Transformer Inrush Current: Saturation and Residual Flux

Explore why a transformer draws a large current when switched on, including core saturation, residual flux and switching angle in this extension guide.

Switch on a transformer with its secondary winding disconnected, and something unexpected can happen: the primary current briefly becomes many times larger than its normal magnetising current. There is no load connected to the secondary, so what is causing such a large current?

The answer lies in the magnetic history of the transformer core. The AC supply tries to establish a changing magnetic flux, but the core may already contain some residual magnetism. Depending on exactly when the transformer is switched on, these two contributions can combine to drive the core into magnetic saturation.

Syllabus note: Transformer inrush current is an extension beyond the required assessment content of the NESA Physics 11-12 Syllabus (2025). The Year 12 Electromagnetism focus area provides the prerequisite knowledge, particularly Faraday’s law, magnetic flux, and transformer action. This article develops an additional application; inrush-current analysis is not an HSC assessment requirement. NESA schedules implementation of the new Year 12 syllabus from Term 4 2027.

01The transformer model you already know

A transformer transfers electrical energy between two circuits through electromagnetic induction.

An alternating current in the primary winding produces a changing magnetic flux in the iron core. This changing flux induces an electromotive force (EMF) in both the primary and secondary windings.

In the ideal transformer model, all the magnetic flux produced by the primary links both windings. This is called perfect flux linkage.

The ideal transformer relationships are:

\[ \frac{V_p}{V_s}=\frac{N_p}{N_s} \]

and

\[ P_{\mathrm{in}}=P_{\mathrm{out}} \]

Here:

  • \(V_p\) and \(V_s\) are the primary and secondary voltages.
  • \(N_p\) and \(N_s\) are the numbers of turns in the respective windings.
  • \(P_{\mathrm{in}}\) and \(P_{\mathrm{out}}\) are the input and output powers.

An ideal transformer transfers all the input power to the secondary circuit.

Real transformers are different. They have several imperfections that reduce their efficiency.

What makes a real transformer less efficient?

Three important effects are incomplete flux linkage, eddy currents, and resistive heating.

1. Incomplete flux linkage

Not all the magnetic flux produced by the primary winding passes through the secondary winding.

Some flux links only the primary, while other flux links only the secondary. These are called leakage fluxes.

Only the mutual flux, which links both windings, contributes to the useful electromagnetic coupling between them.

Leakage flux produces leakage reactance, which can cause additional voltage drops and reduce the secondary terminal voltage under load.

Importantly, leakage flux is not automatically energy lost as heat. It is primarily an effect of imperfect magnetic coupling.

2. Eddy currents

The changing magnetic flux also induces circulating currents within the conducting iron core.

These are called eddy currents. They dissipate electrical energy as heat within the core.

Transformer cores are therefore constructed from thin, electrically insulated laminations. Breaking up the conducting paths increases their resistance and reduces eddy-current losses.

For a more detailed explanation, see Eddy-Current Losses in Transformers: HSC Physics Guide.

3. Resistive heating

The copper or aluminium windings have electrical resistance.

As current flows through them, electrical energy is converted into thermal energy through Joule heating.

The total winding power loss can be represented by:

\[ P_{\mathrm{Cu}}=I_p^2R_p+I_s^2R_s \]

where \(I_p\) and \(I_s\) are the primary and secondary currents, while \(R_p\) and \(R_s\) are their respective winding resistances.

These effects mean that a real transformer delivers less power to its load than it receives from its supply.

Its efficiency is:

\[ \eta=\frac{P_{\mathrm{out}}}{P_{\mathrm{in}}} \]

The distinction between ideal and real transformer behaviour is important because winding resistance and leakage reactance also influence the current drawn during energisation.

If you need to revise the ideal transformer relationships first, see Ideal Transformer Current and Power for HSC Physics.

02Flux does not follow voltage instant by instant

To understand inrush current, we need to examine what happens to the magnetic flux immediately after the supply is connected.

Start with one important relationship from Faraday’s law:

\[ v_p=N_p\frac{d\Phi}{dt} \]

Here:

  • \(v_p\) is the instantaneous primary voltage, in volts.
  • \(N_p\) is the number of primary turns.
  • \(\Phi\) is the magnetic flux through the core, in webers (Wb).
  • \(d\Phi/dt\) is the rate of change of magnetic flux.

The equation tells us something important:

Voltage determines how quickly magnetic flux changes, not the instantaneous value of the flux itself.

