Why a Step-Down Transformer Increases Current
Discover why a step-down transformer increases secondary current as voltage decreases. Learn how the ideal transformer relationship works, why the load affects current, and how to distinguish useful current transformation from resistive power losses, with worked HSC Physics examples.
Imagine a school physics experiment using a small transformer. Its primary coil is supplied with \(24\text{ V}\) AC, while its secondary produces just \(6.0\text{ V}\).
You connect a \(6.0\ \Omega\) resistor to the secondary. Predict what happens to the current. Should the secondary current be one-quarter of the primary current because its voltage is one-quarter as large, or four times as large?
It’s four times as large in an ideal transformer. The secondary current is \(1.0\text{ A}\), while the primary current is only \(0.25\text{ A}\).
A step-down transformer increases secondary current because it trades voltage for current while transferring the same power. Lower voltage means less energy transferred per coulomb of charge, so more coulombs must flow each second to transfer the same amount of energy per second.
The important qualification is that this inverse voltage-current relationship assumes the same transferred power. The load still determines how much current actually flows.
01How a step-down transformer increases current
Start with what the experiment measures
To investigate the current transformation, we need to measure both sides of the transformer.
The apparatus is arranged in a specific order:
- An isolated, low-voltage AC supply connects to the primary coil.
- An ammeter is placed in series with the primary coil to measure primary current, \(I_p\).
- A voltmeter is connected in parallel across the primary coil to measure primary voltage, \(V_p\).
- The primary and secondary coils are wound around a shared laminated iron core.
- The secondary coil connects to a resistor through a second ammeter, which measures secondary current, \(I_s\).
- A second voltmeter measures the voltage across the secondary load.
The two coils are electrically separate. Energy transfers between them through the changing magnetic flux in the core, rather than charge travelling directly from one coil to the other.
For a classroom demonstration, use approved, isolated, current-limited low-voltage equipment. Do not improvise a connection to mains electricity.
Why an unloaded test is not enough
Suppose the first design leaves the secondary circuit disconnected.
You can still measure an induced voltage across the secondary terminals. However, no secondary current flows because there is no closed circuit.
This test demonstrates voltage transformation, but it does not demonstrate an increase in secondary current.
The experiment needs a load.
Connect the \(6.0\ \Omega\) resistor across the secondary. Now there is a complete path for charge to flow, and we can predict the current.
For the ideal transformer:
\[ V_s=6.0\text{ V} \]
Using Ohm’s law:
\[ I_s=\frac{V_s}{R} \]
\[ I_s=\frac{6.0}{6.0}=1.0\text{ A} \]
The secondary transfers:
\[ P_s=V_sI_s \]
\[ P_s=6.0\times1.0=6.0\text{ W} \]
An ideal transformer has no energy losses, so the primary must receive the same power.
\[ P_p=P_s=6.0\text{ W} \]
Therefore:
\[ I_p=\frac{P_p}{V_p} \]
\[ I_p=\frac{6.0}{24}=0.25\text{ A} \]
The predicted readings are:
| Measurement | Primary | Secondary |
|---|---|---|
| Voltage | 24 V | 6.0 V |
| Current | 0.25 A | 1.0 A |
| Power | 6.0 W | 6.0 W |
Key result
The secondary current is four times the primary current, even though the secondary voltage is four times smaller.
These are ideal predictions. A real transformer will produce slightly different readings because of energy losses and the current needed to establish its magnetic field.
Why the mathematics produces this result
To understand the current increase, consider what voltage and current actually measure.
Voltage describes the energy transferred per unit charge:
\[ V=\frac{\Delta E}{Q} \]
Current describes how much charge passes a point each second:
\[ I=\frac{Q}{t} \]
Here, \(\Delta E\) is the energy transferred, \(Q\) is the charge, and \(t\) is the time.
Multiplying these quantities gives electrical power:
\[ P=VI \]
In other words:
\[ \text{Power} = \text{energy per coulomb} \times \text{coulombs per second} \]
This explains the voltage-current trade-off.
If the energy transferred per coulomb decreases, more charge must flow each second to maintain the same power.
A step-down transformer therefore transfers energy using a lower voltage and a higher current.
Deriving the current transformation
For an ideal transformer:
\[ P_p=P_s \]
For the resistive loads considered here, \(P=VI\), so:
\[ V_pI_p=V_sI_s \]
Rearranging:
\[ \boxed{\frac{I_s}{I_p}=\frac{V_p}{V_s}} \]
This is the inverse voltage-current relationship.
