How to Analyse Two Transformers and Transmission-Line Losses
Learn how to track voltage, current, and power through two transformers and a resistive transmission line. Follow worked HSC Physics examples to calculate line losses, load power, and the complete energy budget.
A generator supplies 60.0 kW to a step-up transformer, a transmission line, and a step-down transformer. The load receives 59.5 kW. If both transformers are ideal, where did the missing 0.5 kW go?
It became thermal energy in the transmission line.
The key to analysing this entire system is to keep three calculations separate:
- Transformer 1: Calculate how the voltage and current change. For an ideal transformer, power is conserved.
- Transmission line: Calculate the power converted into heat using \(P_{\mathrm{loss}}=I^2R\).
- Transformer 2: Transfer the remaining power to the load, changing the voltage and current again.
The order matters. In particular, you must calculate transmission-line losses using the current in the transmission line, not the current at the generator or the load.
Before working through the numbers, make a prediction: if the generator current is 250 A and the load current is 312.5 A, which current belongs in the line-loss equation?
Neither. You need the current between the two transformers.
01The system: two transformers and one transmission line
Picture the electricity travelling through four stages:
- The generator supplies electrical power to the primary coil of the first transformer.
- The first transformer increases the voltage and reduces the current.
- The transmission line carries the electrical power, converting some of it into heat because of its resistance.
- The second transformer reduces the voltage and increases the current before delivering the remaining power to the load.
The important observation is that the current changes at each transformer, but the current remains constant along the transmission line in this simplified series model.
That means the generator current, transmission current, and load current are generally three different values.
02Establish the assumptions first
Before calculating anything, identify which parts of the system are ideal and which can lose energy.
For the examples in this article, use the following model.
| Component | Assumption | Energy behaviour |
|---|---|---|
| First transformer | Ideal | Input power equals output power |
| Transmission line | Resistive | Some electrical power becomes thermal energy |
| Second transformer | Ideal | Input power equals output power |
| Load | Resistive | Receives the remaining electrical power |
We also assume:
- All voltages and currents are RMS values.
- The load has a power factor of 1, so \(P=VI\).
- The transmission line has a constant resistance.
- The stated line resistance includes both outgoing and return conductors unless otherwise specified.
- The system operates steadily, so power remains constant during the stated time interval.
The ideal-transformer assumption is particularly important.
An ideal transformer has no copper losses, no eddy-current losses, and no other energy losses. It changes voltage and current without changing the total power transferred.
The transmission line, however, is deliberately treated as resistive. Its resistance is where the energy loss occurs in this model.
If a question supplies transformer efficiencies, you must account for those losses separately rather than assuming the transformers are ideal.
03Step 1: Calculate the current transformation at the first transformer
An ideal transformer follows two important relationships.
The voltage ratio is determined by the turns ratio:
\[ \frac{V_s}{V_p}=\frac{N_s}{N_p} \]
The power entering and leaving the transformer is equal:
\[ V_pI_p=V_sI_s \]
Here:
- \(V_p\) is the primary voltage, in volts.
- \(V_s\) is the secondary voltage, in volts.
- \(I_p\) is the primary current, in amperes.
- \(I_s\) is the secondary current, in amperes.
- \(N_p\) is the number of primary coil turns.
- \(N_s\) is the number of secondary coil turns.
Combining the two relationships gives the current ratio:
\[ \frac{I_s}{I_p}=\frac{N_p}{N_s} \]
Notice that the current ratio is the inverse of the voltage ratio.
A step-up transformer increases voltage but decreases current. A step-down transformer does the opposite.
For example, suppose a transformer has 40 times as many secondary turns as primary turns.
Its secondary voltage increases by a factor of 40, while its secondary current decreases by a factor of 40, provided the same power is transferred.
This is not energy disappearing. The transformer is changing the combination of voltage and current used to transfer that energy.
If you want to revise this relationship independently of transmission-line losses, see Ideal Transformer Current and Power for HSC Physics.
04Step 2: Calculate the transmission-line losses
Once you know the current leaving the first transformer, you can calculate the energy dissipated in the transmission line.
A wire with resistance converts electrical energy into thermal energy.
The rate of this energy transfer is:
\[ P_{\mathrm{loss}}=I_{\mathrm{line}}^2R_{\mathrm{line}} \]
where:
- \(P_{\mathrm{loss}}\) is the power converted into heat, in watts.
- \(I_{\mathrm{line}}\) is the current through the transmission line, in amperes.
- \(R_{\mathrm{line}}\) is the total resistance of the transmission line, in ohms.
The square on the current is important.
If the transmission current is halved, the power loss becomes one-quarter of its original value, provided the resistance stays constant.
However, be careful about which current you use.
The transmission-line current is the secondary current of the first transformer and the primary current of the second transformer.
It is not generally equal to the generator current or the load current.
What happens to the voltage along the line?
The resistance also produces a voltage drop.
Using Ohm’s law:
\[ \Delta V_{\mathrm{line}}=I_{\mathrm{line}}R_{\mathrm{line}} \]
Therefore:
\[ V_{\mathrm{receive}} = V_{\mathrm{send}}-\Delta V_{\mathrm{line}} \]
The receiving voltage is lower than the sending voltage.
