Transformer Equivalent Circuits: Modelling Real Transformer Losses
Learn how real transformer equivalent circuits represent leakage flux, magnetising current, winding resistance, and core losses. Explore the approximate circuit model through worked examples and challenging HSC extension questions.
Connect a transformer to a load and the secondary voltage may be lower than the turns ratio predicts. The input power can also be noticeably greater than the useful power delivered to the load. An ideal transformer predicts neither problem: it transfers power without losing any. Real transformers behave differently because some magnetic flux misses a winding, the iron core requires a magnetising current, and electrical resistance and induced currents convert useful energy into heat. An equivalent circuit gives us a way to represent these effects separately and predict how they change a transformer’s performance. This is an extension beyond the required Year 12 NSW HSC Physics syllabus. The 2025 Electromagnetism content provides the foundation, but transformer equivalent circuits are not an additional HSC assessment requirement.
01Start with the ideal transformer model
A transformer has two windings wrapped around a shared magnetic core.
- The primary winding connects to the AC supply.
- The secondary winding connects to the load.
- An alternating current in the primary produces a changing magnetic flux in the core.
- That changing flux induces an electromotive force (emf) in the secondary winding through electromagnetic induction.
The key idea is that both windings experience the same changing magnetic flux in the ideal model.
Due to technical limitations, this figure may display incorrectly or contain inaccuracies. Please check key details against your course materials.
Faraday’s law tells us that the induced emf depends on the rate of change of magnetic flux and the number of turns in a winding.
For an ideal transformer:
\[ \frac{V_p}{V_s}=\frac{N_p}{N_s} \]
Here:
- \(V_p\) is the primary voltage.
- \(V_s\) is the secondary voltage.
- \(N_p\) is the number of primary turns.
- \(N_s\) is the number of secondary turns.
The current ratio works in the opposite direction:
\[ \frac{I_p}{I_s}=\frac{N_s}{N_p} \]
The ideal transformer therefore trades voltage for current.
A step-up transformer increases voltage while decreasing current. A step-down transformer decreases voltage while increasing current.
Think of a gearbox in a car. It can trade rotational speed for torque, but it cannot create extra power. A transformer makes a similar trade between voltage and current. The analogy stops there: a transformer has no moving parts, and its behaviour comes from electromagnetic induction.
The ideal transformer also assumes perfect power transfer:
\[ P_{\text{in}}=P_{\text{out}} \]
For sinusoidal AC, real power is calculated using:
\[ P=VI\cos\phi \]
where \(\phi\) is the phase angle between voltage and current.
In an ideal transformer, the input real power equals the output real power. No energy is dissipated inside the transformer.
But what happens when you connect a real transformer to a load?
Its secondary voltage can fall below the ideal prediction, and its input power must exceed its output power.
To understand why, we need to examine four effects that the ideal model ignores.
02Four effects that make transformers non-ideal
1. Incomplete flux linkage: some magnetic flux misses the secondary
The ideal model assumes that all magnetic flux produced by the primary links both windings.
Real transformers cannot achieve perfect magnetic coupling.
Some flux travels through the core and links both windings. This is called mutual flux. Other flux travels around only one winding without linking the other.
This second type is called leakage flux.
Why does this matter?
Imagine that the primary produces a changing magnetic field. Only the part of that field linking the secondary contributes to the mutually induced secondary emf.
The leakage flux does not contribute to the mutual induction between the windings.
Consequently, the real transformer has imperfect coupling. Its secondary voltage under load can differ from the ideal prediction.
In an equivalent circuit, leakage flux is represented by a leakage inductance in series with each winding.
For an AC supply, the leakage inductance produces leakage reactance:
\[ X_\ell=2\pi fL_\ell \]
where:
- \(X_\ell\) is leakage reactance in ohms (\(\Omega\)).
- \(f\) is the AC supply frequency in hertz (Hz).
- \(L_\ell\) is leakage inductance in henries (H).
Leakage reactance opposes changes in current and contributes to the voltage drop between the transformer supply and its load.
There is an important distinction here: leakage reactance is not the same as resistive power loss.
An ideal inductor stores energy in its magnetic field and returns that energy to the circuit. It does not continuously dissipate real power.
Leakage reactance therefore mainly affects voltage regulation and the amount of power that can be delivered to a particular load. It is not, by itself, an explanation for all the missing real power.
For a closer look at how magnetic coupling is quantified, read Coupling Coefficients: Magnetic Flux Linkage in Real Transformers.
2. Winding resistance: electrical energy becomes heat
A transformer winding is made from conducting wire, usually copper.
Copper has a small but non-zero electrical resistance.
When current flows through a winding, some electrical energy is converted into thermal energy.
This is resistive heating, often called copper loss.
