Power Factor
A heater and an electric motor can each use 1,000 W of real electrical power from the same AC supply, yet the motor may draw twice as much current. If both receive the same amount of energy each second, why does one need so much more current?
A heater and an electric motor can each use 1,000 W of real electrical power from the same AC supply, yet the motor may draw twice as much current. If both receive the same amount of energy each second, why does one need so much more current?
You might suspect that the motor is wasting the difference as heat. Some energy certainly becomes heat inside a real motor, but that isn’t the whole explanation. Part of its current is needed to build magnetic fields that later return energy to the electrical supply.
This is where power factor becomes useful.
Power factor goes beyond the required content of the NSW Physics 11-12 Syllabus (2025). It’s an extension of Year 12 Electromagnetism, not an additional formula you need to memorise for the HSC. We’ll start with the transformer model you already know, then examine something that model leaves out.
Due to technical limitations, this figure may display incorrectly or contain inaccuracies. Please check key details against your course materials.
01Start with the transformer you already know
A transformer transfers electrical energy between two coils through a changing magnetic field.
An alternating voltage is applied to the primary winding. The changing magnetic flux through the core induces an alternating voltage in the secondary winding.
For an ideal transformer:
\[ \frac{V_\mathrm{s}}{V_\mathrm{p}} = \frac{N_\mathrm{s}}{N_\mathrm{p}} \]
where:
- \(V_\mathrm{p}\) and \(V_\mathrm{s}\) are the primary and secondary RMS voltages, measured in volts (V).
- \(N_\mathrm{p}\) and \(N_\mathrm{s}\) are the numbers of turns in the primary and secondary windings.
The ideal model also assumes that no energy is lost:
\[ P_\mathrm{in}=P_\mathrm{out} \]
Here, \(P_\mathrm{in}\) and \(P_\mathrm{out}\) are the average rates of real energy transfer into and out of the transformer, measured in watts (W).
That’s an energy conservation statement. It doesn’t mean every real transformer transfers electrical energy perfectly.
Why real transformers deliver less power
Three important limitations are incomplete flux linkage, eddy currents, and resistive heating.
| Limitation | What physically happens | Consequence |
|---|---|---|
| Incomplete flux linkage | Some magnetic flux produced by one winding does not link the other winding. | Leakage flux reduces effective magnetic coupling and can cause voltage drops under load. |
| Eddy currents | Changing magnetic flux induces circulating currents within the conducting core. | The currents produce resistive heating in the core. |
| Resistive heating | Current flows through windings with non-zero electrical resistance. | Electrical energy becomes heat at a rate described by \(I^2R\). |
In the heating equation, \(I\) is the RMS current in amperes (A), and \(R\) is the electrical resistance in ohms (\(\Omega\)).
Notice an important difference.
Eddy currents and winding resistance directly produce heat. Incomplete flux linkage is not automatically an equivalent amount of energy converted into heat. Leakage flux changes how effectively the windings interact and can reduce the secondary terminal voltage.
Transformer designers use laminated, electrically insulated core sheets to restrict large eddy-current loops. Low-resistance windings reduce heating, while suitable core and winding geometries improve magnetic coupling.
For a closer look at incomplete flux linkage, see Coupling Coefficients: Magnetic Flux Linkage in Real Transformers.
A real transformer can also have magnetic hysteresis losses. Its core must repeatedly reverse its magnetisation, and this process dissipates energy.
The transformer’s efficiency is therefore:
\[ \eta=\frac{P_\mathrm{out}}{P_\mathrm{in}} \]
where \(\eta\) is its efficiency, expressed as a fraction. Multiply by 100% to express it as a percentage.
But there’s another complication. Even a transformer with very small energy losses needs current to establish its changing magnetic field.
That current introduces a different idea: reactive power.
02Why AC current doesn’t always mean energy is being used
Imagine two devices connected separately to an AC source.
The first is a simple resistance heater. The second contains a coil of wire, like the winding of an electric motor.
Both experience alternating voltage and current, but their behaviour differs.
In a resistor, voltage and current move together
When the voltage across an ideal resistor increases, the current increases proportionally.
When the voltage reverses, the current reverses too.
The voltage and current reach their maximum values at the same time. We say they are in phase.
At any instant, the electrical power transferred into the resistor is:
\[ p(t)=v(t)i(t) \]
Here, \(p(t)\) is instantaneous power in watts, while \(v(t)\) and \(i(t)\) are the voltage and current at time \(t\).
For a resistor, voltage and current always have the same sign. Their product is therefore never negative.
Electrical energy continually becomes heat, even though the current reverses direction.
In an inductor, current responds later
Now consider a coil.
When current begins changing, the coil’s magnetic field changes too. Faraday’s law tells us that a changing magnetic flux induces an electromotive force (emf).
By Lenz’s law, the induced emf opposes the change that produces it.