The power reaching the second transformer is consequently:
\[ P_{\mathrm{receive}} = P_{\mathrm{send}}-P_{\mathrm{loss}} \]
You can check this independently using:
\[ P_{\mathrm{receive}} = V_{\mathrm{receive}}I_{\mathrm{line}} \]
Both methods should produce the same answer under our assumptions.
One detail about resistance is worth remembering. If a question gives the resistance of each transmission conductor separately, add the two resistances. The current travels through the outgoing conductor and returns through the other conductor.
If the question already gives the total loop resistance, do not double it again.
05Step 3: Calculate what reaches the load
The second transformer receives the power remaining after transmission-line losses.
If the second transformer is ideal:
\[ P_{\mathrm{load}}=P_{\mathrm{receive}} \]
Its turns ratio determines the output voltage:
\[ \frac{V_{\mathrm{load}}}{V_{\mathrm{receive}}} = \frac{N_{s2}}{N_{p2}} \]
Once you know the output voltage, calculate the load current using:
\[ I_{\mathrm{load}} = \frac{P_{\mathrm{load}}}{V_{\mathrm{load}}} \]
You can also use the inverse current-to-turns relationship:
\[ I_{\mathrm{load}} = I_{\mathrm{line}} \frac{N_{p2}}{N_{s2}} \]
These two methods should agree.
The important detail is that you must use the power remaining after the transmission-line loss, not the original generator power.
06The complete power budget
The entire system can now be represented by three power relationships.
For the first ideal transformer:
\[ P_{\mathrm{T1,out}}=P_{\mathrm{generator}} \]
For the transmission line:
\[ P_{\mathrm{T2,in}} = P_{\mathrm{T1,out}}-I_{\mathrm{line}}^2R_{\mathrm{line}} \]
For the second ideal transformer:
\[ P_{\mathrm{load}}=P_{\mathrm{T2,in}} \]
Combining them gives:
\[ \boxed{ P_{\mathrm{generator}} = P_{\mathrm{line\,loss}}+P_{\mathrm{load}} } \]
This is the central energy-budget relationship.
If the system operates for a known time, convert the powers into energies using:
\[ E=Pt \]
For constant power:
\[ E_{\mathrm{generator}} = E_{\mathrm{line\,heat}}+E_{\mathrm{load}} \]
Use joules when power is in watts and time is in seconds. You can use kilowatt-hours when power is in kilowatts and time is in hours.
07A model investigation: Where does the missing power go?
Imagine investigating a model electricity transmission system to determine whether the transformers or the transmission line account for the difference between the generator’s output and the load’s input.
The apparatus follows the same sequence described earlier:
- An AC source connects to the primary coil of T1.
- The secondary coil of T1 connects to the transmission-line conductors.
- The conductors connect to the primary coil of T2.
- The secondary coil of T2 supplies a resistive load.
Ammeters are placed in series with the generator, transmission line, and load. Voltmeters measure the potential difference across the relevant sections.
This is a model investigation, not a report of measured experimental results.
What should the apparatus show?
The prediction is straightforward.
The first ideal transformer should transfer the same power it receives. The transmission line should dissipate some power as heat. The second ideal transformer should transfer all the power reaching its primary to its secondary.
Therefore, the difference between the generator power and the load power should equal the transmission-line loss.
Why measuring voltage alone is insufficient
Suppose the first design uses only voltmeters at the generator and load.
A student might compare the two voltage readings and interpret their ratio as the system’s efficiency.
That is incorrect.
The transformers deliberately change the voltage. A lower voltage at the load does not necessarily mean that a large amount of energy has been lost.
The revised measurement method must measure both voltage and current at each relevant boundary. Multiplying the corresponding values gives the power transferred at that stage.
The first worked example shows why this matters.
08Worked example: Follow 60 kW through both transformers and the line
A generator supplies 60.0 kW at 240 V to an ideal step-up transformer with a secondary-to-primary turns ratio of 40:1.
The transformer feeds a transmission line with a total resistance of 12.8 Ω.
At the receiving end, an ideal step-down transformer has a primary-to-secondary turns ratio of 50:1.
The system operates continuously for 2.00 hours.
Calculate:
- The generator current.
- The transmission voltage and current.
- The transmission-line voltage drop and power loss.
- The voltage, current, and power delivered to the load.
- The energy supplied, lost as heat, and delivered to the load over 2.00 hours.
Step 1
Start with the power equation:
\[ P=VI \]
Rearrange:
\[ I=\frac{P}{V} \]
Substitute the generator values:
\[ I_{\mathrm{generator}} = \frac{60\,000}{240} \]
\[ \boxed{I_{\mathrm{generator}}=250\ \mathrm{A}} \]
The generator supplies 250 A to the primary coil of T1.
Step 2
The first transformer has a turns ratio of 40:1.
Therefore, its secondary voltage is:
\[ V_{\mathrm{send}}=40(240) \]
\[ \boxed{V_{\mathrm{send}}=9600\ \mathrm{V}} \]
Because the transformer is ideal, its output power remains 60.0 kW.
Calculate the transmission current:
\[ I_{\mathrm{line}} = \frac{60\,000}{9600} \]
\[ \boxed{I_{\mathrm{line}}=6.25\ \mathrm{A}} \]
Notice what has happened.
The voltage has increased by a factor of 40, while the current has decreased by a factor of 40.
