally, but the power source must supply more than 3.0 kW because some energy heats the cables along the way.

How much extra power must the source provide? Can you work it out from the delivered power alone?

Not quite. You also need the current flowing through the transmission line and the total resistance of the cables. Once you know those, calculating the power lost as heat is straightforward. The tricky part is making sure you’re using the current and voltage at the correct points in the system.

01The direct method: Start with the delivered power

Suppose a transmission line delivers electrical power \(P_{\rm d}\) to a load.

The line has some electrical resistance. As current passes through the conductors, electrical energy is converted into thermal energy.

The rate of this unwanted energy transfer is

\[ P_{\rm loss}=I_\ell^2R_\ell \]

where:

  • \(P_{\rm loss}\) is the power lost as heat, measured in watts (W).
  • \(I_\ell\) is the current through the transmission line, measured in amperes (A).
  • \(R_\ell\) is the total resistance of the transmission path, measured in ohms (\(\Omega\)).

If the question gives the power delivered to the load and the voltage at the receiving end of the line, you can first calculate the line current:

\[ I_\ell=\frac{P_{\rm d}}{V_{\rm r}} \]

Here, \(V_{\rm r}\) is the receiving-end line voltage in volts (V). If an ideal step-down transformer connects the line to the load, \(V_{\rm r}\) means the voltage on the transformer’s high-voltage side.

Substituting the current into the heating equation gives

\[ P_{\rm loss} =\frac{P_{\rm d}^2R_\ell}{V_{\rm r}^2} \]

This is the direct answer to a transmission-loss question when the delivered power, receiving-end voltage, and line resistance are known.

If the receiving-end voltage isn’t given, you’ll need additional information to find the current. Delivered power by itself isn’t enough.

Assumptions behind these equations

We’ll use the idealised HSC model of a single two-wire transmission path with a resistive load.

All AC voltages and currents are RMS values, voltage and current are in phase, and the power factor is one. Transformers are ideal unless stated otherwise, and the line has fixed resistance with negligible inductive and capacitive effects.

The total resistance includes the outward and return conductors. If each wire has resistance \(1.5\ \Omega\), the total line resistance is \(3.0\ \Omega\), not \(1.5\ \Omega\).

We take positive current as travelling from the sending end towards the load along the outgoing conductor. Voltage drop and resistive power loss are reported as positive magnitudes.

02Why the voltage measurement matters

Imagine that a load receives 1,000 W.

At a receiving voltage of 100 V, the line must carry

\[ I_\ell=\frac{1000}{100}=10\ \text{A} \]

At a receiving voltage of 500 V, the current would be

\[ I_\ell=\frac{1000}{500}=2.0\ \text{A} \]

Both arrangements deliver exactly the same useful power, but the second carries only one-fifth as much current.

Why does that help?

Voltage describes how much electrical energy is transferred per unit charge. Current describes how much charge passes each second. More energy transferred per coulomb means fewer coulombs per second are needed to supply the same power.

But the wires still resist the movement of charge. Their heating depends on current squared, so reducing the current to one-fifth reduces the resistive loss to one twenty-fifth.

There’s an important condition: we held the delivered power constant.

If you simply increase the source voltage without controlling what happens at the load, the current and delivered power may both increase instead. Higher voltage alone doesn’t guarantee lower losses.

03A transmission experiment: What should we actually compare?

Consider a small model transmission system with an adjustable AC source, two conductors, and a purely resistive load.

The following values are illustrative calculations, not measurements from a real experiment.

The apparatus has:

  • A \(24\ \Omega\) load resistor at the receiving end.
  • Two connecting conductors, each represented by \(1.0\ \Omega\) of resistance.
  • An ammeter connected in series with the outgoing conductor.
  • Voltmeters connected across the sending-end terminals and across the receiving load.

The total transmission-line resistance is therefore \(2.0\ \Omega\).

An ammeter measures the current through the wire. The voltmeters measure the potential differences at the two ends. Together, these measurements let us calculate delivered power, voltage drop, and resistive loss.

The first test: Double the source voltage

Adjust the source until the load receives 24 V.