This makes an ideal inductor resist changes in current.
If an alternating voltage is applied to an ideal inductor, its current reaches its maximum one-quarter of a cycle after the voltage reaches its maximum.
The current lags the voltage by \(90^\circ\).
Here’s the important prediction.
If the voltage has reversed but the current is still flowing in its previous direction, what happens to the instantaneous power?
The product \(v(t)i(t)\) becomes negative.
That means energy is flowing back from the inductor towards the supply.
The inductor stores energy in its magnetic field while that field grows. As the field decreases, the stored energy can return to the circuit.
A useful analogy is borrowing and returning a library book. The book travels in both directions, even though you haven’t permanently acquired it.
For the coil, the thing being exchanged is energy stored in a magnetic field. The analogy breaks down because this exchange happens continuously during the AC cycle, rather than as two separate transactions.
For an ideal inductor, the energy received over a complete cycle equals the energy returned. Its average real power consumption is zero.
A real motor isn’t an ideal inductor. It also converts electrical energy into mechanical work and heat.
Its current is influenced by both energy conversion and temporary magnetic energy storage.
That’s why we need more than one description of AC power.
03Real, reactive, and apparent power
For the rest of this guide, assume a steady, single-phase AC circuit in which voltage and current are both sinusoidal and have the same frequency.
We’ll also assume a passive load that consumes non-negative average real power.
These assumptions matter because the simple phase-angle equations below don’t apply unchanged to distorted current waveforms.
RMS voltage and current
AC voltage and current change continuously, so their peak values aren’t usually the most convenient numbers for power calculations.
Instead, we use root mean square (RMS) values.
RMS describes the equivalent constant voltage or current that would produce the same average resistive heating.
For a sinusoidal waveform:
\[ \begin{aligned} V&=\frac{V_0}{\sqrt{2}}\\ I&=\frac{I_0}{\sqrt{2}} \end{aligned} \]
where:
- \(V\) is RMS voltage in volts.
- \(I\) is RMS current in amperes.
- \(V_0\) is peak voltage.
- \(I_0\) is peak current.
From this point onwards, \(V\) and \(I\) mean RMS values unless stated otherwise.
1. Real power: energy transferred on average
Real power, \(P\), measures the average net rate of electrical energy transfer.
It includes energy converted into mechanical work, heat, light, or other forms.
Its unit is the watt (W).
For sinusoidal AC:
\[ P=VI\cos\phi \]
Here, \(\phi\), pronounced phi, is the phase angle between the voltage and current.
We’ll take \(\phi\) as positive when current lags voltage and negative when it leads.
If voltage and current are in phase, \(\phi=0^\circ\), so:
\[ P=VI \]
When they’re out of phase, multiplying voltage by current without accounting for the angle gives the wrong real power.
2. Reactive power: energy exchanged with fields
Reactive power, \(Q\), describes the alternating exchange of energy associated with magnetic or electric fields.
Its unit is the volt-ampere reactive (var).
For sinusoidal AC:
\[ Q=VI\sin\phi \]
The sign provides useful information:
- Positive \(Q\): inductive behaviour, with current lagging voltage.
- Negative \(Q\): capacitive behaviour, with current leading voltage.
- Zero \(Q\): no net reactive power exchange at the supply terminals.
An ideal capacitor stores energy in an electric field rather than a magnetic field. Its current leads its voltage by \(90^\circ\).
An ideal inductor or capacitor has zero average real power, but can have non-zero reactive power.
Reactive power isn’t simply wasted energy. However, the extra current associated with it can cause real heating losses in conductors.
3. Apparent power: the voltage-current demand
Apparent power, \(S\), is the product of RMS voltage and RMS current:
\[ S=VI \]
Its unit is the volt-ampere (VA).
Apparent power tells us how much voltage-current capacity an electrical supply must provide.
This is why transformer ratings are commonly expressed in VA or kVA rather than only watts.
A 2 kVA transformer, for example, has a rated apparent-power capacity of 2,000 VA.
It cannot necessarily supply 2,000 W of real power to every load. The amount depends on the load’s power factor.
Comparing the three quantities
| Quantity | Symbol | Unit | Physical meaning |
|---|---|---|---|
| Real power | \(P\) | W | Average net rate of electrical energy transfer |
| Reactive power | \(Q\) | var | Signed measure of energy exchanged with electric and magnetic fields |
| Apparent power | \(S\) | VA | RMS voltage multiplied by RMS current |
For sinusoidal voltage and current, the quantities form a right-angled power triangle:
\[ S^2=P^2+Q^2 \]
The horizontal side represents real power, the vertical side reactive power, and the hypotenuse apparent power.
For an inductive load, positive \(Q\) points upwards. For a capacitive load, negative \(Q\) points downwards.
Don’t interpret the triangle as three separate amounts of energy being consumed. It is a geometric relationship between quantities describing the same AC circuit.
