Why Doubling Transmission Voltage Can Quarter Power Loss

Learn why doubling transmission voltage reduces resistive power loss to one-quarter when transmitted power and cable resistance stay constant. Explore worked calculations, a controlled experiment, and challenging HSC Physics questions that reveal when the rule doesn't apply.

Two transmission lines carry the same electrical power, but one operates at twice the voltage. If the first line wastes 80 W as heat, would you expect the second to waste 40 W, 20 W, or something else?

It wastes just 20 W, one-quarter as much, provided the power entering the line stays constant and the line resistance doesn’t change. Doubling the transmission voltage halves the current, and resistive power loss depends on the square of that current.

The interesting part is what happens when those conditions aren’t met. Simply doubling a supply voltage can sometimes increase heating instead. A controlled experiment shows why.

01Why current, rather than transmission voltage, determines cable heating

Imagine a transmission line as a very long electrical conductor connecting a power station to equipment somewhere else.

The conductor has electrical resistance. As current flows, some electrical energy is converted into thermal energy within the metal. This is resistive heating, also called Joule heating.

There are two different voltages to keep separate:

  • Transmission voltage: the potential difference between the two conductors at the sending end.
  • Cable voltage drop: the potential difference lost along the resistive transmission path.

A high transmission voltage doesn’t mean that the full voltage is applied across the cable’s resistance.

For a steady circuit with a resistive transmission path, Ohm’s law gives the total cable voltage drop:

\[ V_{\mathrm{drop}}=IR \]

Here:

  • \(V_{\mathrm{drop}}\) is the voltage drop along the complete transmission path, in volts (V).
  • \(I\) is the current through the line, in amperes (A).
  • \(R\) is the combined resistance of the conductors carrying that current, in ohms (\(\Omega\)).

The rate at which electrical energy becomes heat in the conductors is:

\[ P_{\mathrm{loss}}=I^2R \]

\(P_{\mathrm{loss}}\) is the resistive power loss, measured in watts (W).

Notice the square.

If the same cable carries half the current, its heating power becomes:

\[ \begin{aligned} P_{\mathrm{new}} &=\left(\frac{I}{2}\right)^2R\\ &=\frac{I^2R}{4} \end{aligned} \]

So its resistive loss becomes one-quarter of the original value.

You might be thinking of another power equation, \(P=V^2/R\), which seems to say that increasing voltage must increase heating.

That equation is correct. The catch is that \(V\) must be the voltage across the particular resistance producing the heat.

The full transmission voltage is not the voltage across the cable resistance alone. The cable’s own voltage drop is \(IR\), and that becomes smaller when the current decreases.

For a closer look at where the electrical energy goes inside a resistor, see Resistive Heating in HSC Physics: Power and Energy.

02Why doubling voltage halves current only when power is fixed

Voltage tells us how much electrical energy is transferred per unit charge. Current tells us how much charge passes a point each second.

Suppose you need to transfer the same energy every second. If each coulomb transfers twice as much energy, you only need half as many coulombs passing each second.

That is the physical reason higher voltage can reduce the current needed to transfer a given power.

For the basic transmission model, use:

\[ P_{\mathrm{s}}=V_{\mathrm{s}}I \]

where:

  • \(P_{\mathrm{s}}\) is the electrical power entering the transmission line, in watts (W).
  • \(V_{\mathrm{s}}\) is the sending-end transmission voltage, in volts (V).
  • \(I\) is the transmission-line current, in amperes (A).

For AC transmission, these are RMS voltage and current values. The equation assumes voltage and current are in phase, as in the purely resistive model used here.

Rearranging:

\[ I=\frac{P_{\mathrm{s}}}{V_{\mathrm{s}}} \]

If \(P_{\mathrm{s}}\) remains constant, doubling \(V_{\mathrm{s}}\) halves \(I\).

Now substitute this current into the resistive heating equation:

\[ \begin{aligned} P_{\mathrm{loss}}&=I^2R\\ &=\frac{P_{\mathrm{s}}^2R}{V_{\mathrm{s}}^2} \end{aligned} \]

This gives the central relationship:

\[ P_{\mathrm{loss}}\propto\frac{1}{V_{\mathrm{s}}^2} \]

The proportionality applies when the electrical power entering the line and its resistance are both constant.

Doubling the voltage makes the denominator four times larger. Therefore, the resistive loss becomes one-quarter as large.

Worked example: The same power through two transmission voltages

A simplified transmission system sends 240 kW into a cable at 12.0 kV.

The total resistance of the outgoing and return conductors is \(6.0\ \Omega\).

The sending-end voltage is increased to 24.0 kV while the power entering the line remains 240 kW.

Calculate the line current, resistive power loss, and power reaching the receiving equipment in both cases. Assume a purely resistive circuit and no transformer losses.