Step 3
Use:
\[ P_{\mathrm{loss}}=I_{\mathrm{line}}^2R_{\mathrm{line}} \]
Substitute:
\[ P_{\mathrm{loss}}=(6.25)^2(12.8) \]
\[ \boxed{P_{\mathrm{loss}}=500\ \mathrm{W}} \]
The transmission line converts 500 W of electrical power into thermal energy.
Now calculate the voltage drop:
\[ \Delta V_{\mathrm{line}}=I_{\mathrm{line}}R_{\mathrm{line}} \]
\[ \Delta V_{\mathrm{line}}=6.25(12.8) \]
\[ \boxed{\Delta V_{\mathrm{line}}=80\ \mathrm{V}} \]
Therefore, the voltage reaching T2 is:
\[ V_{\mathrm{receive}}=9600-80 \]
\[ \boxed{V_{\mathrm{receive}}=9520\ \mathrm{V}} \]
Step 4
Subtract the line loss from the power leaving the first transformer:
\[ P_{\mathrm{receive}}=60\,000-500 \]
\[ \boxed{P_{\mathrm{receive}}=59\,500\ \mathrm{W}} \]
Check using the receiving voltage and line current:
\[ P_{\mathrm{receive}}=9520(6.25) \]
\[ P_{\mathrm{receive}}=59\,500\ \mathrm{W} \]
Both methods agree.
This is the power available to the second transformer.
Step 5
The second transformer has a primary-to-secondary turns ratio of 50:1.
Therefore:
\[ V_{\mathrm{load}}=\frac{9520}{50} \]
\[ \boxed{V_{\mathrm{load}}=190.4\ \mathrm{V}} \]
Because T2 is ideal, its output power is still 59,500 W.
Calculate the load current:
\[ I_{\mathrm{load}} = \frac{59\,500}{190.4} \]
\[ \boxed{I_{\mathrm{load}}=312.5\ \mathrm{A}} \]
The current also agrees with the transformer current ratio:
\[ I_{\mathrm{load}}=50(6.25)=312.5\ \mathrm{A} \]
Step 6
First, calculate the energy supplied by the generator:
\[ E_{\mathrm{generator}}=60.0(2.00) \]
\[ E_{\mathrm{generator}}=120\ \mathrm{kWh} \]
Next, calculate the energy converted into heat:
\[ E_{\mathrm{loss}}=0.500(2.00) \]
\[ E_{\mathrm{loss}}=1.00\ \mathrm{kWh} \]
Finally, calculate the energy delivered to the load:
\[ E_{\mathrm{load}}=59.5(2.00) \]
\[ E_{\mathrm{load}}=119\ \mathrm{kWh} \]
Check the complete budget:
\[ 120=1+119 \]
The energy supplied by the generator is accounted for exactly.
The complete set of results
| Position | Voltage | Current | Power |
|---|---|---|---|
| Generator / T1 primary | 240 V | 250 A | 60.0 kW |
| T1 secondary / line input | 9.60 kV | 6.25 A | 60.0 kW |
| Line output / T2 primary | 9.52 kV | 6.25 A | 59.5 kW |
| T2 secondary / load | 190.4 V | 312.5 A | 59.5 kW |
Energy budget balances
\[ 120\ \mathrm{kWh} = 1.00\ \mathrm{kWh} + 119\ \mathrm{kWh} \]
What would the voltage-only measurement suggest?
Compare the generator voltage and load voltage:
\[ \frac{190.4}{240}\times100 = 79.3\% \]
A student might interpret this as an efficiency of 79.3%.
But the current has also changed, from 250 A to 312.5 A.
The actual system efficiency is:
\[ \eta = \frac{P_{\mathrm{load}}}{P_{\mathrm{generator}}} \times100 \]
\[ \eta = \frac{59\,500}{60\,000}\times100 \]
\[ \boxed{\eta=99.17\%} \]
The voltage ratio alone was not enough to determine the efficiency.
This is exactly why the investigation needs both voltage and current measurements.
09A useful contrast: What if the transmission voltage were lower?
Consider two systems transmitting the same power of 18 kW through a line with a total resistance of 12 Ω.
The only difference is the voltage at which the power enters the line.
| Quantity | Lower-voltage system | Higher-voltage system |
|---|---|---|
| Sending voltage | 600 V | 18,000 V |
| Sending power | 18 kW | 18 kW |
| Line current | 30 A | 1 A |
| Voltage drop | 360 V | 12 V |
| Line power loss | 10.8 kW | 12 W |
| Power received | 7.2 kW | 17.988 kW |
The higher-voltage system has a current 30 times smaller.
Since power loss depends on the square of current:
\[ \frac{P_{\mathrm{loss,low}}} {P_{\mathrm{loss,high}}} = 30^2 \]
\[ \boxed{\text{Loss ratio}=900:1} \]
The higher-voltage system loses 900 times less power in the line.
This comparison assumes that the transmitted power and line resistance remain constant.
That condition is essential. If the load changes and the transmitted power is no longer fixed, you cannot automatically use the same current-reduction argument.
For a broader explanation of why electricity networks use high transmission voltages, see High-Voltage Electricity Transmission for HSC Physics.
10Worked example: Account for both transmission conductors and operating time
A generator supplies 36.0 kW at 600 V to an ideal step-up transformer with a secondary-to-primary turns ratio of 30:1.