Using Ohm’s law, the current through the \(24\ \Omega\) load is

\[ I=\frac{V}{R} =\frac{24}{24} =1.0\ \text{A} \]

The load receives

\[ P_{\rm d}=VI =24(1.0) =24\ \text{W} \]

The transmission conductors lose

\[ P_{\rm loss}=(1.0)^2(2.0)=2.0\ \text{W} \]

Their voltage drop is \(IR_\ell=2.0\ \text{V}\). The source therefore supplies 26 V to maintain 24 V across the load.

Now double the source voltage to 52 V.

Predict what happens to the wire heating. Does it decrease because the voltage is higher?

No. The total circuit resistance is still \(26\ \Omega\), so the current doubles to 2.0 A.

The load now receives 48 V and 96 W. The conductors lose 8.0 W, four times their original heating loss.

The problem with this test is that we changed two things: the source voltage and the power delivered to the load.

It doesn’t isolate the benefit of transmitting a fixed amount of useful power at a higher voltage.

The revised test: Keep the useful power fixed

Place an ideal 1:2 step-up transformer near the source and an ideal 2:1 step-down transformer near the load.

The step-up transformer raises the voltage before the long conductors. The step-down transformer reduces it again immediately before the \(24\ \Omega\) load.

Adjust the source so that the load still receives 24 V and 24 W.

The receiving transformer’s high-voltage side must now operate at 48 V. Because the transformer is ideal, the line current is

\[ I_\ell=\frac{24\ \text{W}}{48\ \text{V}} =0.50\ \text{A} \]

The line loss becomes

\[ P_{\rm loss}=(0.50)^2(2.0) =0.50\ \text{W} \]

The line drops 1.0 V, so its sending-end voltage is 49 V. The ideal sending transformer therefore requires 24.5 V on its low-voltage side.

Comparing the predicted readings

ArrangementLoad powerLine currentLine loss
Direct connection, 26 V source24 W1.0 A2.0 W
Direct connection, 52 V source96 W2.0 A8.0 W
Ideal transformers, 24 W delivered24 W0.50 A0.50 W

These are calculated readings for the stated ideal model.

The revised arrangement makes a fairer comparison. The load still receives 24 W, but the higher transmission voltage reduces line heating from 2.0 W to 0.50 W.

It also reveals why transformers matter. They change the voltage and current between parts of the circuit without changing the transmitted power in the ideal model.

A real experiment could test these predictions using suitably rated equipment. Deviations could arise from transformer losses, changing conductor resistance, and non-resistive circuit behaviour. These would need to be measured or controlled before claiming that the observed difference came entirely from transmission-line resistance.

04Worked example: Calculate the loss for a specified delivered power

A workshop receives \(3.0\ \text{kW}\) at \(250\ \text{V}\) directly from a two-wire transmission line. The combined resistance of the two wires is \(2.0\ \Omega\).

Calculate the line current, power lost in the line, sending-end voltage, and power supplied to the line. Assume the load is resistive and the source voltage can be adjusted to maintain the stated delivery.

Step 1

\[ P_{\rm d}=3.0\times10^3 =3000\ \text{W} \]

Step 2

The load is connected directly to the line, so its current is also the line current.

\[ \begin{aligned} I_\ell&=\frac{P_{\rm d}}{V_{\rm r}}\\ &=\frac{3000}{250}\\ &=12\ \text{A} \end{aligned} \]

Step 3

\[ \begin{aligned} P_{\rm loss}&=I_\ell^2R_\ell\\ &=(12)^2(2.0)\\ &=288\ \text{W} \end{aligned} \]

The wires convert 288 J of electrical energy into heat every second.

Step 4

For this resistive model, the voltage drop across the wires is

\[ \begin{aligned} \Delta V&=I_\ell R_\ell\\ &=(12)(2.0)\\ &=24\ \text{V} \end{aligned} \]

The sending-end voltage must therefore be

\[ V_{\rm s}=250+24=274\ \text{V} \]

Step 5

\[ \begin{aligned} P_{\rm s}&=P_{\rm d}+P_{\rm loss}\\ &=3000+288\\ &=3288\ \text{W} \end{aligned} \]

We can check using the sending-end voltage:

\[ P_{\rm s}=V_{\rm s}I_\ell =274(12)=3288\ \text{W} \]

The two methods agree.

The source must deliver 3,288 W into the transmission line so that 3,000 W reaches the workshop.