Step 1

Convert the electrical power:

\(240\ \mathrm{kW}=240\,000\ \mathrm{W}\).

Using \(P_{\mathrm{s}}=V_{\mathrm{s}}I\):

\[ \begin{aligned} I_1&=\frac{240\,000}{12\,000}\\ &=20.0\ \mathrm{A} \end{aligned} \]

Step 2

\[ \begin{aligned} P_{\mathrm{loss},1} &=I_1^2R\\ &=(20.0)^2(6.0)\\ &=2400\ \mathrm{W} \end{aligned} \]

The cable wastes 2.40 kW as heat.

The power reaching the load is therefore:

\[ \begin{aligned} P_{\mathrm{r},1} &=240.0-2.40\\ &=237.6\ \mathrm{kW} \end{aligned} \]

Step 3

The sending-end power stays at 240 kW.

\[ \begin{aligned} I_2&=\frac{240\,000}{24\,000}\\ &=10.0\ \mathrm{A} \end{aligned} \]

The current has halved.

Now calculate the line loss:

\[ \begin{aligned} P_{\mathrm{loss},2} &=(10.0)^2(6.0)\\ &=600\ \mathrm{W}\\ &=0.600\ \mathrm{kW} \end{aligned} \]

The power reaching the receiving equipment is:

\[ \begin{aligned} P_{\mathrm{r},2} &=240.0-0.600\\ &=239.4\ \mathrm{kW} \end{aligned} \]

Step 4

QuantityAt 12.0 kVAt 24.0 kV
Sending-end power240 kW240 kW
Line current20.0 A10.0 A
Cable resistance6.0 Ω6.0 Ω
Resistive loss2.40 kW0.600 kW
Power reaching load237.6 kW239.4 kW

The sending-end power hasn’t increased. The second system simply wastes less of it.

The lower-current system delivers an additional 1.80 kW to the receiving equipment because its line heating is smaller.

There is another consequence. The cable voltage drop falls from:

\[ V_{\mathrm{drop},1} =(20.0)(6.0)=120\ \mathrm{V} \]

to:

\[ V_{\mathrm{drop},2} =(10.0)(6.0)=60\ \mathrm{V} \]

The voltage drop halves, but the heating loss quarters.

That’s because voltage drop depends on \(I\), while resistive power loss depends on \(I^2\).

03An experiment that seems to contradict the quarter-loss rule

Suppose you want to demonstrate the effect of transmission voltage using a small AC circuit.

An obvious first experiment would be to connect a resistor through a length of resistive cable, measure its heating, then double the supply voltage without changing anything else.

Would the cable heating fall to one-quarter?

No. In this arrangement, it actually increases fourfold.

This isn’t a failure of the physics. It’s a failure to control the correct variable.

The apparatus

Picture an idealised, isolated, low-voltage AC supply on the left of a laboratory bench.

It feeds a transformer with a selectable output voltage. The transformer’s output connects to a pair of conductors running towards a resistive load at the right.

The outgoing conductor and return conductor each have a resistance of \(0.25\ \Omega\). Their combined resistance is:

\[ R=0.25+0.25=0.50\ \Omega \]

An ammeter is connected in series immediately after the transformer to measure line current.

One voltmeter measures the RMS sending-end voltage across the two conductors. Another measures the RMS voltage across the receiving load.

The load resistance can be adjusted independently.

We will calculate what the meters should show, rather than claim these are readings from an actual experiment.

The model assumes an ideal transformer, purely resistive components, steady operation, and accurate RMS measurements.

Worked example: Why doubling voltage can quadruple heating

The experimental circuit has a fixed receiving-load resistance of \(9.5\ \Omega\) and a combined cable resistance of \(0.50\ \Omega\).

The sending-end voltage is increased from 20.0 V to 40.0 V without changing either resistance.

Calculate the current, resistive cable loss, and power entering the line at each voltage.

Step 1

The cable and load resistances are in series:

\[ \begin{aligned} R_{\mathrm{total}} &=9.5+0.50\\ &=10.0\ \Omega \end{aligned} \]

Using Ohm’s law at 20.0 V:

\[ \begin{aligned} I_1&=\frac{20.0}{10.0}\\ &=2.00\ \mathrm{A} \end{aligned} \]

At 40.0 V:

\[ \begin{aligned} I_2&=\frac{40.0}{10.0}\\ &=4.00\ \mathrm{A} \end{aligned} \]

The current doubles because the total circuit resistance is unchanged.

Step 2

Only the cable’s \(0.50\ \Omega\) resistance belongs in the line-loss calculation.