04What power factor actually measures
Power factor is the ratio of real power to apparent power:
\[ \mathrm{PF}=\frac{P}{S} \]
For the sinusoidal circuits considered here:
\[ \mathrm{PF}=\cos\phi \]
Power factor has no unit.
For a passive load, it ranges from zero to one.
- At \(\mathrm{PF}=1\), voltage and current are in phase. All apparent power corresponds to real power.
- At \(\mathrm{PF}=0.8\), real power is 80% of the numerical value of apparent power when expressed in matching W and VA units.
- At \(\mathrm{PF}=0\), the load exchanges reactive energy without consuming average real power.
A power factor of 0.8 is not the same thing as 80% energy efficiency.
That’s the misconception worth remembering.
Power factor compares real power with apparent power. Efficiency compares useful output power with real input power.
A motor could be highly efficient at converting real electrical power into mechanical power while still having a relatively low power factor.
Likewise, a resistor can have a power factor of one while converting all its electrical input into heat.
Whether that heat is useful depends on what the device is supposed to do.
Worked example: Which load draws more current?
A 230 V RMS AC supply operates two devices separately.
A resistance heater consumes 920 W with a power factor of 1.00. An electric motor also consumes 920 W of real electrical power but has a power factor of 0.80 lagging.
Calculate the RMS current and apparent power of each device. Also calculate the motor’s reactive power.
Step 1
Since the heater has a power factor of one:
\[ \begin{aligned} S&=\frac{P}{\mathrm{PF}}\\ &=\frac{920\ \mathrm{W}}{1.00}\\ &=920\ \mathrm{VA} \end{aligned} \]
Its apparent and real power are numerically equal.
Step 2
Using \(S=VI\):
\[ \begin{aligned} I&=\frac{S}{V}\\ &=\frac{920\ \mathrm{VA}}{230\ \mathrm{V}}\\ &=4.00\ \mathrm{A} \end{aligned} \]
Step 3
The motor has the same real power but a smaller power factor.
\[ \begin{aligned} S&=\frac{920\ \mathrm{W}}{0.80}\\ &=1150\ \mathrm{VA} \end{aligned} \]
Its current is:
\[ \begin{aligned} I&=\frac{1150\ \mathrm{VA}}{230\ \mathrm{V}}\\ &=5.00\ \mathrm{A} \end{aligned} \]
Step 4
Using the power triangle:
\[ Q=\sqrt{S^2-P^2} \]
Substitute the values:
\[ \begin{aligned} Q&=\sqrt{1150^2-920^2}\\ &=690\ \mathrm{var} \end{aligned} \]
The motor’s reactive power is positive because its current lags the voltage.
Step 5
| Quantity | Heater | Motor |
|---|---|---|
| Real power | 920 W | 920 W |
| Apparent power | 920 VA | 1150 VA |
| Reactive power | 0 var | +690 var |
| RMS current | 4.00 A | 5.00 A |
| Power factor | 1.00 | 0.80 lagging |
Both devices consume the same average real electrical power.
But the motor draws 25% more current because of its reactive behaviour.
That doesn’t mean the motor wastes 20% of its input energy. Its actual efficiency would require information about its useful mechanical output and real electrical input.
05Why low power factor matters to a power supply
Suppose a motor must receive a fixed amount of real power at a fixed RMS voltage.
Rearranging the power factor equation gives:
\[ I=\frac{P}{V\,\mathrm{PF}} \]
As power factor decreases, the current required increases.
That matters because wires and transformer windings have resistance.
Their heating losses are:
\[ P_\mathrm{heat}=I^2R \]
If the current doubles while the resistance stays constant, the heating rate becomes four times as large.
That’s a real energy loss caused indirectly by the extra current associated with reactive power.
A lower power factor also uses more of a transformer’s available VA rating.
A transformer supplying 1,200 W at a power factor of 0.60 must handle:
\[ S=\frac{1200}{0.60}=2000\ \mathrm{VA} \]
That is 2.0 kVA of apparent power, even though the load consumes only 1.2 kW of real power.
Power factor correction
Many motors and transformers have inductive behaviour. Their current lags the voltage, giving positive reactive power.
An ideal capacitor produces negative reactive power.
If a capacitor is connected in parallel with an inductive load, the reactive contributions can partially cancel.
The load itself hasn’t stopped needing a magnetic field. Instead, the capacitor can exchange energy locally with the inductive load, reducing the reactive current that must travel through the upstream supply.
For ideal compensation, the total real power stays unchanged:
\[ P_\mathrm{total}=P_\mathrm{load} \]
The net reactive power becomes:
\[ Q_\mathrm{total}=Q_\mathrm{load}+Q_\mathrm{cap} \]
Here, \(Q_\mathrm{cap}\) is negative.