The power dissipated in a resistor is:
\[ P=I^2R \]
For a transformer with primary and secondary winding resistances:
\[ P_{\text{copper}} =I_p^2R_p+I_s^2R_s \]
Here:
- \(R_p\) is primary winding resistance.
- \(R_s\) is secondary winding resistance.
- \(I_p\) is primary current.
- \(I_s\) is secondary current.
Notice the squared current.
If the current doubles, the resistive heating increases by a factor of four, assuming the resistance remains constant.
This is why winding resistance becomes particularly important when a transformer supplies a heavy load.
3. Eddy currents: the core also experiences induced currents
The changing magnetic flux does not only induce an emf in the secondary winding.
It can also induce circulating currents within the conducting iron core itself.
These are called eddy currents.
Think about what happens when a changing magnetic field passes through a solid piece of metal. The induced electric fields can drive currents around closed paths inside the material.
Those currents dissipate energy through resistive heating.
This means that even when the secondary winding is disconnected, the transformer can still lose energy in its core.
Manufacturers reduce eddy-current losses by constructing transformer cores from thin sheets of electrical steel, called laminations.
Each sheet is electrically insulated from its neighbours.
This interrupts large circulating current paths and increases their electrical resistance, reducing the eddy currents.
The core can also lose energy through magnetic hysteresis as its magnetic domains repeatedly change orientation during each AC cycle.
An equivalent circuit commonly groups hysteresis and eddy-current losses together into a single core-loss resistance.
We will call this resistance \(R_c\).
It is a mathematical representation of the core’s real power consumption, not an actual resistor installed inside the transformer.
4. Magnetising current: the transformer draws current even without a load
Here is another prediction worth making.
Suppose the secondary winding is completely disconnected. No current can flow through the secondary.
Does that mean the primary draws zero current?
Not in a real transformer.
The primary still needs current to establish and repeatedly reverse the magnetic flux in the core.
This is called the magnetising current, \(I_m\).
It is required even when the transformer supplies no useful output power.
In a simplified model, magnetising current is represented by a magnetising inductance, \(L_m\), or its corresponding reactance:
\[ X_m=2\pi fL_m \]
The magnetising reactance is connected in parallel with the core-loss resistance.
The magnetising current is approximately:
\[ I_m=\frac{V_p}{X_m} \]
For an ideal inductor, this current lags the voltage by \(90^\circ\). It transfers energy into the magnetic field during part of the cycle and returns it during another part.
It therefore does not consume average real power in the idealised model.
The core-loss current, on the other hand, is different.
It flows through \(R_c\), is approximately in phase with the applied voltage, and represents real power dissipated in the core.
The no-load current is the combination of these two components.
This distinction is useful:
- Magnetising current establishes the alternating magnetic field.
- Core-loss current supplies energy lost through processes such as eddy currents and hysteresis.
- Load current supplies energy to the secondary load.
When a load is connected, the secondary current produces a magnetic effect that opposes the original flux change, consistent with Lenz’s law.
The primary then draws additional current to balance this opposing effect.
The core flux remains approximately constant when the primary voltage and frequency are held constant and the transformer operates normally.
The extra primary current is therefore mainly a load-related current, not a dramatic increase in the magnetising current.
This is an important distinction when interpreting a real transformer.
03Constructing the equivalent circuit
We can now represent the four non-ideal effects using familiar circuit components.
Instead of treating the transformer as a mysterious device with unexplained losses, we model it as an ideal transformer surrounded by resistances and reactances.
The full equivalent circuit
A real transformer can be represented using the following components:
| Circuit element | Physical meaning | Main effect |
|---|---|---|
| \(R_p\) | Primary winding resistance | Primary copper heating |
| \(R_s\) | Secondary winding resistance | Secondary copper heating |
| \(X_{\ell p}\) | Primary leakage reactance | Primary voltage drop |
| \(X_{\ell s}\) | Secondary leakage reactance | Secondary voltage drop |
| \(X_m\) | Magnetising reactance | Magnetising current |
| \(R_c\) | Core-loss resistance | Eddy-current and hysteresis losses |
The complete model has:
- Primary resistance and leakage reactance in series with the primary.
- A parallel magnetising branch containing \(X_m\) and \(R_c\).
- An ideal transformer with the appropriate turns ratio.
- Secondary resistance and leakage reactance in series with the load.
Each component has a specific job.
The model separates effects that would otherwise be difficult to distinguish from measurements at the transformer terminals.
Referring everything to the primary side
There is another useful simplification.
We can mathematically transfer the secondary-side circuit quantities to the primary side, removing the need to work with two different voltage and current levels.
This process is called referring quantities to the primary.