At 20.0 V:

\[ \begin{aligned} P_{\mathrm{loss},1} &=(2.00)^2(0.50)\\ &=2.00\ \mathrm{W} \end{aligned} \]

At 40.0 V:

\[ \begin{aligned} P_{\mathrm{loss},2} &=(4.00)^2(0.50)\\ &=8.00\ \mathrm{W} \end{aligned} \]

The resistive loss has increased by a factor of four.

Step 3

At 20.0 V:

\[ P_{\mathrm{s},1}=(20.0)(2.00)=40.0\ \mathrm{W} \]

At 40.0 V:

\[ P_{\mathrm{s},2}=(40.0)(4.00)=160\ \mathrm{W} \]

The power entering the transmission line has increased fourfold.

Step 4

The quarter-loss prediction assumes constant transmitted power. This experiment kept the load resistance constant instead.

Because the source voltage increased while total resistance stayed fixed, both the current and the power drawn from the source increased.

The experiment is answering a different question.

The revised experiment: Hold transmitted power constant

The first design couldn’t separate the effect of higher voltage from the effect of increased power demand.

To test the quarter-loss claim properly, change the experimental procedure.

Keep the cable resistance at \(0.50\ \Omega\), but adjust the receiving load when changing the transmission voltage.

This time, arrange for the power entering the line to remain exactly 120 W in both trials.

At 20.0 V, the required current is:

\[ I_1=\frac{120}{20.0}=6.00\ \mathrm{A} \]

At 40.0 V:

\[ I_2=\frac{120}{40.0}=3.00\ \mathrm{A} \]

Now the current halves.

For the first setting, the cable voltage drop is \(6.00(0.50)=3.00\ \mathrm{V}\), leaving 17.0 V across the load.

The load must therefore be adjusted to approximately \(17.0/6.00=2.83\ \Omega\).

For the second setting, the cable voltage drop is \(3.00(0.50)=1.50\ \mathrm{V}\), leaving 38.5 V across the load. Its required resistance is approximately \(38.5/3.00=12.83\ \Omega\).

The following table contains calculated predictions for this controlled experiment, not recorded measurements.

Quantity20.0 V trial40.0 V trial
Power entering line120 W120 W
Receiving-load resistance2.83 Ω12.83 Ω
Line current6.00 A3.00 A
Cable voltage drop3.00 V1.50 V
Resistive cable loss18.0 W4.50 W
Power reaching load102 W115.5 W

The heating falls from 18.0 W to 4.50 W.

\[ \frac{4.50}{18.0}=\frac14 \]

This is exactly the quarter-loss relationship.

Notice that the receiving power increases from 102 W to 115.5 W, even though both trials send 120 W into the cable.

Energy is conserved:

\[ 120=102+18 \]

and:

\[ 120=115.5+4.50 \]

All powers in these two equations are measured in watts.

The difference is the amount of electrical energy converted to heat before reaching the load.

An actual experiment would also need to account for changes in cable resistance as its temperature changes, transformer losses, and measurement uncertainty. The predicted numbers follow the ideal circuit model.

The important experimental lesson is that two trials can use the same equipment and the same voltage change, yet produce opposite results because they hold different quantities constant.

04A quick way to recognise when the quarter-loss rule applies

The first decision in a transmission calculation isn’t which equation to substitute into. It’s what the problem says stays constant.

What changes?What stays constant?Current responseCable heating response
Voltage doublesPower entering line and cable resistanceHalvesQuarters
Voltage doublesTotal resistance of a simple fixed-load series circuitDoublesQuadruples
Voltage doublesLine current and cable resistanceUnchangedUnchanged

The second row describes a direct supply connected to the same fixed resistive circuit. It doesn’t automatically describe a system with step-up and step-down transformers.

A useful calculation sequence is:

  1. Identify the power, voltage, resistance, or load condition that is being held fixed.
  2. Determine the current actually flowing through the transmission conductors.
  3. Calculate line heating using \(P_{\mathrm{loss}}=I^2R\).
  4. Calculate receiving power separately if it is required.

Don’t substitute the generator’s current, the receiving appliance’s current, or the transformer’s primary current into the line-loss equation without checking whether that is also the transmission-line current.

Where the ideal model stops being exact

Real electricity systems have additional complications.

The simple \(P=VI\) expression applies to DC circuits and to AC circuits where current and voltage are in phase.

For general single-phase AC, real power is:

\[ P=VI\cos\phi \]

Here, \(\phi\) is the phase angle between voltage and current, and \(\cos\phi\) is called the power factor.

This is an extension caveat to the basic resistive model. If the power factor changes, doubling RMS voltage at constant real power does not necessarily halve RMS current.

Real transmission lines also have reactance, transformers have losses, and cable resistance can vary with temperature.

Most importantly, constant sending-end power is not the same condition as constant receiving-end power. If the load must receive exactly the same power after losses, the sending-end power may need to change.