The voltage ratio is also determined by the number of turns in each coil:
\[ \frac{V_s}{V_p}=\frac{N_s}{N_p} \]
where:
- \(N_p\) is the number of turns in the primary coil.
- \(N_s\) is the number of turns in the secondary coil.
Combining the two relationships gives:
\[ \boxed{\frac{I_s}{I_p}=\frac{N_p}{N_s}} \]
The secondary current ratio is therefore the inverse of the turns ratio.
For the \(24\text{ V}\) to \(6\text{ V}\) experiment:
\[ \frac{V_s}{V_p}=\frac{6}{24}=\frac14 \]
Therefore:
\[ \frac{I_s}{I_p}=\frac{24}{6}=4 \]
The secondary has one-quarter as many turns and carries four times the current in the ideal model.
What does ideal actually mean?
The ideal transformer model makes several simplifying assumptions:
- All magnetic flux produced by the primary links the secondary.
- There is no energy lost through winding resistance.
- There are no eddy-current or hysteresis losses in the core.
- There are no other energy losses.
- The transformer transfers energy perfectly between the two circuits.
Under these assumptions:
\[ P_{\text{in}}=P_{\text{out}} \]
The equations use RMS voltage and current values. The numerical examples in this article use resistive loads, so \(P=VI\).
In a real transformer, output power is less than input power. The ideal current relationship is a useful prediction, but actual measurements can differ slightly.
For a more detailed derivation of the ideal transformer relationships, see Ideal Transformer Current and Power for HSC Physics.
02The important catch: the load determines the current
Here’s a common misconception.
A student learns that a step-down transformer increases current. They then assume that lowering the secondary voltage must always produce a larger secondary current.
That prediction is not correct.
The transformer changes the available secondary voltage. The load determines how much current flows.
For a resistive load:
\[ I_s=\frac{V_s}{R_L} \]
where \(R_L\) is the load resistance.
Consider a \(6.0\ \Omega\) resistor connected to two different secondary voltages.
| Secondary voltage | Load resistance | Secondary current | Output power |
|---|---|---|---|
| 12 V | 6.0 Ω | 2.0 A | 24 W |
| 6.0 V | 6.0 Ω | 1.0 A | 6.0 W |
When the voltage halves, the current also halves.
Why?
The resistance stays constant, so Ohm’s law requires current to decrease with voltage.
The output power also decreases because:
\[ P=\frac{V^2}{R} \]
Halving the voltage reduces the power to one-quarter of its original value.
This does not contradict the transformer current relationship.
For a \(240\text{ V}\) primary, the two operating conditions give:
| Secondary voltage | Secondary current | Primary current |
|---|---|---|
| 12 V | 2.0 A | 0.10 A |
| 6.0 V | 1.0 A | 0.025 A |
In both cases, the secondary current is larger than the primary current.
The distinction is that we’re comparing two different operating conditions. The transformer transfers less power in the second condition because the fixed resistor draws less power.
The rule to remember is:
- Same transferred power: lower voltage means higher current.
- Same resistive load: lower voltage means lower current.
- Open secondary circuit: secondary current is zero.
A transformer does not force a particular current through its load.
03Current transformation is not the same as resistive loss
This distinction is particularly important in HSC calculations.
The increase in secondary current is a useful part of the transformer operation. It is not automatically an energy loss.
Resistive heating is a separate process.
Real transformer windings have electrical resistance. As current flows through the copper wire, some electrical energy becomes thermal energy.
The power dissipated as heat is:
\[ P_{\text{loss}}=I^2R \]
For a transformer, the total copper loss in both windings is:
\[ \boxed{ P_{\text{copper}} = I_p^2R_p+I_s^2R_s } \]
Here:
- \(I_p\) is the actual RMS current in the primary winding.
- \(I_s\) is the actual RMS current in the secondary winding.
- \(R_p\) is the primary winding resistance.
- \(R_s\) is the secondary winding resistance.
Notice that the current is squared.
This means that doubling the current through a winding with unchanged resistance increases its copper heating by a factor of four.
However, you cannot conclude that the secondary winding must always experience greater heating simply because it carries more current.
Its resistance also matters.