Think of filling a bucket with water. The flow rate determines how quickly the water level changes, while the amount of water already in the bucket determines its starting level.

Voltage plays the role of the flow rate, and magnetic flux plays the role of the accumulated quantity.

The analogy is useful, but it has limits: magnetic flux is a signed physical quantity, and an iron core has a nonlinear saturation characteristic.

The importance of the starting conditions

Suppose we connect a transformer to a sinusoidal AC supply.

The voltage can be written as:

\[ v_p(t)=V_m\sin(\omega t+\alpha) \]

where:

  • \(V_m\) is the peak supply voltage.
  • \(\omega\) is the angular frequency, in radians per second.
  • \(t\) is the time since switching.
  • \(\alpha\) is the switching angle, describing the phase of the supply voltage at the instant the switch closes.

The angular frequency is:

\[ \omega=2\pi f \]

where \(f\) is the supply frequency in hertz.

For this simplified model, we assume a single-phase transformer, a sinusoidal supply, negligible winding resistance and leakage reactance, and an open secondary winding.

We also choose the voltage polarity so that positive voltage increases positive magnetic flux.

Let \(\Phi_r\) represent the residual magnetic flux already present in the core when the transformer is switched on.

Integrating Faraday’s law gives:

\[ \Phi(t)=\Phi_r+ \frac{1}{N_p} \int_0^t V_m\sin(\omega t'+\alpha)\,dt' \]

Therefore:

\[ \Phi(t)=\Phi_r+ \frac{V_m}{\omega N_p} [\cos\alpha-\cos(\omega t+\alpha)] \]

Define the normal peak operating flux as:

\[ \Phi_m=\frac{V_m}{\omega N_p} \]

For sinusoidal operation, this can also be written as:

\[ \Phi_m=\frac{V_{\mathrm{rms}}}{4.44fN_p} \]

The flux equation becomes:

\[ \boxed{ \Phi(t)=\Phi_r+ \Phi_m[\cos\alpha-\cos(\omega t+\alpha)] } \]

This equation is the starting point for understanding transformer inrush current.

What happens when we switch on at a voltage zero crossing?

First, assume there is no residual flux:

\[ \Phi_r=0 \]

Now suppose the transformer is switched on at a positive voltage zero crossing.

This means:

\[ \alpha=0^\circ \]

Substituting into the flux equation:

\[ \Phi(t)=\Phi_m(1-\cos\omega t) \]

Consider what happens during the first half-cycle.

At the instant of switching:

\[ \Phi(0)=0 \]

Half a cycle later:

\[ \omega t=180^\circ \]

Since \(\cos180^\circ=-1\):

\[ \Phi=\Phi_m(1-(-1)) \]

Therefore:

\[ \boxed{\Phi_{\max}=2\Phi_m} \]

The magnetic flux has reached twice its normal peak value.

This is the flux-doubling effect.

Why does it happen?

The voltage starts at zero but immediately increases in the positive direction. The positive voltage accumulates over the first half-cycle, driving the magnetic flux further in one direction before the voltage reverses.

Now compare this with switching on at the positive voltage peak:

\[ \alpha=90^\circ \]

The flux equation becomes:

\[ \Phi(t)=\Phi_m\sin\omega t \]

The flux now follows a normal sinusoidal trajectory, reaching its usual peak of \(\Phi_m\).

The difference is caused by the switching phase, not a change in the supply voltage’s peak magnitude.

03Why the current suddenly becomes large

So far, we have calculated how much magnetic flux the supply voltage attempts to establish.

But why does this produce such a large current?

The answer is magnetic saturation.

A transformer core is made from ferromagnetic material. Its magnetic properties can be described using a magnetisation curve, which relates magnetic flux density \(B\) to magnetic field strength \(H\).

Flux density is:

\[ B=\frac{\Phi}{A} \]

where:

  • \(B\) is magnetic flux density, measured in tesla (T).
  • \(\Phi\) is magnetic flux, measured in webers.
  • \(A\) is the cross-sectional area of the core, measured in square metres.

Magnetic field strength \(H\) is related to the magnetising current in the winding.

The saturation region

At relatively low flux densities, the core can produce a substantial change in magnetic flux with a comparatively small magnetising current.

However, this relationship is not linear across the entire operating range.

As the magnetic field increases, the core approaches a point called the saturation knee.