That difference becomes important in harder questions.

05Questions and solutions

Question 1

A simplified transmission line carries 90.0 kW of electrical power at a sending-end voltage of 9.00 kV.

The total cable resistance is \(10.0\ \Omega\).

The voltage is increased to 18.0 kV while the power entering the line and the cable resistance remain unchanged.

Calculate the transmission current and resistive loss before and after the voltage change.

Assume a purely resistive circuit.

Solution 1

The current falls from 10.0 A to 5.00 A, and the resistive loss falls from 1.00 kW to 0.250 kW. Doubling the voltage quarters the loss because the transmitted power and cable resistance stay constant.

Initially:

\[ \begin{aligned} I_1&=\frac{90\,000}{9000}\\ &=10.0\ \mathrm{A} \end{aligned} \]

The initial heating loss is:

\[ \begin{aligned} P_{\mathrm{loss},1} &=(10.0)^2(10.0)\\ &=1000\ \mathrm{W}\\ &=1.00\ \mathrm{kW} \end{aligned} \]

After the voltage doubles:

\[ \begin{aligned} I_2&=\frac{90\,000}{18\,000}\\ &=5.00\ \mathrm{A} \end{aligned} \]

The new heating loss is:

\[ \begin{aligned} P_{\mathrm{loss},2} &=(5.00)^2(10.0)\\ &=250\ \mathrm{W}\\ &=0.250\ \mathrm{kW} \end{aligned} \]

The ratio is \(250/1000=0.25\).

The tempting mistake is to predict that halving current halves the heating. It doesn’t, because heating depends on the square of current.

Question 2

A technician investigates an AC transmission feeder using sending-end and receiving-end voltage measurements.

The power entering the feeder is maintained at 80.0 kW in both trials. The receiving load is adjusted between trials.

All components are modelled as resistive, and the voltages are RMS values.

MeasurementTrial ATrial B
Sending voltage8.00 kV16.0 kV
Line current10.0 A5.00 A
Receiving voltage7.90 kV15.94 kV

Assume the readings are exact for this question.

a. Determine the effective total resistance of the transmission conductors in each trial.

b. Calculate the resistive power loss and receiving power in each trial.

c. A student claims Trial B must have exactly one-quarter the cable heating of Trial A because the voltage doubled. Explain why the claim disagrees with the readings. State what can, and cannot, be concluded about the cause.

Solution 2

Trial A loses 1.00 kW, while Trial B loses 0.300 kW. The loss is not exactly quartered because the measurements imply that the effective cable resistance increased from \(10.0\ \Omega\) to \(12.0\ \Omega\).

Part a: Find the resistances.

Take the voltage drop from sending end to receiving end as positive.

For Trial A:

\[ \begin{aligned} V_{\mathrm{drop},A} &=8000-7900\\ &=100\ \mathrm{V} \end{aligned} \]

Using \(V_{\mathrm{drop}}=IR\):

\[ \begin{aligned} R_A&=\frac{100}{10.0}\\ &=10.0\ \Omega \end{aligned} \]

For Trial B:

\[ \begin{aligned} V_{\mathrm{drop},B} &=16\,000-15\,940\\ &=60.0\ \mathrm{V} \end{aligned} \]

Therefore:

\[ \begin{aligned} R_B&=\frac{60.0}{5.00}\\ &=12.0\ \Omega \end{aligned} \]

The effective line resistance differs between trials.

Part b: Calculate the losses and receiving powers.

For Trial A:

\[ \begin{aligned} P_{\mathrm{loss},A} &=(10.0)^2(10.0)\\ &=1000\ \mathrm{W} \end{aligned} \]

The receiving power is:

\[ \begin{aligned} P_{\mathrm{r},A} &=(7900)(10.0)\\ &=79\,000\ \mathrm{W} \end{aligned} \]

For Trial B:

\[ \begin{aligned} P_{\mathrm{loss},B} &=(5.00)^2(12.0)\\ &=300\ \mathrm{W} \end{aligned} \]

The receiving power is:

\[ \begin{aligned} P_{\mathrm{r},B} &=(15\,940)(5.00)\\ &=79\,700\ \mathrm{W} \end{aligned} \]

Energy conservation agrees with both results:

  • Trial A: 80,000 W entering, 79,000 W received, and 1000 W lost.
  • Trial B: 80,000 W entering, 79,700 W received, and 300 W lost.

Part c: Diagnose the discrepancy.

If the resistance had remained \(10.0\ \Omega\), Trial B would have lost:

\[ (5.00)^2(10.0)=250\ \mathrm{W} \]

Instead, it loses 300 W.

The measured loss ratio is:

\[ \frac{300}{1000}=0.300 \]

So the loss falls to 30% of the original value, rather than 25%.