Worked example: Calculate copper losses in both windings
A real transformer has the following illustrative measured values:
| Quantity | Primary | Secondary |
|---|---|---|
| RMS current | 0.26 A | 1.02 A |
| Winding resistance | 4.0 Ω | 0.20 Ω |
Calculate the copper loss in each winding and the total copper loss.
Step 1
Use:
\[ P_p=I_p^2R_p \]
Substitute:
\[ P_p=(0.26)^2(4.0) \]
\[ P_p=0.2704\text{ W} \]
Step 2
\[ P_s=I_s^2R_s \]
\[ P_s=(1.02)^2(0.20) \]
\[ P_s=0.20808\text{ W} \]
Step 3
\[ P_{\text{copper}}=0.2704+0.20808 \]
\[ \boxed{P_{\text{copper}}\approx0.48\text{ W}} \]
The secondary current is almost four times the primary current, yet its copper loss is slightly smaller.
This happens because the secondary winding has a much lower resistance.
The example shows why you must calculate resistive heating separately rather than assume that a larger current automatically means a proportionally larger energy loss.
What about other transformer losses?
Copper losses are not the only reason a real transformer is less than 100% efficient.
Other losses include:
- Eddy-current losses in the conducting core.
- Hysteresis losses caused by repeated magnetisation and demagnetisation.
- Energy associated with magnetic flux that does not link both windings.
These losses reduce the useful power delivered to the load.
The overall power balance becomes:
\[ P_{\text{in}}=P_{\text{out}}+P_{\text{loss}} \]
The current transformation and the energy losses must be treated separately.
For more detail, see Eddy-Current Losses in Transformers: HSC Physics Guide.
04Choosing the correct equation in an exam
A useful way to avoid transformer calculation mistakes is to identify exactly what the question gives you.
| Information provided | What to calculate |
|---|---|
| Primary and secondary voltages, plus one current | Use \(V_pI_p=V_sI_s\) for an ideal transformer |
| Number of turns | Use the turns ratio to find the voltage ratio |
| A resistor connected to the secondary | Use \(I_s=V_s/R_L\) first |
| Winding resistance and actual current | Use \(P_{\text{loss}}=I^2R\) |
| Connecting-wire resistance | Include it in the circuit resistance, then calculate its heating separately |
| Input and output power | Find total losses using \(P_{\text{in}}-P_{\text{out}}\) |
One final warning: an ideal transformer conserves power at each operating condition. It does not necessarily transfer the same amount of power when you change the load.
05Worked examples
Worked example: Find the primary current from the secondary current
An ideal transformer has a primary voltage of \(230\text{ V}\) and a secondary voltage of \(23\text{ V}\). The secondary supplies a resistive load with a current of \(2.5\text{ A}\).
Calculate:
- The power delivered to the secondary load.
- The primary current.
- The ratio of secondary current to primary current.
Step 1
\[ P_s=V_sI_s \]
\[ P_s=23\times2.5 \]
\[ P_s=57.5\text{ W} \]
Step 2
\[ P_p=P_s=57.5\text{ W} \]
Step 3
\[ I_p=\frac{P_p}{V_p} \]
\[ I_p=\frac{57.5}{230} \]
\[ \boxed{I_p=0.25\text{ A}} \]
Step 4
\[ \frac{I_s}{I_p}=\frac{2.5}{0.25} \]
\[ \boxed{\frac{I_s}{I_p}=10} \]
The secondary current is ten times the primary current.
This matches the voltage ratio: the secondary voltage is one-tenth of the primary voltage, so the secondary current must be ten times larger for the same power transfer.
Worked example: Calculate load current and connecting-wire losses
An ideal transformer has a \(240\text{ V}\) primary and a \(24\text{ V}\) secondary.
The secondary supplies a \(6.0\ \Omega\) resistor through connecting wires with a combined resistance of \(0.40\ \Omega\).
Treat the \(24\text{ V}\) as the voltage supplied at the secondary terminals, before the connecting-wire voltage drop. Ignore winding resistance.
Calculate:
- The secondary current.
- The voltage across the load.
- The power dissipated in the load.
- The power dissipated in the connecting wires.
- The primary current.