Beyond this region, increasing the magnetising current produces a much smaller increase in magnetic flux density.

In other words, the core becomes increasingly difficult to magnetise further.

This means that when the flux demand suddenly increases beyond the normal operating range, the transformer needs a much larger magnetising current.

That current surge is called transformer inrush current.

Notice an important distinction: saturation does not mean the magnetic flux becomes completely fixed. It means that substantially more magnetising current is required to produce further increases in flux.

The flux demanded by the voltage integral can therefore drive the core into saturation, and the current rises sharply in response.

The inrush current can be many times the normal operating current. An IEEE study of transformer energisation reports that peak inrush currents can approach ten times rated current in some cases. This is not a universal value; the actual magnitude depends on transformer design and the electrical network.

There is another important point.

The secondary winding does not need to be connected to a load for inrush current to occur.

The primary still needs to establish the magnetic flux in the core. Consequently, a large current can flow even when the secondary is completely open-circuit.

This is why inrush current should not be confused with the normal load current transformed from the secondary.

04Residual flux makes the problem worse

The flux-doubling effect becomes even more interesting when we consider what happens after a transformer is switched off.

You might expect the magnetic flux in the core to return to zero once the supply is disconnected.

That prediction is not necessarily correct.

Transformer cores are made from ferromagnetic materials, which exhibit a property called magnetic hysteresis.

Hysteresis means that the magnetisation of the material depends partly on its previous magnetic history.

Even after the external magnetising field has been removed, the core can retain some magnetisation.

The remaining magnetic flux is called residual flux, or remanent flux.

It is the starting flux present when the transformer is next energised.

When residual flux reinforces the new flux

Return to the earlier example.

The transformer is switched on at a positive voltage zero crossing, so the supply initially drives positive flux into the core.

Now suppose the core already contains positive residual flux.

The new flux adds to the existing flux.

Instead of starting at zero and reaching \(2\Phi_m\), the prospective peak becomes:

\[ \boxed{\Phi_{\max}=2\Phi_m+\Phi_r} \]

For this particular switching condition, the residual flux makes the saturation problem worse.

If the residual flux points in the opposite direction, it subtracts from the first positive flux excursion.

The peak then becomes:

\[ \Phi_{\max}=2\Phi_m-|\Phi_r| \]

assuming the residual flux opposes that excursion and the resulting positive peak is the largest flux magnitude.

The important principle is that residual flux has a direction. It must be added algebraically, not simply added as a positive magnitude.

This gives us a much better explanation for why two apparently identical transformers can draw different inrush currents when switched on under different conditions.

Their residual flux may be different.

05Switching angle and residual flux work together

We can now combine both effects.

The switching angle determines the flux offset created by energisation, while residual flux determines the initial magnetic condition of the core.

Starting with:

\[ \Phi(t)=\Phi_r+ \Phi_m[\cos\alpha-\cos(\omega t+\alpha)] \]

Rearrange:

\[ \Phi(t)= -\Phi_m\cos(\omega t+\alpha) + \Phi_r+\Phi_m\cos\alpha \]

The final two terms form a constant flux offset in this idealised model.

Define:

\[ \boxed{ C=\Phi_r+\Phi_m\cos\alpha } \]

Therefore:

\[ \Phi(t)=-\Phi_m\cos(\omega t+\alpha)+C \]

This equation reveals exactly how the switching angle and residual flux interact.

The first term is the normal sinusoidal flux.

The second term is the additional offset created by the switching conditions.

In a real transformer, this offset is transient rather than permanently constant. Winding resistance and the electrical network cause it to decay.

Three important switching conditions

Switching conditionResult
Zero-crossing energisation, no residual fluxA flux offset of one normal peak, producing a prospective peak of \(2\Phi_m\).
Voltage-peak energisation, no residual fluxNo additional flux offset; the normal sinusoidal flux is established.
Voltage-peak energisation, non-zero residual fluxThe residual flux remains as an offset and can still increase the peak flux.

The third condition is particularly important.

Switching at the voltage peak is not automatically the best possible switching instant when residual flux is present.

To eliminate the transient offset in the simplified single-phase model, we require:

\[ C=0 \]

Therefore:

\[ \Phi_r+\Phi_m\cos\alpha=0 \]

Rearranging:

\[ \boxed{ \cos\alpha=-\frac{\Phi_r}{\Phi_m} } \]

The ideal switching angle depends on the residual flux already present in the core.