The transmission line consists of two conductors, each with a resistance of 6.0 Ω.
An ideal step-down transformer at the receiving end has a primary-to-secondary turns ratio of 60:1.
The system operates for 1.50 hours.
Calculate the line current, line power loss, receiving voltage, load voltage and current, and the energy lost as heat during operation.
Step 1
\[ I_{\mathrm{generator}} = \frac{P_{\mathrm{generator}}}{V_{\mathrm{generator}}} \]
\[ I_{\mathrm{generator}} = \frac{36\,000}{600} \]
\[ \boxed{I_{\mathrm{generator}}=60.0\ \mathrm{A}} \]
Step 2
The first transformer increases the voltage by a factor of 30:
\[ V_{\mathrm{send}}=30(600) \]
\[ V_{\mathrm{send}}=18\,000\ \mathrm{V} \]
The transformer is ideal, so the transmitted power remains 36.0 kW.
Therefore:
\[ I_{\mathrm{line}} = \frac{36\,000}{18\,000} \]
\[ \boxed{I_{\mathrm{line}}=2.00\ \mathrm{A}} \]
Step 3
There are two conductors, each with a resistance of 6.0 Ω.
The current travels through both conductors, so:
\[ R_{\mathrm{line}}=6.0+6.0 \]
\[ \boxed{R_{\mathrm{line}}=12.0\ \Omega} \]
This is a common place to lose marks. Using only one conductor’s resistance would underestimate the line loss by a factor of two.
Step 4
The voltage drop is:
\[ \Delta V_{\mathrm{line}} = I_{\mathrm{line}}R_{\mathrm{line}} \]
\[ \Delta V_{\mathrm{line}}=2.00(12.0) \]
\[ \boxed{\Delta V_{\mathrm{line}}=24.0\ \mathrm{V}} \]
The resistive power loss is:
\[ P_{\mathrm{loss}} = I_{\mathrm{line}}^2R_{\mathrm{line}} \]
\[ P_{\mathrm{loss}}=(2.00)^2(12.0) \]
\[ \boxed{P_{\mathrm{loss}}=48.0\ \mathrm{W}} \]
Step 5
The receiving voltage is:
\[ V_{\mathrm{receive}}=18\,000-24 \]
\[ \boxed{V_{\mathrm{receive}}=17\,976\ \mathrm{V}} \]
The power reaching T2 is:
\[ P_{\mathrm{receive}}=36\,000-48 \]
\[ \boxed{P_{\mathrm{receive}}=35\,952\ \mathrm{W}} \]
Step 6
The second transformer reduces the voltage by a factor of 60:
\[ V_{\mathrm{load}} = \frac{17\,976}{60} \]
\[ \boxed{V_{\mathrm{load}}=299.6\ \mathrm{V}} \]
Its secondary current is:
\[ I_{\mathrm{load}}=60(2.00) \]
\[ \boxed{I_{\mathrm{load}}=120\ \mathrm{A}} \]
Check the output power:
\[ P_{\mathrm{load}}=299.6(120) \]
\[ \boxed{P_{\mathrm{load}}=35\,952\ \mathrm{W}} \]
The load receives exactly the power available at the second transformer’s primary.
Step 7
Convert the operating time into hours, which is already given as 1.50 hours.
\[ E_{\mathrm{loss}}=P_{\mathrm{loss}}t \]
\[ E_{\mathrm{loss}}=48.0(1.50) \]
\[ E_{\mathrm{loss}}=72.0\ \mathrm{Wh} \]
Therefore:
\[ \boxed{E_{\mathrm{loss}}=0.0720\ \mathrm{kWh}} \]
The complete energy budget is:
\[ E_{\mathrm{generator}}=36.0(1.50)=54.0\ \mathrm{kWh} \]
\[ E_{\mathrm{load}}=35.952(1.50)=53.928\ \mathrm{kWh} \]
And:
\[ 54.0=0.072+53.928 \]
Again, the energy budget balances.
11A reliable decision process for exam questions
When a question contains two transformers and a transmission line, work through the stages in this order.
| Stage | What you calculate | Main relationship |
|---|---|---|
| Generator | Initial current | \(I=P/V\) |
| First transformer | Transmission voltage | \(V_s/V_p=N_s/N_p\) |
| First transformer | Transmission current | \(P_p=P_s\) |
| Transmission line | Voltage drop | \(\Delta V=IR\) |
| Transmission line | Resistive power loss | \(P_{\mathrm{loss}}=I^2R\) |
| Second transformer | Load voltage | \(V_s/V_p=N_s/N_p\) |
| Second transformer | Load current | \(P_p=P_s\) |
| Entire system | Energy transferred | \(E=Pt\) |
Before accepting your final answer, check three things:
- The power reaching the load must be less than the generator power if the line has non-zero resistance.
- The difference between those powers must equal the calculated line loss when both transformers are ideal.
- The current used in \(I^2R\) must be the transmission-line current.
If your calculated load power is greater than the generator power, something has gone wrong with the current ratio, power budget, or line-loss calculation.
12Questions and solutions
The following questions move from a standard transmission calculation towards problems where you need to challenge an assumption about how the system behaves.
Question 1
A generator supplies 24.0 kW at 400 V to an ideal step-up transformer with a secondary-to-primary turns ratio of 20:1.