For this simple sinusoidal model, the new apparent power is:
\[ S_\mathrm{new} = \sqrt{P_\mathrm{total}^2+Q_\mathrm{total}^2} \]
Worked example: Can a capacitor prevent transformer overload?
An ideal single-phase transformer has a rated output of 1.8 kVA at 230 V RMS.
It supplies a motor consuming 1.2 kW at a power factor of 0.60 lagging.
An ideal capacitor is connected in parallel with the motor and supplies 800 var of capacitive reactive power.
Determine whether the transformer is within its rating before and after correction. Calculate the new supply current and power factor.
Assume sinusoidal operation, constant motor real power, constant terminal voltage, and no capacitor losses.
Step 1
\[ \begin{aligned} S&=\frac{1200\ \mathrm{W}}{0.60}\\ &=2000\ \mathrm{VA} \end{aligned} \]
The original reactive power is:
\[ \begin{aligned} Q&=\sqrt{2000^2-1200^2}\\ &=1600\ \mathrm{var} \end{aligned} \]
The motor draws 2.0 kVA, exceeding the transformer’s 1.8 kVA rating.
Its original current is:
\[ \begin{aligned} I&=\frac{2000\ \mathrm{VA}}{230\ \mathrm{V}}\\ &=8.70\ \mathrm{A} \end{aligned} \]
Step 2
The capacitor supplies negative reactive power:
\[ \begin{aligned} Q_\mathrm{total} &=1600-800\\ &=800\ \mathrm{var} \end{aligned} \]
The motor still consumes 1,200 W of real power.
Step 3
\[ \begin{aligned} S_\mathrm{new} &=\sqrt{1200^2+800^2}\\ &\approx1442\ \mathrm{VA} \end{aligned} \]
The new apparent power is about 1.44 kVA.
This is below the transformer’s 1.8 kVA rating.
Step 4
\[ \begin{aligned} I_\mathrm{new} &=\frac{1442\ \mathrm{VA}}{230\ \mathrm{V}}\\ &=6.27\ \mathrm{A} \end{aligned} \]
The corrected power factor is:
\[ \begin{aligned} \mathrm{PF}_\mathrm{new} &=\frac{1200}{1442}\\ &\approx0.832 \end{aligned} \]
The power factor has improved from 0.60 to approximately 0.83 lagging.
The upstream current has fallen from 8.70 A to 6.27 A.
However, the motor winding still carries its original current. The capacitor hasn’t removed the motor’s own magnetic requirements or internal resistive losses.
It has reduced the reactive current flowing through the transformer and its upstream conductors.
Three decisions worth separating
Before choosing a power factor correction method, distinguish three questions.
| Question | Relevant quantity |
|---|---|
| How much real electrical energy is transferred each second? | Real power, \(P\) |
| How much electrical capacity must the supply provide? | Apparent power, \(S\) |
| How effectively does a device convert real input power into useful output? | Efficiency, \(\eta\) |
Improving power factor can reduce current, release transformer capacity, and reduce upstream \(I^2R\) losses.
It doesn’t automatically improve a motor’s internal conversion efficiency.
Also, the location of the correcting capacitor matters. A capacitor connected near the source can improve power factor measured at the source without reducing current in a cable farther downstream.
We’ll test that idea in the final question.
One final limit: real electronic equipment can draw non-sinusoidal current. In that case, the general definition \(\mathrm{PF}=P/(VI)\) still applies, but power factor cannot always be calculated from one phase angle. The simple power triangle and \(\cos\phi\) relationship used here are for sinusoidal voltage and current.
The distinction between instantaneous and average power is developed further in OpenStax’s University Physics treatment of AC power.
06Questions and solutions
Question 1
A single-phase fan motor operates from a 230 V RMS AC supply.
It draws an RMS current of 4.0 A at a power factor of 0.75 lagging.
Calculate:
a) Its apparent power.
b) Its real power.
c) Its reactive power.
d) Whether the reactive power is inductive or capacitive.
Solution 1
The motor draws 920 VA of apparent power, consumes 690 W of real power, and has approximately 609 var of positive, inductive reactive power.
Part a: Apparent power
Use:
\[ S=VI \]
Substitute:
\[ \begin{aligned} S&=(230\ \mathrm{V})(4.0\ \mathrm{A})\\ &=920\ \mathrm{VA} \end{aligned} \]
Part b: Real power
\[ P=S\,\mathrm{PF} \]
Therefore:
\[ \begin{aligned} P&=(920\ \mathrm{VA})(0.75)\\ &=690\ \mathrm{W} \end{aligned} \]
The motor receives 690 J of net electrical energy per second on average.
Part c: Reactive power
Using the power triangle:
\[ Q=\sqrt{S^2-P^2} \]
\[ \begin{aligned} Q&=\sqrt{920^2-690^2}\\ &\approx609\ \mathrm{var} \end{aligned} \]
Part d: Type of reactive power
The reactive power is inductive and positive because current lags voltage.