This is a more precise result than simply saying that transformers should always be switched on at a voltage peak.

What happens in a real transformer?

The equations above provide a useful model, but they do not calculate the exact current in a real transformer.

There are several reasons.

First, the transformer has winding resistance and leakage reactance. These affect the voltage actually available to establish the core flux.

Second, once the core saturates, the magnetising current increases sharply. This produces additional voltage drops across the transformer and its supply network.

Third, the magnetic properties of the core are nonlinear and exhibit hysteresis.

Finally, a three-phase transformer can have magnetic coupling between its different core limbs. The optimum switching instant for one phase may not be the optimum instant for another.

The practical inrush current is therefore influenced by:

  • The switching angle.
  • The magnitude and direction of residual flux.
  • The saturation characteristics of the core.
  • The winding resistance and leakage reactance.
  • The impedance of the supply network.
  • The magnetic coupling between phases in a three-phase transformer.

These factors also explain why the transient current eventually decreases.

The winding and network resistances help damp the transient, allowing the flux offset to decay and the transformer to settle into normal operation.

The resulting current waveform is often asymmetric and contains a DC component and harmonics. The initial surge generally decreases over several cycles, although the duration depends on the transformer and network conditions.

Energy Queensland discusses these effects in its engineering standard for transformer energisation. Research published in IEEE Transactions on Industry Applications also investigates how controlled switching can reduce inrush currents while accounting for residual flux and interactions between phases.

06Worked examples

Worked example: calculate the flux doubling during energisation

A single-phase transformer has 500 turns in its primary winding and operates from a 230 V RMS, 50 Hz AC supply. Assume that its secondary winding is open, its residual flux is zero, and winding resistance and leakage reactance are negligible.

The transformer is switched on at a positive voltage zero crossing.

Calculate:

(a) The normal peak magnetic flux.

(b) The prospective maximum magnetic flux during the first half-cycle after energisation.

Step 1

\[ \begin{aligned} V_{\mathrm{rms}}&=230\text{ V}\\ f&=50\text{ Hz}\\ N_p&=500 \end{aligned} \]

The peak supply voltage is:

\[ V_m=\sqrt{2}V_{\mathrm{rms}} \]

\[ V_m=\sqrt{2}\times230 \]

\[ V_m=325.3\text{ V} \]

Step 2

Using the transformer EMF relationship:

\[ \Phi_m=\frac{V_m}{2\pi fN_p} \]

Substitute:

\[ \Phi_m= \frac{325.3}{2\pi\times50\times500} \]

\[ \Phi_m=0.00207\text{ Wb} \]

Therefore:

\[ \boxed{\Phi_m=2.07\text{ mWb}} \]

Step 3

The transformer is switched on at a positive voltage zero crossing, so:

\[ \alpha=0^\circ \]

With zero residual flux:

\[ \Phi(t)=\Phi_m(1-\cos\omega t) \]

At the end of the first half-cycle:

\[ \omega t=180^\circ \]

Therefore:

\[ \Phi_{\max}=2\Phi_m \]

\[ \Phi_{\max}=2\times2.07 \]

\[ \boxed{\Phi_{\max}=4.14\text{ mWb}} \]

Step 4

The prospective flux is twice the normal operating peak flux.

If the transformer core is designed to operate near its saturation knee during normal operation, this sudden increase can drive it deeply into saturation.

A substantial magnetising current is then required.

This is the physical origin of the inrush current.

Worked example: how residual flux changes the best switching instant

A single-phase transformer has a normal peak operating flux of 2.0 mWb.

After being switched off, it retains positive residual flux equal to \(0.40\Phi_m\).

Compare the maximum absolute prospective flux when the transformer is energised at:

(a) A positive voltage peak, \(\alpha=90^\circ\).

(b) A voltage phase of \(\alpha=120^\circ\).

Assume the simplified single-phase model applies.

Step 1

\[ \Phi_r=0.40\Phi_m \]

\[ \Phi_r=0.40\times2.0 \]

\[ \Phi_r=0.80\text{ mWb} \]

Step 2

Recall:

\[ C=\Phi_r+\Phi_m\cos\alpha \]

For \(\alpha=90^\circ\):

\[ C=0.80+2.0\cos90^\circ \]

\[ C=0.80\text{ mWb} \]

The sinusoidal component has an amplitude of 2.0 mWb.