The current transformation behaves exactly as expected: current halves when the sending voltage doubles at fixed power.

The assumption that fails is constant effective resistance.

A different cable temperature, additional connection resistance, or a change in the effective transmission path could explain the difference. The readings establish the changed resistance but don’t identify its physical cause.

The tempting route is to assume that the same physical cable must have exactly the same resistance in both trials. That’s not guaranteed, and it conflicts with the given voltage-drop measurements.

Question 3

A simplified transmission system operates with:

  • Sending-end voltage: \(420\ \mathrm{V}\)
  • Line current: \(20.0\ \mathrm{A}\)
  • Total line resistance: \(5.00\ \Omega\)

The sending-end voltage is increased to \(840\ \mathrm{V}\).

Unlike the earlier examples, the receiving equipment is adjusted so that the power it receives remains constant.

Assume a purely resistive circuit. The receiving-end voltage must remain greater than half the sending-end voltage in both operating conditions.

a. Determine the original receiving power and line loss.

b. Find the new line current and line loss.

c. Explain why the new loss is not one-quarter of the original. Your calculation may produce two possible currents; explain which is physically allowed by the stated operating condition.

Solution 3

The new line current is 8.00 A, and the line loss falls from 2.00 kW to 0.320 kW. That is 16% of the original loss, not 25%, because the receiving power is held constant rather than the sending power.

Part a: Find the initial receiving power.

The original cable voltage drop is:

\[ \begin{aligned} V_{\mathrm{drop}} &=IR\\ &=(20.0)(5.00)\\ &=100\ \mathrm{V} \end{aligned} \]

The receiving voltage is:

\[ V_{\mathrm{r}}=420-100=320\ \mathrm{V} \]

Therefore:

\[ \begin{aligned} P_{\mathrm{r}} &=V_{\mathrm{r}}I\\ &=(320)(20.0)\\ &=6400\ \mathrm{W} \end{aligned} \]

The original line loss is:

\[ \begin{aligned} P_{\mathrm{loss},1} &=(20.0)^2(5.00)\\ &=2000\ \mathrm{W} \end{aligned} \]

The sending-end power is \(420(20.0)=8400\ \mathrm{W}\), consistent with 6400 W received and 2000 W lost.

Part b: Find the current after increasing the voltage.

The receiving power remains 6400 W.

However, the receiving voltage depends on the unknown current:

\[ V_{\mathrm{r}}=840-5I \]

Use \(P_{\mathrm{r}}=V_{\mathrm{r}}I\):

\[ 6400=I(840-5I) \]

Rearrange:

\[ \begin{aligned} 5I^2-840I+6400&=0\\ I^2-168I+1280&=0\\ (I-8)(I-160)&=0 \end{aligned} \]

There are two mathematical solutions:

\[ I=8.00\ \mathrm{A} \]

or:

\[ I=160\ \mathrm{A} \]

We must test the operating constraint.

At 8.00 A:

\[ V_{\mathrm{r}}=840-5(8)=800\ \mathrm{V} \]

This exceeds half the sending voltage, which is 420 V.

At 160 A:

\[ V_{\mathrm{r}}=840-5(160)=40\ \mathrm{V} \]

This fails the given condition.

Therefore, the required current is 8.00 A.

The new line loss is:

\[ \begin{aligned} P_{\mathrm{loss},2} &=(8.00)^2(5.00)\\ &=320\ \mathrm{W} \end{aligned} \]

Part c: Explain the unexpected loss ratio.

The loss ratio is:

\[ \frac{320}{2000}=0.160 \]

A student might expect the current to halve from 20.0 A to 10.0 A, producing a loss of 500 W.

That prediction assumes the power entering the line stays constant.

But the problem fixes the power arriving at the receiver.

The new sending-end power is:

\[ P_{\mathrm{s},2}=(840)(8.00)=6720\ \mathrm{W} \]

Originally, the source needed to supply 8400 W to deliver 6400 W.

After the voltage increase, it only needs to supply 6720 W to deliver the same 6400 W, because the cable wastes much less energy.

That is why the current falls by more than half.

The second quadratic root is an additional trap: fixed receiving power can mathematically correspond to different combinations of current and receiving voltage in a lossy circuit. The voltage constraint is what selects the intended operating point.

Question 4

A generator supplies \(6.00\ \mathrm{kV}\) and \(20.0\ \mathrm{A}\) of RMS electrical output.

Power travels through two successive sections of resistive transmission line:

  • Section 1 has a total conductor resistance of \(18.0\ \Omega\).
  • Section 2 has a total conductor resistance of \(2.00\ \Omega\).

An ideal step-up transformer has a secondary-to-primary turns ratio of 2:1.

Two arrangements are considered.