The tempting mistake is to treat all 920 VA as real power.
But apparent power describes voltage-current demand, not the net rate of energy conversion. The phase difference reduces real power below the apparent-power value.
Question 2
An AC device operates at 50 Hz.
An oscilloscope shows that both voltage and current are sinusoidal. The current reaches each positive maximum 2.5 ms after the voltage reaches its positive maximum.
The RMS voltage is 200 V, and the RMS current is 5.0 A.
A separate wattmeter displays 900 W.
Assume the waveforms are steady, measurements are exact, and the device is absorbing positive average real power.
a) Determine the phase angle and power factor from the waveforms.
b) Calculate the real and reactive power predicted by the voltage and current measurements.
c) Can the 900 W wattmeter reading be correct under the stated assumptions?
d) Immediately after the voltage changes from positive to negative, is electrical energy entering or leaving the device? Explain how this can happen even though the device consumes real power overall.
Solution 2
The current lags by \(45^\circ\), giving a power factor of approximately 0.707 lagging. The predicted real power is 707 W, not 900 W, so the measurements are inconsistent. Immediately after the specified voltage reversal, energy briefly flows from the device towards the supply.
Part a: Phase angle and power factor
First calculate the period from the frequency.
\[ T=\frac{1}{f} \]
where \(T\) is the period in seconds and \(f\) is the frequency in hertz.
\[ \begin{aligned} T&=\frac{1}{50\ \mathrm{Hz}}\\ &=0.020\ \mathrm{s}\\ &=20\ \mathrm{ms} \end{aligned} \]
The current peaks 2.5 ms later.
This represents:
\[ \frac{2.5}{20}=\frac18 \]
of a cycle.
Therefore:
\[ \begin{aligned} \phi&=360^\circ\times\frac18\\ &=45^\circ \end{aligned} \]
The current lags, so the angle is positive under our convention.
\[ \begin{aligned} \mathrm{PF}&=\cos45^\circ\\ &\approx0.707 \end{aligned} \]
Part b: Real and reactive power
First calculate apparent power:
\[ \begin{aligned} S&=VI\\ &=(200\ \mathrm{V})(5.0\ \mathrm{A})\\ &=1000\ \mathrm{VA} \end{aligned} \]
The real power is:
\[ \begin{aligned} P&=S\cos45^\circ\\ &=(1000)(0.7071)\\ &\approx707\ \mathrm{W} \end{aligned} \]
The reactive power is:
\[ \begin{aligned} Q&=S\sin45^\circ\\ &=(1000)(0.7071)\\ &\approx+707\ \mathrm{var} \end{aligned} \]
Part c: Assess the wattmeter reading
The 900 W reading is inconsistent with the other measurements.
At 1000 VA, a real power of 900 W would require:
\[ \begin{aligned} \mathrm{PF}&=\frac{900}{1000}\\ &=0.900 \end{aligned} \]
But the measured time delay gives a power factor of approximately 0.707.
Both values cannot describe the same steady sinusoidal voltage and current.
At least one measurement or assumption must be wrong. Under the question’s exact waveform assumptions, 900 W cannot be the correct average real power.
Part d: Direction of instantaneous energy transfer
Immediately after voltage changes from positive to negative, the lagging current is still positive.
Therefore:
\[ p(t)=v(t)i(t)<0 \]
The instantaneous power is negative, meaning energy is temporarily flowing back towards the supply.
The device can still consume positive real power overall because the positive energy-transfer periods outweigh the negative ones.
A common misconception is that a device consuming real power must receive energy at every instant.
For AC circuits with energy storage, the direction of instantaneous energy transfer can reverse while the average remains positive.
Question 3
A real transformer is tested under a steady sinusoidal load.
Measurements at its primary terminals are:
- RMS voltage: 220 V
- RMS current: 5.0 A
- Real input power: 880 W
- Lagging input current
Measurements at its secondary terminals are:
- RMS voltage: 100 V
- RMS current: 10.0 A
- Power factor: 0.80 lagging
The two windings operate at the same AC frequency.
a) Calculate the secondary real power and transformer efficiency.
b) Calculate the primary power factor.
c) Determine the primary and secondary reactive powers.
d) A student argues: “The input and output power factors are equal, so the transformer must be ideal.” Evaluate this claim.
e) Explain which information the measurements provide about real losses and why they cannot identify exactly how much energy is lost through each individual mechanism.
Solution 3
The transformer delivers 800 W, loses 80 W of real power, and has an efficiency of approximately 90.9%. Both sides have a power factor of 0.80 lagging, but that does not make the transformer ideal. Their reactive powers are different.