The maximum absolute flux is therefore:

\[ \Phi_{\mathrm{peak}}=\Phi_m+|C| \]

\[ =2.0+0.80 \]

\[ \boxed{\Phi_{\mathrm{peak}}=2.80\text{ mWb}} \]

Step 3

\[ C=0.80+2.0\cos120^\circ \]

Since:

\[ \cos120^\circ=-0.5 \]

We obtain:

\[ C=0.80-1.0 \]

\[ C=-0.20\text{ mWb} \]

Step 4

\[ \Phi_{\mathrm{peak}}=\Phi_m+|C| \]

\[ =2.0+0.20 \]

\[ \boxed{\Phi_{\mathrm{peak}}=2.20\text{ mWb}} \]

Step 5

Switching angleFlux offsetMaximum absolute flux
\(90^\circ\)+0.80 mWb2.80 mWb
\(120^\circ\)−0.20 mWb2.20 mWb

The \(120^\circ\) switching condition produces a smaller prospective flux peak.

Why?

The switching-induced offset partially cancels the positive residual flux.

This example demonstrates why the voltage peak is not necessarily the optimum switching instant when a transformer retains residual magnetism.

07Questions and solutions

Question 1

A transformer is switched on while its secondary winding is disconnected from any load.

A large current briefly flows through the primary winding before settling to a much smaller alternating current.

Explain why the initial current surge is not caused by the secondary load. Identify the physical mechanism responsible for it.

Solution 1

The initial current surge is magnetising inrush current, caused by the transformer core entering magnetic saturation.

The secondary winding is open, so there is no secondary load current.

However, the primary winding must still establish the changing magnetic flux required for transformer operation.

Depending on the switching angle and residual flux, the initial magnetic flux can exceed its normal operating peak.

If the core enters saturation, its incremental permeability decreases. A much larger magnetising current is then needed to produce further changes in magnetic flux.

As the transient decays, the core returns to its normal operating range, and the primary current settles towards its much smaller steady-state magnetising current.

The key distinction is that magnetising current exists even without a secondary load.

Question 2

A transformer has a normal peak operating flux of 1.8 mWb.

It is switched on at a positive voltage zero crossing, and its residual flux is initially:

(a) \(+0.50\text{ mWb}\).

(b) \(-0.50\text{ mWb}\).

Using the simplified flux model, calculate the prospective positive flux peak during the first half-cycle for each condition.

Explain why the two results differ.

Solution 2

The prospective positive flux peaks are 4.1 mWb and 3.1 mWb, respectively.

The difference is caused by the direction of residual flux relative to the initial flux excursion.

At a positive voltage zero crossing:

\[ \Phi_{\max}=2\Phi_m+\Phi_r \]

where \(\Phi_m=1.8\text{ mWb}\).

(a) Positive residual flux

Substitute:

\[ \Phi_{\max}=2(1.8)+0.50 \]

\[ \boxed{\Phi_{\max}=4.10\text{ mWb}} \]

The residual flux points in the same direction as the initial flux excursion.

It therefore reinforces the flux produced by the applied voltage.

(b) Negative residual flux

Now substitute:

\[ \Phi_{\max}=2(1.8)-0.50 \]

\[ \boxed{\Phi_{\max}=3.10\text{ mWb}} \]

The residual flux opposes the initial positive flux excursion.

Consequently, the positive peak is smaller.

The important principle: Residual flux must be treated as a signed quantity. Its direction determines whether it increases or decreases the flux excursion produced during energisation.

Question 3

A single-phase transformer is energised under two different switching conditions.

Its residual flux is unknown, but its magnitude is known to be less than its normal peak flux.

An idealised model predicts the following maximum absolute prospective flux values:

  • Switching at a positive voltage zero crossing: \(2.6\Phi_m\).
  • Switching at a negative voltage zero crossing: \(1.4\Phi_m\).

Determine the magnitude and direction of the residual flux relative to the positive flux reference.

Show that your result is consistent with both observations.

Solution 3

The residual flux is:

\[ \boxed{\Phi_r=+0.60\Phi_m} \]

It is positive, meaning that it reinforces the initial positive flux excursion when the transformer is switched on at the positive voltage zero crossing.

To establish this, use the general expression for the flux offset:

\[ C=\Phi_r+\Phi_m\cos\alpha \]

The maximum absolute prospective flux is:

\[ \Phi_{\mathrm{peak}}=\Phi_m+|C| \]

Step 1: Consider the positive voltage zero crossing.