Notice the distinction: the delivered power is 3,000 W, not 3,288 W. Using the sending-end voltage of 274 V with the delivered power in \(I=P/V\) would give the wrong current because those two quantities belong to different ends of the line.

05Worked example: Include a receiving-end transformer

A transmission line supplies \(6.0\ \text{kW}\) to a resistive load operating at \(300\ \text{V}\). An ideal step-down transformer is installed at the receiving end, with a primary-to-secondary turns ratio of 8:1.

The total resistance of the transmission line is \(4.0\ \Omega\).

Calculate the transmission-line loss and the power required at the sending end. Compare this with supplying the load directly at 300 V, keeping the delivered power unchanged.

Step 1

The load receives 6,000 W at 300 V.

\[ I_{\rm load}=\frac{6000}{300} =20\ \text{A} \]

The transformer’s secondary carries 20 A, but that’s not the transmission-line current.

Step 2

For an ideal transformer,

\[ \frac{V_{\rm p}}{V_{\rm sec}} =\frac{N_{\rm p}}{N_{\rm sec}} \]

Here, \(V_{\rm p}\) and \(V_{\rm sec}\) are the transformer’s primary and secondary voltages, while \(N_{\rm p}\) and \(N_{\rm sec}\) are their respective coil turns.

The 8:1 ratio gives the receiving-end transmission voltage:

\[ V_{\rm r}=8(300)=2400\ \text{V} \]

Because the transformer is ideal, the power entering its primary equals the power delivered by its secondary.

Therefore,

\[ \begin{aligned} I_\ell&=\frac{6000}{2400}\\ &=2.5\ \text{A} \end{aligned} \]

Step 3

\[ \begin{aligned} P_{\rm loss}&=I_\ell^2R_\ell\\ &=(2.5)^2(4.0)\\ &=25\ \text{W} \end{aligned} \]

Only 25 W is lost in the transmission line.

The line’s voltage drop is

\[ \Delta V=(2.5)(4.0)=10\ \text{V} \]

So its sending-end voltage and power are

\[ \begin{aligned} V_{\rm s}&=2400+10\\ &=2410\ \text{V}\\ P_{\rm s}&=6000+25\\ &=6025\ \text{W} \end{aligned} \]

Step 4

Without the transformer, the 20 A load current would flow through the line.

\[ \begin{aligned} P_{\rm loss,direct} &=(20)^2(4.0)\\ &=1600\ \text{W} \end{aligned} \]

The transformer arrangement reduces the line loss from 1,600 W to 25 W, a factor of 64.

The delivered power hasn’t changed. The current through the long line has.

This comparison assumes the sending source is adjusted as required to keep the load at 300 V. It doesn’t assume the same sending-end voltage in the two arrangements.

06A decision rule for transmission-loss questions

The most reliable method is to locate the resistance first, then determine the current flowing through that particular resistance.

Information providedCorrect first move
Delivered power and receiving-end line voltageCalculate \(I_\ell=P_{\rm d}/V_{\rm r}\).
Delivered power and load voltage, with no transformerThe line and load currents are equal.
Delivered power and load voltage, with an ideal receiving transformerUse the turns ratio to find the high-side receiving voltage, then calculate line current.
Delivered power and sending-end voltage onlyAccount for the voltage drop before finding line current.
Sending-end power and line currentCalculate \(I_\ell^2R_\ell\), then subtract the loss to find delivered power.

For a simple resistive line,

\[ V_{\rm s}=V_{\rm r}+I_\ell R_\ell \]

and energy conservation gives

\[ P_{\rm s}=P_{\rm d}+P_{\rm loss} \]

The second equation is also a useful diagnostic. In this ideal model, power lost in the wires must equal the difference between power entering and leaving the transmission path.

Don’t automatically use the same current on both sides of a transformer. And don’t count a transformer’s energy loss as transmission-wire heating unless the question explicitly asks for total system losses.

One important limitation

These equations describe a simple resistive circuit. Real transmission systems involve three-phase AC, reactive effects, transformer inefficiency, and conductor resistance that changes with temperature.

The underlying idea survives: the heating in a particular conductor depends on the square of the current through it.

But real AC power calculations must also account for power factor and the actual circuit arrangement. Don’t treat \(P=VI\) as a universal real-power equation for every AC system.