Part a: Output power and efficiency
At the secondary:
\[ P_\mathrm{out}=VI\,\mathrm{PF} \]
\[ \begin{aligned} P_\mathrm{out} &=(100)(10.0)(0.80)\\ &=800\ \mathrm{W} \end{aligned} \]
The efficiency is:
\[ \begin{aligned} \eta&=\frac{P_\mathrm{out}}{P_\mathrm{in}}\\ &=\frac{800\ \mathrm{W}}{880\ \mathrm{W}}\\ &\approx0.909 \end{aligned} \]
Therefore:
\[ \eta\approx90.9\% \]
The real power loss is:
\[ \begin{aligned} P_\mathrm{loss} &=P_\mathrm{in}-P_\mathrm{out}\\ &=880-800\\ &=80\ \mathrm{W} \end{aligned} \]
Part b: Primary power factor
The primary apparent power is:
\[ \begin{aligned} S_\mathrm{in} &=(220\ \mathrm{V})(5.0\ \mathrm{A})\\ &=1100\ \mathrm{VA} \end{aligned} \]
Hence:
\[ \begin{aligned} \mathrm{PF}_\mathrm{in} &=\frac{880}{1100}\\ &=0.80 \end{aligned} \]
It is lagging, as stated in the measurements.
Part c: Reactive power on each side
At the primary:
\[ \begin{aligned} Q_\mathrm{in} &=\sqrt{1100^2-880^2}\\ &=660\ \mathrm{var} \end{aligned} \]
At the secondary:
\[ \begin{aligned} S_\mathrm{out} &=(100)(10.0)\\ &=1000\ \mathrm{VA} \end{aligned} \]
Therefore:
\[ \begin{aligned} Q_\mathrm{out} &=\sqrt{1000^2-800^2}\\ &=600\ \mathrm{var} \end{aligned} \]
Both reactive powers are positive because both currents lag their respective voltages.
The difference is:
\[ Q_\mathrm{in}-Q_\mathrm{out}=60\ \mathrm{var} \]
This represents the transformer’s net internal reactive demand in the stated model. It is not an additional 60 W of heating.
Part d: Does equal power factor imply an ideal transformer?
No.
Power factor is the ratio of real to apparent power on each side.
Both ratios happen to equal 0.80:
\[ \frac{880}{1100}=\frac{800}{1000}=0.80 \]
But the actual real powers differ.
An ideal transformer would have equal real input and output power.
This transformer loses 80 W, so it is not ideal.
Part e: What can the measurements establish?
The measurements establish the total real power loss: 80 W.
Possible causes include winding resistance, eddy currents, and magnetic hysteresis.
Incomplete flux linkage can also affect the voltage delivered under load.
However, the measurements don’t isolate the contribution of each mechanism. Separating winding heating from core losses would require additional measurements or tests.
The tempting interpretation is to treat every difference between input and output electrical quantities as energy dissipated.
But reactive power describes reversible field-energy exchange, while the 80 W difference in real power represents net energy converted into other forms.
Question 4
A regulated AC supply maintains 200 V RMS at a load bus. Two units are connected in parallel.
Unit A: An inductive motor consuming 600 W of real power and +800 var of reactive power.
Unit B: A 200 W resistance heater combined with an ideal capacitor supplying −800 var of reactive power.
The units are supplied through a cable with total resistance \(R=0.20\ \Omega\).
A switch disconnects Unit B completely while Unit A remains operating at the same voltage and load.
Assume sinusoidal operation, constant electrical properties, and no other losses.
a) Calculate the load-bus power factor and feeder current with both units connected.
b) Calculate the load-bus power factor and feeder current after Unit B is disconnected.
c) Calculate the cable heating losses before and after disconnection.
d) Explain how disconnecting a unit that consumes real power can increase the current and heating in the supply cable, even while reducing the total real power drawn from the source.
Solution 4
Disconnecting Unit B reduces total real load power from 800 W to 600 W, but increases feeder current from 4.0 A to 5.0 A. Cable heating rises from 3.2 W to 5.0 W because Unit B had been cancelling the motor’s reactive power.
Part a: Both units connected
Real powers add:
\[ \begin{aligned} P_\mathrm{total}&=600+200\\ &=800\ \mathrm{W} \end{aligned} \]
Signed reactive powers also add:
\[ \begin{aligned} Q_\mathrm{total}&=800-800\\ &=0\ \mathrm{var} \end{aligned} \]
The apparent power is:
\[ \begin{aligned} S_\mathrm{total} &=\sqrt{800^2+0^2}\\ &=800\ \mathrm{VA} \end{aligned} \]
Therefore:
\[ \mathrm{PF}=\frac{800}{800}=1.00 \]
The feeder current is:
\[ \begin{aligned} I&=\frac{800\ \mathrm{VA}}{200\ \mathrm{V}}\\ &=4.0\ \mathrm{A} \end{aligned} \]
Part b: Unit B disconnected
Only the motor remains.