Arrangement E: The transformer is placed immediately after the generator, before both cable sections.

Arrangement L: The transformer is placed between Section 1 and Section 2.

The receiving load is adjusted so that the generator still supplies \(6.00\ \mathrm{kV}\) and \(20.0\ \mathrm{A}\) in either arrangement.

Assume ideal transformers, purely resistive circuits, and no other losses.

a. Calculate the current and resistive loss in each cable section for both arrangements.

b. Determine the total cable heating and power delivered to the receiving load in each arrangement.

c. An engineer argues that the transformer should provide the same benefit wherever it is installed because it doubles voltage. Explain the flaw.

Solution 4

Arrangement E delivers 118.0 kW and loses 2.00 kW in the transmission conductors. Arrangement L delivers only 112.6 kW and loses 7.40 kW. Placing the transformer after Section 1 cannot reduce the heating already occurring in that section.

Part a: Calculate currents and section losses.

For Arrangement E, the transformer acts before either line section.

An ideal 2:1 step-up transformer doubles the voltage and halves the current.

Therefore, the transmission voltage is:

\[ V_{\mathrm{s}}=2(6000)=12\,000\ \mathrm{V} \]

The current entering Section 1 is:

\[ I=\frac{20.0}{2}=10.0\ \mathrm{A} \]

The same current passes through Section 2 because the sections are connected in series.

Section 1 loses:

\[ \begin{aligned} P_1&=(10.0)^2(18.0)\\ &=1800\ \mathrm{W} \end{aligned} \]

Section 2 loses:

\[ \begin{aligned} P_2&=(10.0)^2(2.00)\\ &=200\ \mathrm{W} \end{aligned} \]

For Arrangement L, the transformer comes after Section 1.

Section 1 therefore still carries the generator current of 20.0 A.

Its loss is:

\[ \begin{aligned} P_1&=(20.0)^2(18.0)\\ &=7200\ \mathrm{W} \end{aligned} \]

The voltage drop across Section 1 is:

\[ V_{\mathrm{drop},1}=(20.0)(18.0)=360\ \mathrm{V} \]

So the voltage reaching the transformer primary is:

\[ V_{\mathrm{p}}=6000-360=5640\ \mathrm{V} \]

The ideal transformer doubles this to:

\[ V_{\mathrm{secondary}}=11\,280\ \mathrm{V} \]

Its output current is half its primary current:

\[ I_{\mathrm{secondary}}=10.0\ \mathrm{A} \]

Section 2 therefore loses:

\[ \begin{aligned} P_2&=(10.0)^2(2.00)\\ &=200\ \mathrm{W} \end{aligned} \]

Part b: Compare total losses and delivered power.

The generator supplies:

\[ \begin{aligned} P_{\mathrm{generator}} &=(6000)(20.0)\\ &=120\,000\ \mathrm{W} \end{aligned} \]

For Arrangement E:

\[ \begin{aligned} P_{\mathrm{loss},E} &=1800+200\\ &=2000\ \mathrm{W} \end{aligned} \]

Therefore:

\[ P_{\mathrm{received},E}=118.0\ \mathrm{kW} \]

For Arrangement L:

\[ \begin{aligned} P_{\mathrm{loss},L} &=7200+200\\ &=7400\ \mathrm{W} \end{aligned} \]

Therefore:

\[ P_{\mathrm{received},L}=112.6\ \mathrm{kW} \]

Part c: Explain why transformer position matters.

The engineer’s argument ignores where the current is reduced.

In Arrangement E, both cable sections carry 10.0 A. Both benefit from the lower current.

In Arrangement L, Section 1 still carries 20.0 A, and its large resistance causes substantial heating before the electricity reaches the transformer.

Only Section 2 benefits from the step-up.

There is another subtlety. The transformer in Arrangement L doesn’t receive the full 6.00 kV generator voltage. The first cable section has already caused a 360 V drop, so its primary receives only 5.64 kV.

Its secondary consequently produces 11.28 kV rather than 12.0 kV.

An ideal transformer conserves the electrical power entering it. It cannot restore electrical energy that was already dissipated upstream.

Question 5

An ideal AC source maintains a fixed RMS output voltage of \(100\ \mathrm{V}\).

It feeds an ideal step-up transformer, followed by a transmission line whose combined conductor resistance is \(30.0\ \Omega\).

At the far end, an ideal step-down transformer feeds a fixed \(10.0\ \Omega\) resistive load.

The transformer turns ratios are reciprocal:

  • Initially, both transformers have a 1:1 ratio.
  • In the second arrangement, the first transformer steps voltage up by a factor of 2, and the second steps it back down by a factor of 2.

The source voltage and the physical receiving-load resistance do not change. The source can supply whatever current the circuit demands.