07Questions and solutions

Question 1

A two-wire transmission line supplies \(2.0\ \text{kW}\) at \(200\ \text{V}\) to a resistive load. The total line resistance is \(1.2\ \Omega\).

Calculate:

a. The transmission-line current.

b. The power lost in the line.

c. The power required at the sending end.

Assume the source maintains the stated receiving voltage.

Solution 1

The line carries 10 A, loses 120 W as heat, and requires 2,120 W at the sending end.

Part a: Convert the delivered power into watts and divide by the receiving voltage.

\[ \begin{aligned} I_\ell&=\frac{P_{\rm d}}{V_{\rm r}}\\ &=\frac{2000}{200}\\ &=10\ \text{A} \end{aligned} \]

Part b: Use the resistance of the complete transmission path.

\[ \begin{aligned} P_{\rm loss}&=I_\ell^2R_\ell\\ &=(10)^2(1.2)\\ &=120\ \text{W} \end{aligned} \]

Part c: Add the loss to the delivered power.

\[ \begin{aligned} P_{\rm s}&=P_{\rm d}+P_{\rm loss}\\ &=2000+120\\ &=2120\ \text{W} \end{aligned} \]

The load receives 2,000 W while the line converts 120 W into heat.

A common mistake is to report 120 W as the total sending-end power. It is only the additional power needed to overcome the line resistance.

Question 2

A power source supplies a resistive load receiving \(3.2\ \text{kW}\) at \(200\ \text{V}\).

Electricity passes through the following components in order:

  1. A short, low-voltage two-wire feeder with total resistance \(0.50\ \Omega\).
  2. An ideal 1:4 step-up transformer.
  3. A long transmission line with total resistance \(8.0\ \Omega\).
  4. An ideal 4:1 step-down transformer.
  5. The load.

Assume all transformer ratios describe primary-to-secondary voltage ratios, the source can be adjusted, and the load continues to receive its specified power.

a. Calculate the power lost in each resistive section.

b. Determine the voltage and power required at the source.

c. An engineer proposes moving the step-up transformer to before the short feeder, so both resistive sections operate on the high-voltage side. Calculate the new total resistive loss and explain why it changes.

Solution 2

Both resistive sections initially lose 128 W, giving a total loss of 256 W. The source must supply 216 V and 3,456 W. Moving the step-up transformer before the short feeder reduces total resistive loss to 136 W.

The surprising result is that the short \(0.50\ \Omega\) feeder initially loses as much power as the much more resistive \(8.0\ \Omega\) transmission line.

Part a: Follow the current backwards from the load.

The load current is

\[ I_{\rm load}=\frac{3200}{200} =16\ \text{A} \]

The step-down transformer has a 4:1 primary-to-secondary voltage ratio.

Its high-voltage primary therefore operates at

\[ V_{\rm r}=4(200)=800\ \text{V} \]

For an ideal transformer, input and output powers are equal. Thus the long-line current is

\[ I_{\rm high}=\frac{3200}{800} =4.0\ \text{A} \]

The loss in the long line is

\[ \begin{aligned} P_{\rm long}&=I_{\rm high}^2R\\ &=(4.0)^2(8.0)\\ &=128\ \text{W} \end{aligned} \]

Now consider the short feeder.

It sits before the step-up transformer, so it carries the low-voltage current of 16 A.

\[ \begin{aligned} P_{\rm short}&=(16)^2(0.50)\\ &=128\ \text{W} \end{aligned} \]

The total loss is

\[ P_{\rm loss}=128+128 =256\ \text{W} \]

The short feeder has one-sixteenth of the long line’s resistance but four times its current. Squaring that current produces the same heating.

Part b: Work backwards to the source.

The long line loses 32 V:

\[ \Delta V_{\rm long} =(4.0)(8.0)=32\ \text{V} \]

The step-up transformer’s high-voltage output must therefore be

\[ V_{\rm high,s}=800+32 =832\ \text{V} \]

Its 1:4 ratio means its low-voltage input must be

\[ V_{\rm low}=\frac{832}{4} =208\ \text{V} \]

The short feeder carries 16 A and loses

\[ \Delta V_{\rm short} =(16)(0.50)=8.0\ \text{V} \]

Therefore, the source voltage is

\[ V_{\rm source}=208+8.0 =216\ \text{V} \]

The source current is 16 A, giving

\[ \begin{aligned} P_{\rm source}&=VI\\ &=216(16)\\ &=3456\ \text{W} \end{aligned} \]

This agrees with the power balance:

\[ 3200+128+128=3456\ \text{W} \]

Part c: Move the step-up transformer.