The transmission line has a total resistance of 5.0 Ω. At the receiving end, an ideal step-down transformer has a primary-to-secondary turns ratio of 40:1.
Calculate:
- The generator current.
- The transmission-line current.
- The power lost in the transmission line.
- The voltage reaching the second transformer.
- The load voltage, current, and power.
Solution 1
The transmission-line current is 3.00 A, the line loses 45.0 W, and the load receives 23.955 kW at 199.625 V and 120 A.
Step 1: Calculate the generator current.
\[ I_{\mathrm{generator}} = \frac{24\,000}{400} \]
\[ \boxed{I_{\mathrm{generator}}=60.0\ \mathrm{A}} \]
Step 2: Calculate the transmission voltage.
The first transformer increases the voltage by a factor of 20:
\[ V_{\mathrm{send}}=20(400) \]
\[ V_{\mathrm{send}}=8000\ \mathrm{V} \]
Step 3: Calculate the transmission current.
Because the transformer is ideal, the transmitted power remains 24,000 W.
\[ I_{\mathrm{line}} = \frac{24\,000}{8000} \]
\[ \boxed{I_{\mathrm{line}}=3.00\ \mathrm{A}} \]
Step 4: Calculate the line loss.
\[ P_{\mathrm{loss}}=I^2R \]
\[ P_{\mathrm{loss}}=(3.00)^2(5.0) \]
\[ \boxed{P_{\mathrm{loss}}=45.0\ \mathrm{W}} \]
The voltage drop is:
\[ \Delta V=3.00(5.0)=15.0\ \mathrm{V} \]
Therefore:
\[ V_{\mathrm{receive}}=8000-15 \]
\[ \boxed{V_{\mathrm{receive}}=7985\ \mathrm{V}} \]
Step 5: Calculate the power reaching T2.
\[ P_{\mathrm{receive}}=24\,000-45 \]
\[ \boxed{P_{\mathrm{receive}}=23\,955\ \mathrm{W}} \]
Step 6: Calculate the load voltage and current.
The second transformer reduces the voltage by a factor of 40:
\[ V_{\mathrm{load}}=\frac{7985}{40} \]
\[ \boxed{V_{\mathrm{load}}=199.625\ \mathrm{V}} \]
The current increases by a factor of 40:
\[ I_{\mathrm{load}}=40(3.00) \]
\[ \boxed{I_{\mathrm{load}}=120\ \mathrm{A}} \]
Check the load power:
\[ P_{\mathrm{load}}=199.625(120) \]
\[ \boxed{P_{\mathrm{load}}=23\,955\ \mathrm{W}} \]
The result agrees with the power reaching T2, as expected for an ideal transformer.
Question 2
A generator supplies 48.0 kW at 800 V to an ideal step-up transformer with a secondary-to-primary turns ratio of 25:1.
The transmission line consists of two conductors, each with a resistance of 4.0 Ω. An ideal step-down transformer at the receiving end has a primary-to-secondary turns ratio of 50:1.
The system operates continuously for 2.50 hours.
Calculate:
- The generator current and transmission-line current.
- The total transmission-line resistance.
- The voltage drop and power loss in the line.
- The voltage and current delivered to the load.
- The energy converted into heat and the energy delivered to the load.
A student calculates the line loss using a resistance of 4.0 Ω. Explain why this is incorrect.
Solution 2
The line current is 2.40 A, the total line resistance is 8.0 Ω, and the line loses 46.08 W. Over 2.50 hours, 0.1152 kWh becomes heat and 119.8848 kWh reaches the load.
Step 1: Calculate the generator current.
\[ I_{\mathrm{generator}} = \frac{48\,000}{800} \]
\[ \boxed{I_{\mathrm{generator}}=60.0\ \mathrm{A}} \]
Step 2: Calculate the transmission voltage.
\[ V_{\mathrm{send}}=25(800) \]
\[ \boxed{V_{\mathrm{send}}=20\,000\ \mathrm{V}} \]
Since T1 is ideal, the power remains 48,000 W.
\[ I_{\mathrm{line}} = \frac{48\,000}{20\,000} \]
\[ \boxed{I_{\mathrm{line}}=2.40\ \mathrm{A}} \]
Step 3: Calculate the total line resistance.
The outgoing and return conductors are in series.
\[ R_{\mathrm{line}}=4.0+4.0 \]
\[ \boxed{R_{\mathrm{line}}=8.0\ \Omega} \]
Using only 4.0 Ω would ignore the return conductor.
Step 4: Calculate the line voltage drop and power loss.
\[ \Delta V=IR \]
\[ \Delta V=2.40(8.0) \]
\[ \boxed{\Delta V=19.2\ \mathrm{V}} \]
Now calculate the resistive power loss:
\[ P_{\mathrm{loss}}=I^2R \]
\[ P_{\mathrm{loss}}=(2.40)^2(8.0) \]
\[ \boxed{P_{\mathrm{loss}}=46.08\ \mathrm{W}} \]
Step 5: Calculate the receiving voltage and power.
\[ V_{\mathrm{receive}}=20\,000-19.2 \]
\[ \boxed{V_{\mathrm{receive}}=19\,980.8\ \mathrm{V}} \]
The power reaching T2 is:
\[ P_{\mathrm{receive}}=48\,000-46.08 \]
\[ \boxed{P_{\mathrm{receive}}=47\,953.92\ \mathrm{W}} \]
Step 6: Calculate the load voltage and current.