Here:

\[ \alpha=0^\circ \]

Therefore:

\[ 2.6\Phi_m = \Phi_m+|\Phi_r+\Phi_m| \]

We are told that:

\[ |\Phi_r|<\Phi_m \]

Consequently, \(\Phi_r+\Phi_m\) must be positive.

So:

\[ 2.6\Phi_m=2\Phi_m+\Phi_r \]

Rearranging:

\[ \Phi_r=0.6\Phi_m \]

Step 2: Check the negative voltage zero crossing.

Here:

\[ \alpha=180^\circ \]

Therefore:

\[ C=\Phi_r-\Phi_m \]

Substitute the inferred residual flux:

\[ C=0.6\Phi_m-\Phi_m \]

\[ C=-0.4\Phi_m \]

The maximum absolute flux becomes:

\[ \Phi_{\mathrm{peak}} = \Phi_m+|-0.4\Phi_m| \]

\[ \boxed{\Phi_{\mathrm{peak}}=1.4\Phi_m} \]

This matches the second observation.

The two measurements independently confirm the same residual flux.

The tempting approach would be to treat both switching conditions as producing identical flux excursions because the supply has the same voltage magnitude.

However, the initial magnetic condition changes the flux offset. Reversing the voltage zero crossing changes whether the switching-induced offset reinforces or opposes the residual flux.

Question 4

An unloaded transformer has a primary winding resistance of \(0.15\,\Omega\).

During energisation, the instantaneous primary current magnitude reaches 48 A. Its normal steady-state magnetising current magnitude at a comparable point in the cycle is 8 A.

(a) Calculate the instantaneous copper power loss at each current magnitude.

(b) Determine the ratio of the two power losses.

(c) Explain why this does not mean the transformer delivers 36 times its normal output power, or necessarily receives 36 times as much thermal energy during the entire transient.

Solution 4

The instantaneous copper power loss is 345.6 W during the surge and 9.6 W at the normal current magnitude.

The surge produces 36 times the instantaneous resistive heating rate at the stated current magnitudes.

(a) Calculate the copper power losses.

For a winding with resistance \(R\):

\[ p_{\mathrm{Cu}}=i^2R \]

where \(i\) is the instantaneous current.

During inrush:

\[ p_{\mathrm{inrush}}=48^2\times0.15 \]

\[ \boxed{p_{\mathrm{inrush}}=345.6\text{ W}} \]

During normal magnetising operation:

\[ p_{\mathrm{normal}}=8^2\times0.15 \]

\[ \boxed{p_{\mathrm{normal}}=9.6\text{ W}} \]

(b) Calculate the ratio.

\[ \frac{p_{\mathrm{inrush}}}{p_{\mathrm{normal}}} = \frac{345.6}{9.6} \]

\[ \boxed{\text{Ratio}=36:1} \]

This follows directly from the square relationship between current and resistive power loss.

(c) Explain the significance.

The 36:1 ratio describes the instantaneous rate of resistive heating, not the total energy dissipated over the transient.

Total copper heating energy depends on the current waveform and how long the surge lasts:

\[ E_{\mathrm{heat}}=\int i^2R\,dt \]

A short current surge can therefore produce a very different total energy loss from a sustained current of the same magnitude.

Furthermore, the secondary winding is open, so no useful power is being delivered to a secondary load.

The large primary current is predominantly associated with establishing the magnetic flux and driving the core through its nonlinear magnetisation characteristic.

The distinction is between instantaneous current, resistive heating, and useful output power. They are related, but they are not interchangeable.

Question 5

A single-phase transformer has a positive residual flux equal to \(0.60\Phi_m\), where \(\Phi_m\) is its normal peak operating flux.

A student argues that the transformer should always be switched on at the positive voltage peak, \(90^\circ\), because this eliminates the flux-doubling effect.

Using the simplified single-phase model:

(a) Determine the switching angle or angles that eliminate the transient flux offset.

(b) Calculate the maximum absolute prospective flux if the transformer is instead switched on at \(90^\circ\).

(c) Explain why eliminating the transient flux offset does not guarantee zero inrush current in a real three-phase transformer with a shared magnetic core.

Solution 5

The two switching angles that eliminate the transient flux offset in the idealised single-phase model are:

\[ \boxed{\alpha=126.9^\circ\text{ or }233.1^\circ} \]

Switching at \(90^\circ\) does not eliminate the offset because the transformer already contains positive residual flux.