After the transformer is relocated, both sections carry the high-voltage current of 4.0 A.

The combined resistance remains

\[ R_{\rm total}=0.50+8.0 =8.5\ \Omega \]

But the heating becomes

\[ \begin{aligned} P_{\rm loss,new} &=(4.0)^2(8.5)\\ &=136\ \text{W} \end{aligned} \]

The source now needs to supply

\[ P_{\rm source,new}=3200+136 =3336\ \text{W} \]

Moving the transformer reduces the loss by

\[ 256-136=120\ \text{W} \]

The tempting approach is to combine both resistances first and assume the same current passes through them. That fails in the original arrangement because a transformer separates the two resistive sections.

The transformer is ideal, so it doesn’t destroy power. It changes the current flowing through each section. Its position therefore determines where the resistive heating occurs.

Question 3

A transmission system delivers \(5.00\ \text{kW}\) at \(250\ \text{V}\) to a resistive load through an ideal receiving-end step-down transformer with a 5:1 primary-to-secondary turns ratio.

The transmission line has an unknown resistance.

Measurements show that:

  • The sending-end line voltage is \(1260\ \text{V}\).
  • The electrical input power to the non-ideal sending transformer is \(5.20\ \text{kW}\).

Assume there are no other losses.

a. Determine the total transmission-line resistance.

b. Calculate the power lost in the transmission line.

c. Determine the power lost in the sending transformer and its efficiency.

d. A student claims that the transmission line must lose 200 W because the difference between source input power and delivered power is 200 W. Explain the error.

Solution 3

The line resistance is \(2.5\ \Omega\), the line loses 40 W, and the sending transformer loses 160 W. The transformer’s efficiency is approximately 96.9%.

The 200 W difference is the combined loss of the transformer and line, not the line loss alone.

Part a: Determine the line current and resistance.

The ideal receiving transformer has a 5:1 voltage ratio.

Its primary voltage is

\[ V_{\rm r}=5(250) =1250\ \text{V} \]

The line current is

\[ I_\ell=\frac{5000}{1250} =4.0\ \text{A} \]

The measured sending voltage is 1260 V, so the line voltage drop is

\[ \Delta V=1260-1250 =10\ \text{V} \]

Applying Ohm’s law,

\[ \begin{aligned} R_\ell&=\frac{\Delta V}{I_\ell}\\ &=\frac{10}{4.0}\\ &=2.5\ \Omega \end{aligned} \]

Part b: Calculate the line loss.

\[ \begin{aligned} P_{\rm loss,line} &=I_\ell^2R_\ell\\ &=(4.0)^2(2.5)\\ &=40\ \text{W} \end{aligned} \]

The line converts 40 J of electrical energy into heat each second.

Part c: Separate the transformer loss.

The power entering the line from the sending transformer is

\[ P_{\rm line,in}=1260(4.0) =5040\ \text{W} \]

But the sending transformer’s input is 5,200 W.

Therefore,

\[ \begin{aligned} P_{\rm loss,transformer} &=5200-5040\\ &=160\ \text{W} \end{aligned} \]

The transformer’s efficiency is

\[ \begin{aligned} \eta&=\frac{P_{\rm out}}{P_{\rm in}}\times100\%\\ &=\frac{5040}{5200}\times100\%\\ &\approx96.9\% \end{aligned} \]

Here, \(\eta\) represents transformer efficiency, not the efficiency of the entire transmission system.

Part d: Explain the student’s error.

The student has correctly identified the total power difference:

\[ 5200-5000=200\ \text{W} \]

But the 200 W includes losses in two separate components.

\[ P_{\rm total\ loss}=160+40 =200\ \text{W} \]

A wattmeter before the first transformer measures power entering that transformer. It doesn’t measure power entering the transmission line.

The mistake is ignoring the boundary between the transformer and the line. To calculate transmission-wire heating, use the current and resistance of the line itself.