Define the turns ratio:
\[ a=\frac{N_p}{N_s} \]
The secondary resistance, when referred to the primary, becomes:
\[ R_s'=a^2R_s \]
Similarly, the secondary leakage reactance becomes:
\[ X_{\ell s}'=a^2X_{\ell s} \]
The secondary load impedance becomes:
\[ Z_L'=a^2Z_L \]
The voltage and current transformations are:
\[ V_s'=aV_s \]
\[ I_s'=\frac{I_s}{a} \]
The square in the impedance relationship is important.
It comes from transforming both voltage and current, rather than just one of them.
The total equivalent series resistance and reactance referred to the primary are therefore:
\[ R_{\text{eq}}=R_p+a^2R_s \]
\[ X_{\text{eq}}=X_{\ell p}+a^2X_{\ell s} \]
We can now represent the transformer using:
- One equivalent series resistance, \(R_{\text{eq}}\).
- One equivalent series reactance, \(X_{\text{eq}}\).
- One parallel magnetising branch, \(R_c\) and \(X_m\).
- A load referred to the primary side.
The approximate model is particularly useful because it lets us analyse a real transformer using ordinary AC circuit ideas.
There is one qualification.
In the full equivalent circuit, the magnetising branch is connected across the primary’s induced emf, after the primary series impedance. In the approximate circuit, it is moved directly across the supply terminals.
This is reasonable when the excitation current is small and the primary series voltage drop is relatively small.
It is not an exact rearrangement.
What the approximate circuit can and cannot tell us
The model is designed to describe normal transformer operation.
It assumes approximately sinusoidal steady-state operation, a reasonably linear magnetic core, and parameters that remain reasonably constant over the operating range.
It is useful for predicting:
- Voltage drops under load.
- Winding power losses.
- Core power losses.
- Magnetising current.
- Efficiency.
- Voltage regulation.
It does not fully describe magnetic saturation, inrush current, strongly distorted waveforms, or the detailed distribution of magnetic fields.
In particular, \(X_m\) is not truly constant if the core approaches saturation. The magnetising inductance can change substantially.
The equivalent circuit is a useful approximation, not a complete description of every physical process inside a transformer.
04Worked examples
Worked example: Calculating winding losses and efficiency
A transformer has 1000 primary turns and 100 secondary turns. It is connected to a 240 V AC supply.
The primary winding resistance is \(0.40\,\Omega\), and the secondary winding resistance is \(0.050\,\Omega\).
When supplying a resistive load, the secondary current is 4.0 A and the measured secondary terminal voltage is 23.8 V. The core dissipates 2.0 W.
Calculate:
- The ideal secondary voltage.
- The primary current associated with the load.
- The total winding power loss.
- The transformer’s efficiency.
Assume the magnetising current is small enough to neglect when estimating primary winding copper loss.
Step 1
The turns ratio is:
\[ \frac{N_p}{N_s}=\frac{1000}{100}=10 \]
Using the ideal transformer voltage relationship:
\[ V_s=\frac{240}{10} \]
\[ \boxed{V_s=24.0\text{ V}} \]
The ideal model predicts 24.0 V. The actual terminal voltage is 23.8 V, showing a small voltage reduction under load.
Step 2
The current ratio is the inverse of the voltage ratio.
\[ I_p=\frac{I_s}{10} \]
\[ I_p=\frac{4.0}{10} \]
\[ \boxed{I_p=0.40\text{ A}} \]
This is the primary current associated with transferring power to the load. It excludes the small excitation-current contribution.
Step 3
For the primary:
\[ P_p=I_p^2R_p \]
\[ P_p=(0.40)^2(0.40) \]
\[ P_p=0.064\text{ W} \]
For the secondary:
\[ P_s=I_s^2R_s \]
\[ P_s=(4.0)^2(0.050) \]
\[ P_s=0.80\text{ W} \]
Therefore:
\[ P_{\text{copper}}=0.064+0.80 \]
\[ \boxed{P_{\text{copper}}=0.864\text{ W}} \]
Most of the winding loss occurs in the secondary because its current is much larger.
Step 4
The load is resistive, so its power factor is one.
\[ P_{\text{out}}=V_sI_s \]
\[ P_{\text{out}}=23.8\times4.0 \]
\[ \boxed{P_{\text{out}}=95.2\text{ W}} \]
Step 5
The total power loss is the sum of winding and core losses:
\[ P_{\text{loss}}=0.864+2.0 \]
\[ P_{\text{loss}}=2.864\text{ W} \]
Therefore:
\[ P_{\text{in}}=95.2+2.864 \]
\[ P_{\text{in}}=98.064\text{ W} \]
Efficiency is:
\[ \eta=\frac{P_{\text{out}}}{P_{\text{in}}}\times100\% \]
\[ \eta=\frac{95.2}{98.064}\times100\% \]
\[ \boxed{\eta=97.1\%} \]
The transformer delivers approximately 97.1% of its input power to the load. The remaining energy is dissipated mainly as heat in the core and windings.
Worked example: Using the complete approximate model
A real transformer has the following characteristics:
- Primary voltage: 240 V.