The second transformer has a primary-to-secondary turns ratio of 50:1.
\[ V_{\mathrm{load}} = \frac{19\,980.8}{50} \]
\[ \boxed{V_{\mathrm{load}}=399.616\ \mathrm{V}} \]
The output current is:
\[ I_{\mathrm{load}}=50(2.40) \]
\[ \boxed{I_{\mathrm{load}}=120\ \mathrm{A}} \]
The load power is:
\[ P_{\mathrm{load}}=399.616(120) \]
\[ \boxed{P_{\mathrm{load}}=47\,953.92\ \mathrm{W}} \]
Step 7: Calculate the energy budget.
The generator supplies:
\[ E_{\mathrm{generator}}=48.0(2.50) \]
\[ E_{\mathrm{generator}}=120\ \mathrm{kWh} \]
The energy lost in the line is:
\[ E_{\mathrm{loss}}=0.04608(2.50) \]
\[ \boxed{E_{\mathrm{loss}}=0.1152\ \mathrm{kWh}} \]
The energy delivered to the load is:
\[ E_{\mathrm{load}}=47.95392(2.50) \]
\[ \boxed{E_{\mathrm{load}}=119.8848\ \mathrm{kWh}} \]
The final check is:
\[ 120=0.1152+119.8848 \]
The complete energy budget balances.
Question 3
An ideal step-up transformer increases a generator’s 400 V output to 10.0 kV.
The transmission line has a total resistance of 8.0 Ω and carries a current of 4.0 A.
At the receiving end, an ideal step-down transformer has a primary-to-secondary turns ratio of 40:1.
A student argues:
“The second transformer reduces the voltage by a factor of 40, so the output power must be one-fortieth of the power entering it.”
Determine whether this statement is correct.
Calculate:
- The power entering the transmission line.
- The power lost in the line.
- The power reaching the second transformer.
- The load voltage and current.
- The energy dissipated in the line over 15.0 minutes.
Solution 3
The student’s statement is incorrect. The load receives 39.872 kW, not one-fortieth of the input power. The second ideal transformer reduces voltage while increasing current by the same factor.
Step 1: Calculate the power entering the transmission line.
The voltage and current at the sending end are:
\[ V_{\mathrm{send}}=10\,000\ \mathrm{V} \]
\[ I_{\mathrm{line}}=4.0\ \mathrm{A} \]
Therefore:
\[ P_{\mathrm{send}}=VI \]
\[ P_{\mathrm{send}}=10\,000(4.0) \]
\[ \boxed{P_{\mathrm{send}}=40\,000\ \mathrm{W}} \]
Because T1 is ideal, the generator also supplies 40,000 W.
Its current is:
\[ I_{\mathrm{generator}} = \frac{40\,000}{400} \]
\[ \boxed{I_{\mathrm{generator}}=100\ \mathrm{A}} \]
Step 2: Calculate the transmission-line loss.
\[ P_{\mathrm{loss}}=I^2R \]
\[ P_{\mathrm{loss}}=(4.0)^2(8.0) \]
\[ \boxed{P_{\mathrm{loss}}=128\ \mathrm{W}} \]
The line voltage drop is:
\[ \Delta V=4.0(8.0)=32\ \mathrm{V} \]
Therefore, the receiving voltage is:
\[ V_{\mathrm{receive}}=10\,000-32 \]
\[ \boxed{V_{\mathrm{receive}}=9968\ \mathrm{V}} \]
Step 3: Calculate the power reaching T2.
\[ P_{\mathrm{receive}}=40\,000-128 \]
\[ \boxed{P_{\mathrm{receive}}=39\,872\ \mathrm{W}} \]
Step 4: Calculate the load voltage.
The second transformer reduces the voltage by a factor of 40:
\[ V_{\mathrm{load}}=\frac{9968}{40} \]
\[ \boxed{V_{\mathrm{load}}=249.2\ \mathrm{V}} \]
Step 5: Calculate the load current and power.
For an ideal transformer, the current increases by a factor of 40:
\[ I_{\mathrm{load}}=40(4.0) \]
\[ \boxed{I_{\mathrm{load}}=160\ \mathrm{A}} \]
The load power is:
\[ P_{\mathrm{load}}=249.2(160) \]
\[ \boxed{P_{\mathrm{load}}=39\,872\ \mathrm{W}} \]
The voltage has decreased by a factor of 40, but the current has increased by a factor of 40.
The power therefore remains unchanged across the ideal transformer.
The only power lost in this system is the 128 W dissipated by the transmission line.
Step 6: Calculate the energy dissipated over 15.0 minutes.
Convert the time into seconds:
\[ t=15.0(60)=900\ \mathrm{s} \]
Then:
\[ E_{\mathrm{loss}}=P_{\mathrm{loss}}t \]
\[ E_{\mathrm{loss}}=128(900) \]
\[ \boxed{E_{\mathrm{loss}}=115\,200\ \mathrm{J}} \]
Or:
\[ \boxed{E_{\mathrm{loss}}=115.2\ \mathrm{kJ}} \]
Question 4
A factory requires a supply of 240 V and 80.0 A.