Question 4

A fixed \(12\ \Omega\) resistive load is connected to a source through a transmission line.

Initially, the total line resistance is \(2.0\ \Omega\), and the source supplies \(140\ \text{V}\).

Later, the line resistance increases to \(8.0\ \Omega\). The load resistance remains \(12\ \Omega\).

Consider two operating conditions after the resistance increase:

  • Condition A: A voltage regulator adjusts the source to maintain the original delivered power and load voltage.
  • Condition B: The source stays fixed at 140 V.

a. Calculate the original delivered power and line loss.

b. For each condition, calculate the line current, delivered power, line loss, and sending-end power.

c. Which condition produces more line heating? Which has higher transmission efficiency? Explain why these answers aren’t necessarily the same decision.

Solution 4

Initially, the load receives 1,200 W and the line loses 200 W. After the resistance increase, Condition A loses 800 W while delivering 1,200 W; Condition B loses 392 W while delivering only 588 W.

Both later conditions have a transmission efficiency of 60%. Condition B heats the wire less because it supplies substantially less useful power.

Part a: Calculate the original state.

The load and transmission-line resistances are in series, giving

\[ R_{\rm total}=12+2.0 =14\ \Omega \]

The initial current is

\[ I=\frac{140}{14} =10\ \text{A} \]

The load receives

\[ \begin{aligned} P_{\rm d}&=I^2R_{\rm load}\\ &=(10)^2(12)\\ &=1200\ \text{W} \end{aligned} \]

The line loses

\[ P_{\rm loss}=(10)^2(2.0) =200\ \text{W} \]

The sending-end power is \(140(10)=1400\ \text{W}\).

Part b: Compare the two later conditions.

Under Condition A, the load must still receive 1,200 W.

Because its resistance remains \(12\ \Omega\), the current must remain 10 A.

The new line loss is

\[ P_{\rm loss,A}=(10)^2(8.0) =800\ \text{W} \]

The line voltage drop is 80 V, so the source must provide

\[ V_{\rm source,A}=120+80 =200\ \text{V} \]

The sending-end power becomes

\[ P_{\rm s,A}=200(10) =2000\ \text{W} \]

Under Condition B, the source remains at 140 V. The total circuit resistance is now

\[ R_{\rm total}=12+8.0 =20\ \Omega \]

The current falls to

\[ I_{\rm B}=\frac{140}{20} =7.0\ \text{A} \]

The load receives

\[ \begin{aligned} P_{\rm d,B}&=(7.0)^2(12)\\ &=588\ \text{W} \end{aligned} \]

The line loses

\[ \begin{aligned} P_{\rm loss,B}&=(7.0)^2(8.0)\\ &=392\ \text{W} \end{aligned} \]

The sending-end power is

\[ P_{\rm s,B}=140(7.0) =980\ \text{W} \]

Part c: Compare heating and efficiency.

Condition A produces more absolute line heating:

\[ 800\ \text{W}>392\ \text{W} \]

However, efficiency compares useful power with supplied power.

For Condition A,

\[ \eta_{\rm A}=\frac{1200}{2000}\times100\% =60\% \]

For Condition B,

\[ \eta_{\rm B}=\frac{588}{980}\times100\% =60\% \]

Neither condition is more efficient.

This result makes sense from the resistance ratio. After the change, both conditions have the same \(12\ \Omega\) load and \(8.0\ \Omega\) line resistance.

For an entirely resistive series circuit,

\[ \eta=\frac{R_{\rm load}}{R_{\rm load}+R_\ell} \]

So the efficiency is \(12/20=60\%\), regardless of the source voltage.

The tempting conclusion is that Condition B is better simply because it wastes fewer watts. But its load also receives less than half the intended power.

If the load genuinely needs 1,200 W, Condition B fails to meet the requirement. Condition A meets it at the cost of higher absolute heating.

The meaningful comparison depends on what must stay fixed: useful output, source voltage, or load resistance.

Question 5

An ideal AC source maintains a fixed sending-end voltage of \(120\ \text{V}\). It supplies a receiving circuit through a two-wire transmission line with total resistance \(4.0\ \Omega\).