Assume steady, purely resistive operation, ideal transformers with no losses or magnetising current, and no losses outside the transmission resistance.

a. Determine the transmission current, cable heating, and load power in both arrangements.

b. Determine the fraction of sending-end power lost in the cable in each arrangement. Explain how increasing transmission voltage could increase the absolute heating loss while reducing the fraction of power wasted.

c. In the second arrangement, the receiving-load resistance is now allowed to change. Find the load resistance required to keep power entering the transmission line equal to its value in the original 1:1 arrangement. Determine the new cable heating and receiving power.

Has the quarter-loss rule been recovered? Has the power received by the load remained constant?

Solution 5

Doubling the line’s sending voltage from 100 V to 200 V increases its heating from 187.5 W to approximately 244.9 W in this unusual circuit. Yet the fraction of input power lost in the cable falls from 75% to about 42.9%.

The quarter-loss rule is recovered in Part c when the physical load is changed to \(32.5\ \Omega\), allowing the power entering the line to remain fixed.

The crucial issue is that a fixed source voltage and a fixed load resistance do not guarantee fixed transmitted power when transformer ratios change.

Part a: Work out how the transformers affect the whole circuit.

Let:

  • \(V_0=100\ \mathrm{V}\) be the source voltage.
  • \(n\) be the voltage step-up factor.
  • \(I_{\mathrm{line}}\) be the transmission-line current.
  • \(I_{\mathrm{load}}\) be the receiving-load current.
  • \(R_{\mathrm{line}}=30.0\ \Omega\).
  • \(R_{\mathrm{load}}=10.0\ \Omega\).

The first transformer produces a sending voltage:

\[ V_{\mathrm{s}}=nV_0 \]

The receiving transformer reduces the voltage by the same factor \(n\).

Because the receiving transformer is ideal, its output current is \(n\) times its input current:

\[ I_{\mathrm{load}}=nI_{\mathrm{line}} \]

The receiving load obeys Ohm’s law:

\[ V_{\mathrm{load}}=I_{\mathrm{load}}R_{\mathrm{load}} \]

The voltage entering the step-down transformer is \(n\) times the load voltage.

Therefore:

\[ \begin{aligned} V_{\mathrm{r}} &=nV_{\mathrm{load}}\\ &=n^2I_{\mathrm{line}}R_{\mathrm{load}} \end{aligned} \]

The sending voltage must supply both the cable voltage drop and the receiving-end voltage:

\[ \begin{aligned} nV_0 &=I_{\mathrm{line}}R_{\mathrm{line}}\\ &\quad+n^2I_{\mathrm{line}}R_{\mathrm{load}} \end{aligned} \]

Rearranging gives:

\[ I_{\mathrm{line}} =\frac{nV_0}{R_{\mathrm{line}}+n^2R_{\mathrm{load}}} \]

This equation captures the interaction that a simple quarter-loss prediction misses.

Changing the transformer ratio changes the voltage and the effective resistance presented to the transmission line.

First arrangement: \(n=1\).

\[ \begin{aligned} I_{\mathrm{line},1} &=\frac{100}{30.0+10.0}\\ &=2.50\ \mathrm{A} \end{aligned} \]

The cable heating is:

\[ \begin{aligned} P_{\mathrm{loss},1} &=(2.50)^2(30.0)\\ &=187.5\ \mathrm{W} \end{aligned} \]

With a 1:1 receiving transformer, the load current is also 2.50 A.

The load receives:

\[ \begin{aligned} P_{\mathrm{load},1} &=(2.50)^2(10.0)\\ &=62.5\ \mathrm{W} \end{aligned} \]

The total sending power is:

\[ P_{\mathrm{s},1}=(100)(2.50)=250\ \mathrm{W} \]

And \(187.5+62.5=250\ \mathrm{W}\), so energy is conserved.

Second arrangement: \(n=2\).

The line sending voltage is now 200 V.

However, the current is not automatically half the original value.

Using the expression derived above:

\[ \begin{aligned} I_{\mathrm{line},2} &=\frac{200}{30.0+4(10.0)}\\ &=\frac{200}{70.0}\\ &\approx2.857\ \mathrm{A} \end{aligned} \]

The current has increased from 2.50 A to approximately 2.86 A.

Therefore, the cable heating also increases:

\[ \begin{aligned} P_{\mathrm{loss},2} &=(2.857\ldots)^2(30.0)\\ &\approx244.9\ \mathrm{W} \end{aligned} \]

The step-down transformer doubles the current delivered to the load:

\[ \begin{aligned} I_{\mathrm{load},2} &=2I_{\mathrm{line},2}\\ &\approx5.714\ \mathrm{A} \end{aligned} \]

The load receives:

\[ \begin{aligned} P_{\mathrm{load},2} &=(5.714\ldots)^2(10.0)\\ &\approx326.5\ \mathrm{W} \end{aligned} \]

The sending-end power is:

\[ \begin{aligned} P_{\mathrm{s},2} &=(200)(2.857\ldots)\\ &\approx571.4\ \mathrm{W} \end{aligned} \]

And \(244.9+326.5\approx571.4\ \mathrm{W}\), allowing for rounding.