Step 1
The connecting wires and load are in series.
\[ R_{\text{total}}=6.0+0.40 \]
\[ R_{\text{total}}=6.40\ \Omega \]
Step 2
\[ I_s=\frac{V_s}{R_{\text{total}}} \]
\[ I_s=\frac{24}{6.40} \]
\[ \boxed{I_s=3.75\text{ A}} \]
Step 3
\[ V_{\text{load}}=I_sR_L \]
\[ V_{\text{load}}=3.75\times6.0 \]
\[ \boxed{V_{\text{load}}=22.5\text{ V}} \]
Notice that the load receives less than \(24\text{ V}\). The remaining voltage is dropped across the connecting wires.
Step 4
\[ P_{\text{load}}=I_s^2R_L \]
\[ P_{\text{load}}=(3.75)^2(6.0) \]
\[ \boxed{P_{\text{load}}=84.4\text{ W}} \]
Step 5
\[ P_{\text{wires}}=I_s^2R_{\text{wires}} \]
\[ P_{\text{wires}}=(3.75)^2(0.40) \]
\[ \boxed{P_{\text{wires}}=5.63\text{ W}} \]
The total power supplied by the secondary is:
\[ P_s=V_sI_s \]
\[ P_s=24\times3.75=90.0\text{ W} \]
Check the power balance:
\[ 84.4+5.63\approx90.0\text{ W} \]
The small difference is rounding.
Step 6
The transformer itself is ideal, so its input power equals its secondary output power.
\[ P_p=P_s=90.0\text{ W} \]
Therefore:
\[ I_p=\frac{90.0}{240} \]
\[ \boxed{I_p=0.375\text{ A}} \]
The secondary current is ten times the primary current, as expected.
The important distinction is that the transformer has no internal losses in this model, but the external connecting wires still dissipate energy.
06Questions and solutions
Question 1
An ideal step-down transformer has a primary voltage of \(240\text{ V}\) and a secondary voltage of \(24\text{ V}\).
The secondary supplies a current of \(3.0\text{ A}\) to a resistive load.
Calculate:
a. The power delivered to the secondary load.
b. The primary current.
Solution 1
The output power is \(72\text{ W}\), and the primary current is \(0.30\text{ A}\).
The key principle is that an ideal transformer transfers equal power between its primary and secondary circuits.
Part a: Calculate output power.
\[ P_s=V_sI_s \]
\[ P_s=24\times3.0 \]
\[ \boxed{P_s=72\text{ W}} \]
Part b: Calculate primary current.
Since the transformer is ideal:
\[ P_p=P_s=72\text{ W} \]
Therefore:
\[ I_p=\frac{P_p}{V_p} \]
\[ I_p=\frac{72}{240} \]
\[ \boxed{I_p=0.30\text{ A}} \]
The secondary current is ten times the primary current.
A common mistake is to assume that a smaller secondary voltage must produce a smaller current. That ignores power conservation. The current increases because the voltage decreases while the transferred power remains constant.
Question 2
An ideal transformer has a primary voltage of \(240\text{ V}\) and two selectable secondary voltage settings: \(24\text{ V}\) and \(12\text{ V}\).
A \(8.0\ \Omega\) resistor is connected across the secondary. The transformer is tested separately at each voltage setting.
For both tests, calculate:
a. The secondary current.
b. The output power.
c. The primary current.
d. Explain why the secondary current is smaller at the \(12\text{ V}\) setting, even though it is a greater step-down in voltage.
Solution 2
At the \(24\text{ V}\) setting, the secondary current is \(3.0\text{ A}\) and the primary current is \(0.30\text{ A}\).
At the \(12\text{ V}\) setting, the secondary current is \(1.5\text{ A}\) and the primary current is \(0.075\text{ A}\).
The reason is that the load resistance remains constant, so Ohm’s law determines how the current changes.
Test 1: Secondary voltage of \(24\text{ V}\).
Calculate the secondary current:
\[ I_s=\frac{V_s}{R} \]
\[ I_s=\frac{24}{8.0} \]
\[ I_s=3.0\text{ A} \]
Calculate output power:
\[ P_s=V_sI_s \]
\[ P_s=24\times3.0 \]
\[ P_s=72\text{ W} \]
Calculate primary current:
\[ I_p=\frac{P_p}{V_p} \]
\[ I_p=\frac{72}{240} \]
\[ \boxed{I_p=0.30\text{ A}} \]
Test 2: Secondary voltage of \(12\text{ V}\).