An operator can select three arrangements:

  • Arrangement A: An \(8.0\ \Omega\) resistor connected directly across the receiving terminals.
  • Arrangement B: A \(2.0\ \Omega\) resistor connected directly across the receiving terminals.
  • Arrangement C: The same \(2.0\ \Omega\) resistor connected through an ideal 2:1 step-down transformer at the receiving end, with the primary connected to the line.

Assume purely resistive loads, ideal transformer behaviour, fixed line resistance, and no other losses.

a. For each arrangement, calculate the transmission-line current, power delivered to the resistor, and power lost in the line.

b. Explain how the source can deliver the same useful power at the same sending voltage while producing two different line currents and heating losses.

c. A student is told only that the delivered power is 800 W, the sending voltage is 120 V, and the line resistance is \(4.0\ \Omega\). The student calculates \(I=800/120\). Explain why this does not determine the correct line current.

d. The operator wants to deliver 1.00 kW instead. Could any ideal transformer turns ratio make this possible without changing the source voltage or line resistance? Demonstrate your conclusion mathematically.

Solution 5

All three arrangements deliver 800 W, but Arrangement B loses 1,600 W in the line, while A and C each lose only 400 W.

The final request is impossible: no ideal transformer can make this fixed source and line deliver 1.00 kW. The maximum possible delivered power in this model is 900 W.

The key is that the sending-end voltage doesn’t uniquely determine the receiving-end voltage. The load and transformer arrangement determine the current, which then determines the line voltage drop.

Part a: Analyse all three arrangements.

For Arrangement A, the line resistance and \(8.0\ \Omega\) load are in series.

The total resistance is

\[ R_{\rm total}=4.0+8.0 =12\ \Omega \]

The line current is

\[ I_{\rm A}=\frac{120}{12} =10\ \text{A} \]

Power delivered to the load:

\[ \begin{aligned} P_{\rm d,A}&=I_{\rm A}^2R_{\rm load}\\ &=(10)^2(8.0)\\ &=800\ \text{W} \end{aligned} \]

Power lost in the line:

\[ P_{\rm loss,A}=(10)^2(4.0) =400\ \text{W} \]

The source supplies 1,200 W.

Now consider Arrangement B.

The total resistance becomes

\[ R_{\rm total}=4.0+2.0 =6.0\ \Omega \]

The current is

\[ I_{\rm B}=\frac{120}{6.0} =20\ \text{A} \]

The delivered power is

\[ \begin{aligned} P_{\rm d,B}&=(20)^2(2.0)\\ &=800\ \text{W} \end{aligned} \]

But the line loss is

\[ \begin{aligned} P_{\rm loss,B}&=(20)^2(4.0)\\ &=1600\ \text{W} \end{aligned} \]

The source supplies 2,400 W.

Both loads receive 800 W, even though one draws twice as much current from the source.

Arrangement C is different because the transformer changes how the \(2.0\ \Omega\) resistor appears to the transmission line.

For the ideal 2:1 step-down transformer,

\[ V_{\rm p}=2V_{\rm sec} \]

and

\[ I_{\rm p}=\frac{I_{\rm sec}}{2} \]

Since resistance is voltage divided by current, the effective resistance seen at the primary is

\[ \begin{aligned} R_{\rm effective} &=\frac{2V_{\rm sec}}{I_{\rm sec}/2}\\ &=4R_{\rm load}\\ &=8.0\ \Omega \end{aligned} \]

This is the resistance reflected through the ideal transformer. It doesn’t mean the physical \(2.0\ \Omega\) resistor has changed resistance.

From the source’s perspective, Arrangement C behaves like a \(4.0\ \Omega\) line resistance in series with an \(8.0\ \Omega\) effective load.

Therefore,

\[ I_{\rm C}=\frac{120}{4.0+8.0} =10\ \text{A} \]

The receiving-end high-side voltage is

\[ V_{\rm r}=120-(10)(4.0) =80\ \text{V} \]

The transformer’s secondary voltage is 40 V. The \(2.0\ \Omega\) load therefore carries 20 A.

The load power is

\[ P_{\rm d,C}=40(20) =800\ \text{W} \]

The transmission-line loss is

\[ P_{\rm loss,C}=(10)^2(4.0) =400\ \text{W} \]

The results are:

ArrangementLine currentDelivered powerLine loss
A: \(8.0\ \Omega\), direct10 A800 W400 W
B: \(2.0\ \Omega\), direct20 A800 W1,600 W
C: \(2.0\ \Omega\), transformer10 A800 W400 W

Part b: Explain the two possible operating conditions.