Its real and reactive powers are:
\[ \begin{aligned} P&=600\ \mathrm{W}\\ Q&=800\ \mathrm{var} \end{aligned} \]
The apparent power becomes:
\[ \begin{aligned} S&=\sqrt{600^2+800^2}\\ &=1000\ \mathrm{VA} \end{aligned} \]
The power factor is:
\[ \begin{aligned} \mathrm{PF}&=\frac{600}{1000}\\ &=0.60 \end{aligned} \]
It is lagging.
The feeder current is:
\[ \begin{aligned} I&=\frac{1000\ \mathrm{VA}}{200\ \mathrm{V}}\\ &=5.0\ \mathrm{A} \end{aligned} \]
Part c: Cable heating
Before disconnection:
\[ \begin{aligned} P_\mathrm{heat} &=I^2R\\ &=(4.0)^2(0.20)\\ &=3.2\ \mathrm{W} \end{aligned} \]
After disconnection:
\[ \begin{aligned} P_\mathrm{heat} &=(5.0)^2(0.20)\\ &=5.0\ \mathrm{W} \end{aligned} \]
The increase is:
\[ \begin{aligned} \frac{5.0-3.2}{3.2}\times100\% =56.25\% \end{aligned} \]
Part d: Explain the unexpected increase
Unit B was doing two things simultaneously.
Its resistance heater consumed real power, while its capacitor supplied negative reactive power.
That negative reactive power cancelled the motor’s positive reactive power.
While both units operated, the feeder didn’t need to carry a net reactive current component.
When Unit B was removed, the heater’s real power disappeared, but so did the capacitor’s reactive contribution.
The supply now had to provide the motor’s entire reactive demand.
Consequently, apparent power increased even as real load power decreased.
Including feeder losses, the source’s real power falls from:
\[ 800+3.2=803.2\ \mathrm{W} \]
to:
\[ 600+5.0=605.0\ \mathrm{W} \]
So the source genuinely delivers less real power, while the cable carries more current and becomes hotter.
The incorrect shortcut is to add or subtract the RMS currents of different AC branches as ordinary numbers.
Those currents can have different phases. Their combined effect depends on both the real and reactive components.
Question 5
A workshop motor is supplied through a long two-conductor cable from a transformer.
The transformer has a 1.23 kVA output rating.
At the motor terminals, a regulated system maintains a sinusoidal voltage of 200 V RMS.
The motor consumes:
- Real electrical power: 1,200 W
- Reactive power: +1,600 var, inductive
The cable’s total resistance, including both conductors, is \(0.40\ \Omega\).
An ideal capacitor is available to cancel the motor’s reactive power.
Two correction plans are proposed.
Plan A – source-side correction: The capacitor is connected across the transformer secondary terminals, before the long cable.
Plan B – motor-side correction: The capacitor is connected across the motor terminals, after the long cable.
In each plan, choose the ideal capacitor to provide −1,600 var at its own connection point.
Assume that:
- The transformer is lossless but must operate within its 1.23 kVA output rating.
- The upstream voltage can be adjusted to keep the motor-terminal voltage at 200 V RMS in either plan.
- The motor’s real and reactive power demands remain constant.
- The cable is purely resistive, with no inductive or capacitive effects.
- The capacitor has no real power loss, and the waveforms remain sinusoidal.
- No other loads or losses exist.
A technician measures a power factor of 1.00 at the transformer secondary terminals under either plan.
The workshop manager concludes:
“Both plans produce unity power factor at the transformer. So the cable current, cable heating, and transformer loading must be identical.”
a) Calculate the current through the cable and its heating loss under each plan.
b) Determine the real power supplied by the transformer in each plan.
c) Determine whether the transformer operates within its 1.23 kVA rating under each plan.
d) Explain why both plans can produce unity power factor at the transformer even though their cable losses differ.
e) Does either plan reduce current inside the motor’s own windings? Explain.
Solution 5
Both plans achieve unity power factor at the transformer, but only Plan B keeps the transformer within its 1.23 kVA rating.
Plan A produces 40 W of cable heating and requires 1,240 VA from the transformer. Plan B produces only 14.4 W of cable heating and requires approximately 1,214 VA.
The critical distinction is where the reactive current flows.
Part a: Cable current and heating
First calculate the motor’s apparent power:
\[ \begin{aligned} S_\mathrm{motor} &=\sqrt{1200^2+1600^2}\\ &=2000\ \mathrm{VA} \end{aligned} \]
The motor current is:
\[ \begin{aligned} I_\mathrm{motor} &=\frac{2000\ \mathrm{VA}}{200\ \mathrm{V}}\\ &=10.0\ \mathrm{A} \end{aligned} \]
Now compare the plans.
Plan A: Capacitor at the transformer
The capacitor is upstream of the cable.
The cable still supplies the motor’s full current of 10.0 A.