Calculate the secondary current:
\[ I_s=\frac{12}{8.0} \]
\[ I_s=1.5\text{ A} \]
Calculate output power:
\[ P_s=12\times1.5 \]
\[ P_s=18\text{ W} \]
Calculate primary current:
\[ I_p=\frac{18}{240} \]
\[ \boxed{I_p=0.075\text{ A}} \]
Part d: Explain the difference.
The tempting prediction is that halving the secondary voltage should double the secondary current.
That would be correct if the transformer maintained the same output power.
But the output power is not fixed here. The same \(8.0\ \Omega\) resistor remains connected in both tests.
Using Ohm’s law, halving the voltage halves the current. Consequently, the output power falls to one-quarter.
Importantly, the current transformation still works in both cases:
At \(24\text{ V}\):
\[ \frac{I_s}{I_p}=\frac{3.0}{0.30}=10 \]
At \(12\text{ V}\):
\[ \frac{I_s}{I_p}=\frac{1.5}{0.075}=20 \]
The secondary current is larger than the primary current in both tests. It simply does not increase when comparing the two different operating conditions.
Question 3
A real transformer is operating under load.
The following RMS measurements are recorded:
| Quantity | Primary winding | Secondary winding |
|---|---|---|
| Current | 0.80 A | 6.0 A |
| Resistance | 5.0 Ω | 0.30 Ω |
The total measured power loss in the transformer is \(15\text{ W}\).
Calculate:
a. The copper loss in the primary winding.
b. The copper loss in the secondary winding.
c. The total copper loss.
d. The remaining power loss due to other mechanisms.
Explain why the winding with the larger current does not necessarily have the largest resistive loss.
Solution 3
The primary copper loss is \(3.2\text{ W}\), the secondary copper loss is \(10.8\text{ W}\), and the total copper loss is \(14.0\text{ W}\). The remaining \(1.0\text{ W}\) is due to other transformer losses.
Use \(P=I^2R\) separately for each winding.
Part a: Primary copper loss.
\[ P_p=I_p^2R_p \]
\[ P_p=(0.80)^2(5.0) \]
\[ \boxed{P_p=3.2\text{ W}} \]
Part b: Secondary copper loss.
\[ P_s=I_s^2R_s \]
\[ P_s=(6.0)^2(0.30) \]
\[ \boxed{P_s=10.8\text{ W}} \]
Part c: Total copper loss.
\[ P_{\text{copper}}=3.2+10.8 \]
\[ \boxed{P_{\text{copper}}=14.0\text{ W}} \]
Part d: Other losses.
The total transformer loss is \(15\text{ W}\).
Therefore:
\[ P_{\text{other}}=15-14 \]
\[ \boxed{P_{\text{other}}=1.0\text{ W}} \]
This remaining loss can include eddy-current and hysteresis losses in the core.
The tempting approach is to assume that the secondary winding must have proportionally greater heating because its current is much larger.
However, resistive heating depends on both current and resistance:
\[ P=I^2R \]
The secondary winding has a much lower resistance than the primary winding. Its current is larger, but its resistance is smaller.
The correct comparison requires both quantities.
Question 4
A transformer has a primary voltage of \(240\text{ V}\) and an induced secondary emf of \(24\text{ V}\).
Model the transformer as ideal except for a secondary winding resistance of \(0.20\ \Omega\). Assume the primary winding and core have negligible losses.
The secondary load is changed between two resistors:
- First load: \(5.8\ \Omega\).
- Second load: \(2.8\ \Omega\).
For each load, calculate:
a. The secondary current.
b. The voltage across the load.
c. The power delivered to the load.
d. The copper loss in the secondary winding.
e. The primary current.
Assume all values are RMS magnitudes and both loads are resistive.
Solution 4
With the \(5.8\ \Omega\) load, the secondary current is \(4.0\text{ A}\), the load voltage is \(23.2\text{ V}\), and the primary current is \(0.40\text{ A}\).
With the \(2.8\ \Omega\) load, the secondary current is \(8.0\text{ A}\), the load voltage is \(22.4\text{ V}\), and the primary current is \(0.80\text{ A}\).
The key is to include the secondary winding resistance when calculating current, then separate the useful load power from the winding heating.
First condition: \(5.8\ \Omega\) load.