In Arrangement A, the 10 A line current causes a 40 V drop across the line.

The load receives 80 V, giving

\[ P_{\rm d}=80(10)=800\ \text{W} \]

In Arrangement B, the 20 A line current causes an 80 V drop across the line.

The load receives only 40 V, giving

\[ P_{\rm d}=40(20)=800\ \text{W} \]

One circuit delivers 800 W using a higher receiving voltage and lower current. The other delivers the same power using a lower receiving voltage and higher current.

The sending voltage is identical in both cases.

The loads are different, so the currents don’t have to be the same.

Part c: Why dividing by 120 V fails.

The student has mixed quantities from different ends of the transmission line.

The 800 W refers to power at the receiving load, whereas 120 V is the sending-end voltage.

The correct relationship is

\[ P_{\rm d}=V_{\rm r}I_\ell \]

For a resistive transmission line,

\[ V_{\rm r}=V_{\rm s}-I_\ell R_\ell \]

Substituting the fixed sending voltage and line resistance gives

\[ P_{\rm d}=(120-4I_\ell)I_\ell \]

Using the 800 W delivered power,

\[ 800=120I_\ell-4I_\ell^2 \]

Rearranging and dividing by four,

\[ I_\ell^2-30I_\ell+200=0 \]

Factorising,

\[ (I_\ell-10)(I_\ell-20)=0 \]

Therefore,

\[ I_\ell=10\ \text{A} \quad\text{or}\quad I_\ell=20\ \text{A} \]

Both solutions are physically possible for suitable resistive loads.

So knowing delivered power, sending voltage, and line resistance doesn’t always give a unique operating current. You may also need the load resistance, receiving-end voltage, or transformer arrangement.

Part d: Establish the maximum deliverable power.

The source voltage is fixed at 120 V, and the total line resistance is fixed at \(4.0\ \Omega\).

For any line current \(I_\ell\), the sending-end power is

\[ P_{\rm s}=(120\ \text{V})I_\ell \]

The resistive loss is

\[ P_{\rm loss}=(4.0\ \Omega)I_\ell^2 \]

So the delivered power must satisfy

\[ P_{\rm d}=P_{\rm s}-P_{\rm loss} \]

or

\[ P_{\rm d} =(120\ \text{V})I_\ell -(4.0\ \Omega)I_\ell^2 \]

This is a downward-opening quadratic relationship between delivered power and current.

Completing the square gives

\[ \begin{aligned} P_{\rm d} ={}&900\ \text{W}\\ &-(4.0\ \Omega) (I_\ell-15\ \text{A})^2 \end{aligned} \]

The squared term cannot be negative.

Therefore, the delivered power cannot exceed 900 W.

The maximum occurs when

\[ I_\ell=15\ \text{A} \]

At that current, the line voltage drop is

\[ \Delta V=(15)(4.0) =60\ \text{V} \]

The receiving voltage is also 60 V, and the load receives

\[ P_{\rm d,max}=60(15) =900\ \text{W} \]

A suitable ideal transformer can make the effective load resistance equal to \(4.0\ \Omega\), achieving this theoretical maximum in the model.

But no ideal transformer can exceed it.

This is the deeper limitation of transmission design.

An ideal transformer can change the effective load resistance seen by the source. It can select a more favourable operating current and reduce waste compared with a poor arrangement.

But it cannot create electrical power or remove the energy constraint imposed by the source voltage and line resistance.

At the maximum-power operating point, the line itself loses 900 W. Maximum power delivery therefore does not mean maximum efficiency.

08What to take into the next transmission problem

When a question specifies delivered power, identify the receiving-end voltage before calculating current. Then use that current in \(I^2R\) for the particular conductors being considered.

If a transformer lies between the load and the line, transform the voltage and current first. If only the sending voltage is known, account for the voltage drop instead of treating sending and receiving voltages as equal.

That distinction separates three different calculations: useful power delivered to the load, energy lost as heat in the conductors, and total power required from the source.

For the wider reasoning behind raising transmission voltage, choosing transformer ratios, and reducing current over long distances, continue with High-Voltage Electricity Transmission for HSC Physics.