Furthermore, eliminating the transient offset does not guarantee zero magnetising current or eliminate every source of inrush in a real three-phase transformer.

(a) Determine the optimal switching angles.

Recall the flux offset:

\[ C=\Phi_r+\Phi_m\cos\alpha \]

To eliminate the transient offset:

\[ C=0 \]

Therefore:

\[ \Phi_r+\Phi_m\cos\alpha=0 \]

Rearrange:

\[ \cos\alpha=-\frac{\Phi_r}{\Phi_m} \]

Given:

\[ \Phi_r=0.60\Phi_m \]

We obtain:

\[ \cos\alpha=-0.60 \]

Taking the inverse cosine:

\[ \alpha=\cos^{-1}(-0.60) \]

\[ \alpha=126.9^\circ \]

Cosine is also negative in the third quadrant, giving the second solution:

\[ \alpha=360^\circ-126.9^\circ \]

\[ \alpha=233.1^\circ \]

Both switching angles eliminate the constant flux offset in this idealised model.

(b) Calculate the maximum flux at \(90^\circ\).

Substitute into the offset equation:

\[ C=\Phi_r+\Phi_m\cos90^\circ \]

Since:

\[ \cos90^\circ=0 \]

We obtain:

\[ C=0.60\Phi_m \]

The maximum absolute prospective flux is:

\[ \Phi_{\mathrm{peak}}=\Phi_m+|C| \]

Therefore:

\[ \boxed{\Phi_{\mathrm{peak}}=1.60\Phi_m} \]

The student’s prediction fails because switching at the voltage peak only eliminates the switching-induced offset when the initial residual flux is zero.

Here, the residual flux remains present and shifts the entire flux waveform.

(c) Explain the limitations in a real three-phase transformer.

Eliminating the offset in one idealised single-phase model does not guarantee that all three phases of a real transformer will be energised without an inrush transient.

There are several reasons.

First, the three phases may have different residual flux magnitudes and directions.

Second, the magnetic fluxes in a shared three-legged core are coupled. Changing the flux in one limb affects the magnetic conditions in the other limbs.

Third, real transformers have winding resistance, leakage reactance, nonlinear saturation characteristics, and finite supply impedance.

These effects influence both the current magnitude and the actual flux trajectory.

Consequently, practical controlled switching requires consideration of the individual phases and the magnetic design of the transformer.

Research by Mitra, Xu and Benidris, published in IEEE Transactions on Industry Applications, demonstrates why phase coupling and residual flux must both be considered when developing switching strategies for three-phase transformers.

The deeper lesson is that a mathematical model can identify an ideal condition without guaranteeing that every assumption behind that model holds in a real physical system.

08Where this leads next

Transformer inrush current brings together three ideas that are easy to study separately but much more interesting when combined:

  • Faraday’s law determines how the applied voltage changes magnetic flux.
  • Magnetic hysteresis determines the residual flux present before energisation.
  • Magnetic saturation determines how much current is required when the core is driven beyond its normal operating range.

The next useful concept is AC impedance.

Once the core enters saturation, the magnetising current is influenced by the winding resistance, leakage reactance, and impedance of the supply network. These determine how large the actual current surge becomes, rather than simply how much flux the idealised voltage integral predicts.

This is the connection between predicting a transformer’s magnetic behaviour and understanding the current waveform measured in a real electrical power system.

Transformer energisation and controlled switching are specialist electrical engineering activities involving hazardous voltages and protection systems, not experiments to attempt with an ordinary mains transformer.

09Sources and further reading

The following sources support the transformer models, loss mechanisms, and inrush-current explanations developed in this article.

  1. NESA – Physics 11-12 Syllabus (2025). Official syllabus structure and implementation information.

  2. Indian Institute of Technology Madras – Electrical Machines I: Practical Transformer. University teaching material covering leakage flux, winding resistance, magnetic saturation, and core losses.

  3. Energy Queensland – Standard for Plant Energisation (STNW1179). Engineering treatment of transformer energisation, residual flux, switching angle, saturation, and network impedance.

  4. Joydeep Mitra, Xufeng Xu and Mohammed Benidris – Reduction of Three-Phase Transformer Inrush Currents Using Controlled Switching, IEEE Transactions on Industry Applications, 2020. Research examining transformer saturation, residual flux, three-phase magnetic coupling, and controlled switching.