Step 1: Calculate the total secondary circuit resistance.
\[ R_{\text{total}}=5.8+0.20 \]
\[ R_{\text{total}}=6.0\ \Omega \]
Step 2: Calculate secondary current.
\[ I_s=\frac{24}{6.0} \]
\[ \boxed{I_s=4.0\text{ A}} \]
Step 3: Calculate load voltage.
\[ V_{\text{load}}=I_sR_L \]
\[ V_{\text{load}}=4.0\times5.8 \]
\[ \boxed{V_{\text{load}}=23.2\text{ V}} \]
Step 4: Calculate useful load power.
\[ P_{\text{load}}=I_s^2R_L \]
\[ P_{\text{load}}=(4.0)^2(5.8) \]
\[ \boxed{P_{\text{load}}=92.8\text{ W}} \]
Step 5: Calculate secondary winding copper loss.
\[ P_{\text{copper}}=I_s^2R_s \]
\[ P_{\text{copper}}=(4.0)^2(0.20) \]
\[ \boxed{P_{\text{copper}}=3.2\text{ W}} \]
The secondary emf supplies:
\[ P_{\text{emf}}=24\times4.0=96\text{ W} \]
Check:
\[ 92.8+3.2=96\text{ W} \]
Step 6: Calculate primary current.
With negligible primary and core losses:
\[ P_p=P_{\text{emf}}=96\text{ W} \]
Therefore:
\[ I_p=\frac{96}{240} \]
\[ \boxed{I_p=0.40\text{ A}} \]
Second condition: \(2.8\ \Omega\) load.
Step 1: Calculate total resistance.
\[ R_{\text{total}}=2.8+0.20 \]
\[ R_{\text{total}}=3.0\ \Omega \]
Step 2: Calculate secondary current.
\[ I_s=\frac{24}{3.0} \]
\[ \boxed{I_s=8.0\text{ A}} \]
Step 3: Calculate load voltage.
\[ V_{\text{load}}=8.0\times2.8 \]
\[ \boxed{V_{\text{load}}=22.4\text{ V}} \]
Step 4: Calculate load power.
\[ P_{\text{load}}=(8.0)^2(2.8) \]
\[ \boxed{P_{\text{load}}=179.2\text{ W}} \]
Step 5: Calculate secondary copper loss.
\[ P_{\text{copper}}=(8.0)^2(0.20) \]
\[ \boxed{P_{\text{copper}}=12.8\text{ W}} \]
The total secondary power supplied is:
\[ P_{\text{emf}}=24\times8.0=192\text{ W} \]
Check:
\[ 179.2+12.8=192\text{ W} \]
Step 6: Calculate primary current.
\[ I_p=\frac{192}{240} \]
\[ \boxed{I_p=0.80\text{ A}} \]
What changed physically?
The total secondary resistance halved from \(6.0\ \Omega\) to \(3.0\ \Omega\), so the secondary current doubled.
However, the load voltage decreased slightly because more voltage was dropped across the secondary winding resistance.
The winding copper loss increased from \(3.2\text{ W}\) to \(12.8\text{ W}\), a factor of four.
This is an important real-world limitation: increasing secondary current can increase winding heating very quickly, even when the secondary voltage remains relatively low.
Question 5
An ideal transformer has a primary voltage of \(240\text{ V}\) and two selectable secondary voltage settings: \(24\text{ V}\) and \(12\text{ V}\).
Two loads are connected in parallel across the secondary:
- A \(12\ \Omega\) resistor.
- A regulated electronic device that maintains a constant power consumption of \(48\text{ W}\) at either secondary voltage.
Assume the regulated device operates correctly at both voltages and has negligible internal losses.
For each secondary voltage setting, calculate:
a. The current through the resistor.
b. The current through the regulated device.
c. The total secondary current.
d. The total secondary output power.
e. The primary current.
A student makes the following argument:
Halving the secondary voltage must double the total secondary current because the transformer maintains the same power.
Another student argues:
The resistor current halves, so the total secondary current must decrease.
Both predictions seem reasonable. Determine which prediction is correct, or whether both are incomplete. Explain precisely why.
Solution 5
At the \(24\text{ V}\) setting, the total secondary current is \(4.0\text{ A}\) and the primary current is \(0.40\text{ A}\).
At the \(12\text{ V}\) setting, the total secondary current is \(5.0\text{ A}\) and the primary current is \(0.25\text{ A}\).
The surprising result is that the secondary current increases when the voltage is halved, but it does not double. The two parallel loads respond differently to the voltage change.
We need to calculate each branch separately before adding their currents.
First condition: \(24\text{ V}\) secondary.
Step 1: Calculate the resistor current.