The source is now supplying considerably more power than before, even though its own output voltage remains at 100 V.

Part b: Compare the fractions lost.

Initially:

\[ \begin{aligned} \text{Loss fraction}_1 &=\frac{187.5}{250}\\ &=0.750 \end{aligned} \]

So 75.0% of the sending-end power is wasted in the cable.

In the second arrangement:

\[ \begin{aligned} \text{Loss fraction}_2 &=\frac{244.9}{571.4}\\ &\approx0.429 \end{aligned} \]

Approximately 42.9% is lost.

Quantity1:1 transformers2:1 and 1:2 transformers
Line sending voltage100 V200 V
Line current2.50 A2.857 A
Sending-end power250 W571.4 W
Cable heating187.5 W244.9 W
Load power62.5 W326.5 W
Fraction lost in cable75.0%42.9%

Both claims are true:

The second arrangement converts more electrical power into heat in the cable, but a smaller percentage of the transmitted power is wasted.

Why?

The step-up transformer reduces its secondary current relative to its own primary current, but the primary current itself changes when the load and transformer arrangement interact.

In the second arrangement, the source supplies approximately 5.714 A, compared with 2.50 A originally.

The higher sending voltage therefore doesn’t imply that the line current must be half its former value.

The original prediction fails because the sending power increased from 250 W to approximately 571.4 W.

This is an intentionally extreme circuit with substantial initial losses, not a typical well-designed electricity transmission system. Its purpose is to expose the assumption hidden inside the quarter-loss rule.

Part c: Restore constant sending-end power.

Now keep the sending power at its original value of 250 W while retaining the 2:1 step-up and reciprocal step-down transformers.

The line voltage is 200 V.

To transmit 250 W, the line current must be:

\[ \begin{aligned} I_{\mathrm{line}} &=\frac{250}{200}\\ &=1.25\ \mathrm{A} \end{aligned} \]

The cable heating becomes:

\[ \begin{aligned} P_{\mathrm{loss}} &=(1.25)^2(30.0)\\ &=46.875\ \mathrm{W} \end{aligned} \]

Compare this with the original 187.5 W:

\[ \frac{46.875}{187.5}=0.250 \]

The line loss is now exactly one-quarter of its original value.

What receiving resistance makes this possible?

The transmission cable voltage drop is:

\[ V_{\mathrm{drop}}=(1.25)(30.0)=37.5\ \mathrm{V} \]

The voltage entering the receiving transformer is:

\[ V_{\mathrm{r}}=200-37.5=162.5\ \mathrm{V} \]

The receiving transformer halves this voltage:

\[ V_{\mathrm{load}}=\frac{162.5}{2}=81.25\ \mathrm{V} \]

It doubles the line current:

\[ I_{\mathrm{load}}=2(1.25)=2.50\ \mathrm{A} \]

Therefore, the required load resistance is:

\[ \begin{aligned} R_{\mathrm{load}} &=\frac{81.25}{2.50}\\ &=32.5\ \Omega \end{aligned} \]

The receiving power is:

\[ \begin{aligned} P_{\mathrm{load}} &=(81.25)(2.50)\\ &=203.125\ \mathrm{W} \end{aligned} \]

This agrees with energy conservation:

\[ 250-46.875=203.125\ \mathrm{W} \]

The quarter-loss rule has been recovered because sending-end power is now genuinely constant.

But the receiving power hasn’t stayed constant. It has increased from 62.5 W to 203.125 W because far less energy is wasted in the transmission conductors.

This is the deeper constraint behind the whole problem: you cannot assume that source voltage, receiving-load resistance, sending-end power, and receiving-end power all remain fixed when you change a transformer’s turns ratio.

Those quantities are connected by the circuit.

06What to decide in the next transmission problem

When you see a transmission voltage increase, first identify which part of the system is being controlled.

If power entering the cable remains fixed and the resistance is unchanged, doubling the voltage halves the current and quarters the resistive loss.

If the load, source conditions, or transformer arrangement changes, determine the new current from the actual circuit before calculating heating.

The next useful distinction is between losses in the transmission conductors and losses in the transformers themselves. A lower cable current doesn’t necessarily mean that every loss in the overall system falls by the same factor.

For that wider picture, including step-up and step-down transformers, continue with High-Voltage Electricity Transmission for HSC Physics.