An ideal step-down transformer at the factory has a primary-to-secondary turns ratio of 50:1. It is connected to a transmission line with a total resistance of 5.0 Ω.
At the generating station, an ideal step-up transformer is connected to a 240 V source. Its turns ratio is unknown.
Determine:
- The current in the transmission line.
- The voltage required at the primary of the second transformer.
- The voltage that must be supplied by the first transformer.
- The turns ratio required for the first transformer.
- The current drawn from the generator.
- The energy converted into heat in the transmission line over 3.00 hours.
Solution 4
The transmission current must be 1.60 A, the first transformer must step up the voltage by approximately 50.03:1, and the line dissipates 38.4 Wh over three hours.
Step 1: Calculate the power required by the factory.
The factory requires:
\[ P_{\mathrm{load}}=VI \]
\[ P_{\mathrm{load}}=240(80.0) \]
\[ \boxed{P_{\mathrm{load}}=19\,200\ \mathrm{W}} \]
Step 2: Work backwards through the second transformer.
The second transformer has a primary-to-secondary turns ratio of 50:1.
Therefore, its primary voltage must be:
\[ V_{\mathrm{T2,p}}=50(240) \]
\[ \boxed{V_{\mathrm{T2,p}}=12\,000\ \mathrm{V}} \]
The primary current is the secondary current divided by 50:
\[ I_{\mathrm{T2,p}}=\frac{80.0}{50} \]
\[ \boxed{I_{\mathrm{T2,p}}=1.60\ \mathrm{A}} \]
This is also the transmission-line current.
Step 3: Calculate the voltage drop along the line.
\[ \Delta V_{\mathrm{line}}=IR \]
\[ \Delta V_{\mathrm{line}}=1.60(5.0) \]
\[ \boxed{\Delta V_{\mathrm{line}}=8.0\ \mathrm{V}} \]
The first transformer must therefore supply:
\[ V_{\mathrm{send}}=12\,000+8 \]
\[ \boxed{V_{\mathrm{send}}=12\,008\ \mathrm{V}} \]
Why is the sending voltage greater than 12,000 V?
Because 8.0 V is lost across the transmission-line resistance. The receiving end must still have 12,000 V for T2 to provide the required 240 V.
Step 4: Calculate the first transformer’s turns ratio.
The generator supplies 240 V to T1.
Using the voltage ratio:
\[ \frac{N_{s1}}{N_{p1}} = \frac{12\,008}{240} \]
\[ \boxed{\frac{N_{s1}}{N_{p1}}\approx50.03} \]
The required step-up ratio is approximately 50.03:1.
Step 5: Calculate the generator current.
First, calculate the power leaving T1.
The line carries 1.60 A at 12,008 V:
\[ P_{\mathrm{send}}=12\,008(1.60) \]
\[ P_{\mathrm{send}}=19\,212.8\ \mathrm{W} \]
Because T1 is ideal, the generator supplies the same power.
Therefore:
\[ I_{\mathrm{generator}} = \frac{19\,212.8}{240} \]
\[ \boxed{I_{\mathrm{generator}}\approx80.05\ \mathrm{A}} \]
The generator supplies slightly more power than the factory receives because it must also supply the energy that becomes heat in the line.
Step 6: Calculate the energy lost in the transmission line.
First calculate the power loss:
\[ P_{\mathrm{loss}}=I^2R \]
\[ P_{\mathrm{loss}}=(1.60)^2(5.0) \]
\[ P_{\mathrm{loss}}=12.8\ \mathrm{W} \]
Over 3.00 hours:
\[ E_{\mathrm{loss}}=12.8(3.00) \]
\[ \boxed{E_{\mathrm{loss}}=38.4\ \mathrm{Wh}} \]
The complete energy budget is:
\[ E_{\mathrm{generator}} = 19.2128(3) = 57.6384\ \mathrm{kWh} \]
\[ E_{\mathrm{load}} = 19.2(3) = 57.6\ \mathrm{kWh} \]
The difference is:
\[ 57.6384-57.6=0.0384\ \mathrm{kWh} \]
This is exactly 38.4 Wh, matching the calculated line loss.
Question 5
A 240 V RMS source supplies an ideal step-up transformer, followed by a transmission line and an ideal step-down transformer.
The transmission line has a total resistance of 4.0 Ω.
The second transformer has a fixed primary-to-secondary turns ratio of 10:1 and supplies a fixed 4.0 Ω resistive load.
Two operating cases are considered:
- Case A: The first transformer has a secondary-to-primary turns ratio of 10:1.
- Case B: The first transformer has a secondary-to-primary turns ratio of 20:1.
The source voltage, line resistance, second transformer, and load resistance remain unchanged. Assume the source can supply the resulting current.
A student argues:
“Doubling the first transformer’s turns ratio doubles the transmission voltage. Therefore, the transmission current must halve, and the line power loss must fall to one-quarter.”
Is this correct?
Calculate the transmission current and line power loss in both cases. Explain why the student’s prediction does or does not apply.
Solution 5
The student’s prediction is incorrect. The transmission current doubles, and the line power loss becomes four times larger.
The crucial distinction is that the transmitted power is not fixed in this question. The load resistance is fixed, so increasing the first transformer’s turns ratio also increases the voltage and current supplied to the load.
Step 1: Work out how the second transformer interacts with the fixed load.