Using Ohm’s law:
\[ I_R=\frac{V_s}{R} \]
\[ I_R=\frac{24}{12} \]
\[ I_R=2.0\text{ A} \]
Step 2: Calculate the regulated device current.
The device maintains \(48\text{ W}\) consumption.
\[ P=VI \]
Therefore:
\[ I_{\text{device}}=\frac{P}{V_s} \]
\[ I_{\text{device}}=\frac{48}{24} \]
\[ I_{\text{device}}=2.0\text{ A} \]
Step 3: Calculate total secondary current.
The currents in parallel branches add:
\[ I_s=I_R+I_{\text{device}} \]
\[ I_s=2.0+2.0 \]
\[ \boxed{I_s=4.0\text{ A}} \]
Step 4: Calculate total output power.
\[ P_s=V_sI_s \]
\[ P_s=24\times4.0 \]
\[ \boxed{P_s=96\text{ W}} \]
This also agrees with the individual branch powers:
\[ P_R=24\times2=48\text{ W} \]
\[ P_{\text{device}}=48\text{ W} \]
\[ P_{\text{total}}=48+48=96\text{ W} \]
Step 5: Calculate primary current.
For an ideal transformer:
\[ P_p=P_s=96\text{ W} \]
\[ I_p=\frac{96}{240} \]
\[ \boxed{I_p=0.40\text{ A}} \]
Second condition: \(12\text{ V}\) secondary.
Step 1: Calculate the resistor current.
\[ I_R=\frac{12}{12} \]
\[ \boxed{I_R=1.0\text{ A}} \]
The resistor current has halved.
Step 2: Calculate the regulated device current.
The device still requires \(48\text{ W}\).
\[ I_{\text{device}}=\frac{48}{12} \]
\[ \boxed{I_{\text{device}}=4.0\text{ A}} \]
Its current has doubled.
Step 3: Calculate total secondary current.
\[ I_s=1.0+4.0 \]
\[ \boxed{I_s=5.0\text{ A}} \]
Step 4: Calculate total output power.
\[ P_s=12\times5.0 \]
\[ \boxed{P_s=60\text{ W}} \]
Check using the individual branches:
\[ P_R=12\times1.0=12\text{ W} \]
\[ P_{\text{device}}=48\text{ W} \]
\[ P_{\text{total}}=12+48=60\text{ W} \]
Step 5: Calculate primary current.
\[ P_p=P_s=60\text{ W} \]
\[ I_p=\frac{60}{240} \]
\[ \boxed{I_p=0.25\text{ A}} \]
Why both students’ predictions are incomplete
The first student assumes that total output power stays constant when the voltage halves.
But the resistor does not maintain constant power. Its power decreases from \(48\text{ W}\) to \(12\text{ W}\).
Only the regulated device maintains its \(48\text{ W}\) consumption. Its current doubles, while the resistor current halves.
Adding the two branch currents gives \(5.0\text{ A}\), not \(8.0\text{ A}\).
The second student focuses only on the resistor. They correctly predict that its current decreases, but overlook the regulated device, whose current increases by more.
The full comparison is:
| Quantity | 24 V setting | 12 V setting |
|---|---|---|
| Resistor current | 2.0 A | 1.0 A |
| Regulated device current | 2.0 A | 4.0 A |
| Total secondary current | 4.0 A | 5.0 A |
| Secondary output power | 96 W | 60 W |
| Primary current | 0.40 A | 0.25 A |
Finally, check the ideal transformer current relationship.
At \(24\text{ V}\):
\[ \frac{I_s}{I_p}=\frac{4.0}{0.40}=10 \]
At \(12\text{ V}\):
\[ \frac{I_s}{I_p}=\frac{5.0}{0.25}=20 \]
The inverse voltage-current relationship works perfectly in both conditions.
The mistake was assuming that total power remained constant when the load characteristics changed.
This is the deeper lesson: a transformer determines the voltage transformation, but the load determines the current demand and the power transferred.
07What to calculate next
Once you can distinguish useful current transformation from resistive heating, you can tackle a complete transformer energy budget.
Start with the power delivered to the load. Then account separately for copper losses in both windings, core losses, and any external connecting-wire losses.
The final check is always whether the input power can account for all the useful output power and energy dissipated as heat. That is the foundation for calculating transformer efficiency and understanding why real transformers never achieve perfect power transfer.