Therefore:
\[ \begin{aligned} P_\mathrm{heat,A} &=I^2R\\ &=(10.0)^2(0.40)\\ &=40.0\ \mathrm{W} \end{aligned} \]
The reactive current is compensated at the transformer terminals, but it still travels through the long cable to the motor.
Plan B: Capacitor at the motor
The capacitor is connected across the motor terminals.
At that location:
\[ \begin{aligned} Q_\mathrm{net} &=1600-1600\\ &=0\ \mathrm{var} \end{aligned} \]
The total real power at the motor-side connection remains 1,200 W.
Its net apparent power is:
\[ \begin{aligned} S_\mathrm{net} &=\sqrt{1200^2+0^2}\\ &=1200\ \mathrm{VA} \end{aligned} \]
The cable now carries:
\[ \begin{aligned} I_\mathrm{cable,B} &=\frac{1200\ \mathrm{VA}}{200\ \mathrm{V}}\\ &=6.0\ \mathrm{A} \end{aligned} \]
The cable heating is:
\[ \begin{aligned} P_\mathrm{heat,B} &=(6.0)^2(0.40)\\ &=14.4\ \mathrm{W} \end{aligned} \]
The cable’s current has fallen from 10.0 A to 6.0 A.
Its real power loss has fallen from 40.0 W to 14.4 W.
Part b: Real transformer output
In each plan, the transformer must supply the motor’s real power plus cable heating.
The ideal capacitor consumes zero average real power.
For Plan A:
\[ \begin{aligned} P_\mathrm{source,A} &=1200+40.0\\ &=1240\ \mathrm{W} \end{aligned} \]
For Plan B:
\[ \begin{aligned} P_\mathrm{source,B} &=1200+14.4\\ &=1214.4\ \mathrm{W} \end{aligned} \]
Plan B requires 25.6 W less real power from the transformer.
That difference is exactly the reduction in cable heating.
Part c: Transformer apparent-power limit
Both plans are stated to produce a power factor of 1.00 at the transformer secondary.
Therefore, at the transformer’s output:
\[ S=\frac{P}{1.00} \]
For Plan A:
\[ S_\mathrm{source,A}=1240\ \mathrm{VA} \]
The transformer rating is:
\[ 1.23\ \mathrm{kVA}=1230\ \mathrm{VA} \]
Therefore:
\[ 1240\ \mathrm{VA}>1230\ \mathrm{VA} \]
Plan A exceeds the rating by 10 VA.
For Plan B:
\[ S_\mathrm{source,B}=1214.4\ \mathrm{VA} \]
Since:
\[ 1214.4\ \mathrm{VA}<1230\ \mathrm{VA} \]
Plan B operates within the rating.
This result is especially interesting because both plans give the same measured power factor at the transformer.
Part d: Why unity power factor doesn’t guarantee equal cable heating
In Plan A, reactive energy is exchanged between the motor and the capacitor through the long cable.
The capacitor cancels the motor’s reactive demand as seen by the transformer, but the cable still carries the motor’s 10.0 A current.
The feeder’s resistance dissipates 40 W.
In Plan B, the capacitor is located beside the motor.
Much of the reactive energy exchange now occurs between the capacitor and motor without travelling through the long cable.
The cable only needs to carry the net current associated with 1,200 W at the 200 V motor terminals.
That current is 6.0 A.
Because the cable is purely resistive, it contributes real heating loss but no reactive power. The chosen capacitor cancels the motor’s reactive demand at the transformer in either arrangement.
Both plans can therefore have unity source power factor despite different real losses.
One subtle point is that the voltage maintained at 200 V is the motor-terminal voltage, not necessarily the transformer secondary voltage. The transformer output voltage adjusts to account for cable voltage drop.
So it would be incorrect to assume the transformer’s output current is obtained by dividing its real power by 200 V.
Part e: Motor winding current
Neither plan changes the motor’s own current.
The motor still receives the same terminal voltage and demands:
\[ \begin{aligned} P_\mathrm{motor}&=1200\ \mathrm{W}\\ Q_\mathrm{motor}&=1600\ \mathrm{var} \end{aligned} \]
Therefore:
\[ I_\mathrm{motor}=10.0\ \mathrm{A} \]
That current is unchanged.
The motor’s own winding resistance still causes internal heating, even though Plan B reduces heating in the long supply cable.
The manager’s mistake was treating power factor as a property of the entire installation independent of measurement position.
It isn’t.
Power factor describes the relationship between real and apparent power at a particular electrical connection.
Two installations can have the same power factor at the transformer while carrying different currents in their internal branches.
The general lesson is that correcting power factor at one location does not necessarily minimise losses everywhere.
To take this further, the next useful concept is AC Impedance: Understanding Reactance and Phase Differences. Impedance explains how resistance, inductance, capacitance, and AC frequency determine the current and phase angle in the first place.
That gives you the missing step between knowing a circuit’s power factor and predicting how changing its components will affect it.