The second transformer has a primary-to-secondary turns ratio of 10:1.
Therefore:
\[ I_{\mathrm{load}}=10I_{\mathrm{line}} \]
The load resistance is 4.0 Ω, so Ohm’s law gives:
\[ V_{\mathrm{load}}=4.0I_{\mathrm{load}} \]
Substitute the current relationship:
\[ V_{\mathrm{load}}=40I_{\mathrm{line}} \]
The second transformer’s primary voltage is ten times its secondary voltage:
\[ V_{\mathrm{T2,p}}=10V_{\mathrm{load}} \]
Therefore:
\[ V_{\mathrm{T2,p}}=400I_{\mathrm{line}} \]
This tells us something useful.
The fixed 4.0 Ω load, when viewed from the primary side of T2, behaves like a 400 Ω resistance.
You do not need to memorise a special transformer-resistance formula here. The result follows directly from the voltage ratio, current ratio, and Ohm’s law.
Step 2: Calculate the transmission current in Case A.
The first transformer has a turns ratio of 10:1.
Its secondary voltage is:
\[ V_{\mathrm{send,A}}=10(240) \]
\[ V_{\mathrm{send,A}}=2400\ \mathrm{V} \]
The line resistance is 4.0 Ω, and the effective resistance of the load as viewed from T2’s primary is 400 Ω.
Therefore, the total resistance in the transmission-side model is:
\[ R_{\mathrm{total}}=400+4.0 \]
\[ R_{\mathrm{total}}=404\ \Omega \]
Using Ohm’s law:
\[ I_{\mathrm{line,A}} = \frac{2400}{404} \]
\[ \boxed{I_{\mathrm{line,A}}=5.94\ \mathrm{A}} \]
Step 3: Calculate the line power loss in Case A.
\[ P_{\mathrm{loss,A}}=I^2R \]
\[ P_{\mathrm{loss,A}}=(5.9406)^2(4.0) \]
\[ \boxed{P_{\mathrm{loss,A}}\approx141\ \mathrm{W}} \]
The load current is:
\[ I_{\mathrm{load,A}}=10(5.9406) \]
\[ I_{\mathrm{load,A}}\approx59.4\ \mathrm{A} \]
Its voltage is:
\[ V_{\mathrm{load,A}}=4.0(59.406) \]
\[ V_{\mathrm{load,A}}\approx237.6\ \mathrm{V} \]
The load power is approximately:
\[ P_{\mathrm{load,A}}=237.6(59.4) \]
\[ \boxed{P_{\mathrm{load,A}}\approx14.1\ \mathrm{kW}} \]
Step 4: Calculate the transmission current in Case B.
The first transformer now has a turns ratio of 20:1.
Its secondary voltage is:
\[ V_{\mathrm{send,B}}=20(240) \]
\[ V_{\mathrm{send,B}}=4800\ \mathrm{V} \]
The total transmission-side resistance has not changed.
Therefore:
\[ I_{\mathrm{line,B}} = \frac{4800}{404} \]
\[ \boxed{I_{\mathrm{line,B}}=11.9\ \mathrm{A}} \]
The transmission current has doubled, not halved.
Step 5: Calculate the line power loss in Case B.
\[ P_{\mathrm{loss,B}}=I^2R \]
\[ P_{\mathrm{loss,B}}=(11.8812)^2(4.0) \]
\[ \boxed{P_{\mathrm{loss,B}}\approx565\ \mathrm{W}} \]
The load current is now:
\[ I_{\mathrm{load,B}}=10(11.8812) \]
\[ I_{\mathrm{load,B}}\approx118.8\ \mathrm{A} \]
The load voltage is:
\[ V_{\mathrm{load,B}}=4.0(118.812) \]
\[ V_{\mathrm{load,B}}\approx475.2\ \mathrm{V} \]
The load power is approximately:
\[ P_{\mathrm{load,B}}=475.2(118.8) \]
\[ \boxed{P_{\mathrm{load,B}}\approx56.5\ \mathrm{kW}} \]
Step 6: Explain why the student’s prediction failed.
The student used a correct relationship in the wrong situation.
For a fixed transmitted power:
\[ I=\frac{P}{V} \]
Doubling the voltage would halve the current, producing one-quarter of the original resistive loss.
But this question does not keep the transmitted power fixed.
It keeps the load resistance fixed.
When T1’s turns ratio doubles:
- The voltage supplied by T1 doubles.
- The voltage across the load approximately doubles.
- The load current doubles because its resistance is unchanged.
- The current entering T2 also doubles.
- Consequently, the transmission-line current doubles.
Since:
\[ P_{\mathrm{loss}}=I^2R \]
doubling the line current produces four times the original line loss.
The load power also increases by a factor of four because its voltage and current both double.
This is the important boundary of the high-voltage transmission argument: increasing voltage reduces resistive losses when the transmitted power is held constant. It does not guarantee lower losses when the load itself is allowed to draw more power.
13Where to take the method next
You can now analyse a complete transmission system without confusing the transformer current ratios with the energy dissipated in the line.
The next useful step is to replace the ideal-transformer assumptions with actual transformer efficiencies. The method stays the same: calculate the power leaving the first transformer, subtract the transmission-line loss, and then account for the efficiency of the second transformer before determining the load’s final power.