- Turns ratio: \(5:1\).
- Frequency: 50 Hz.
- Primary winding resistance: \(0.30\,\Omega\).
- Secondary winding resistance: \(0.020\,\Omega\).
- Primary leakage reactance: \(0.25\,\Omega\).
- Secondary leakage reactance: \(0.010\,\Omega\).
- Magnetising reactance: \(1200\,\Omega\).
- Core-loss resistance: \(12\,000\,\Omega\).
The transformer supplies a load drawing 8.0 A at a power factor of 0.8 lagging. Its measured secondary terminal voltage is approximately 47.7 V.
Calculate:
- The equivalent resistance and reactance referred to the primary.
- The magnetising and core-loss currents.
- The total copper and core losses.
- The efficiency.
Step 1
The turns ratio is:
\[ a=5 \]
Refer the secondary resistance to the primary:
\[ R_s'=a^2R_s \]
\[ R_s'=5^2(0.020) \]
\[ R_s'=0.50\,\Omega \]
Therefore:
\[ R_{\text{eq}}=R_p+R_s' \]
\[ R_{\text{eq}}=0.30+0.50 \]
\[ \boxed{R_{\text{eq}}=0.80\,\Omega} \]
Now refer the secondary leakage reactance to the primary:
\[ X_{\ell s}'=a^2X_{\ell s} \]
\[ X_{\ell s}'=25(0.010) \]
\[ X_{\ell s}'=0.25\,\Omega \]
Therefore:
\[ X_{\text{eq}}=X_{\ell p}+X_{\ell s}' \]
\[ X_{\text{eq}}=0.25+0.25 \]
\[ \boxed{X_{\text{eq}}=0.50\,\Omega} \]
The primary-referred series impedance now contains both winding resistances and both leakage reactances.
Step 2
The magnetising current is:
\[ I_m=\frac{V_p}{X_m} \]
\[ I_m=\frac{240}{1200} \]
\[ \boxed{I_m=0.20\text{ A}} \]
This current establishes the alternating magnetic field.
Step 3
The core-loss current is:
\[ I_c=\frac{V_p}{R_c} \]
\[ I_c=\frac{240}{12000} \]
\[ \boxed{I_c=0.020\text{ A}} \]
The magnetising and core-loss currents are approximately perpendicular in this simplified AC model.
The no-load current magnitude is therefore:
\[ I_0=\sqrt{I_m^2+I_c^2} \]
\[ I_0=\sqrt{0.20^2+0.020^2} \]
\[ \boxed{I_0\approx0.201\text{ A}} \]
Step 4
The secondary current referred to the primary is:
\[ I_p'=\frac{I_s}{a} \]
\[ I_p'=\frac{8.0}{5}=1.6\text{ A} \]
The primary copper loss is approximately:
\[ P_{\text{primary}}=(1.6)^2(0.30) \]
\[ P_{\text{primary}}=0.768\text{ W} \]
The secondary copper loss is:
\[ P_{\text{secondary}}=(8.0)^2(0.020) \]
\[ P_{\text{secondary}}=1.28\text{ W} \]
Therefore:
\[ P_{\text{copper}}=0.768+1.28 \]
\[ \boxed{P_{\text{copper}}=2.048\text{ W}} \]
Step 5
The core-loss resistance represents real power consumption in the core.
\[ P_{\text{core}}=\frac{V_p^2}{R_c} \]
\[ P_{\text{core}}=\frac{240^2}{12000} \]
\[ \boxed{P_{\text{core}}=4.8\text{ W}} \]
Notice that the magnetising current does not appear in this real-power loss calculation.
Step 6
The load power factor is 0.8, so:
\[ P_{\text{out}}=V_sI_s\cos\phi \]
\[ P_{\text{out}}=47.7(8.0)(0.8) \]
\[ \boxed{P_{\text{out}}=305.28\text{ W}} \]
Total losses are:
\[ P_{\text{loss}}=2.048+4.8 \]
\[ P_{\text{loss}}=6.848\text{ W} \]
Therefore:
\[ P_{\text{in}}=305.28+6.848 \]
\[ P_{\text{in}}=312.128\text{ W} \]
Finally:
\[ \eta=\frac{305.28}{312.128}\times100\% \]
\[ \boxed{\eta\approx97.8\%} \]
The transformer is approximately 97.8% efficient.
The calculation also shows why it is important to distinguish the different circuit elements. The magnetising branch draws current, the core-loss resistance dissipates real power, and the series resistance and reactance affect the voltage delivered to the load.
05Common misconceptions
Before attempting the questions, make sure you can distinguish these statements.
| Tempting assumption | What actually happens |
|---|---|
| An unloaded transformer draws no primary current. | It still draws excitation current to establish the magnetic field and supply core losses. |
| Leakage reactance directly consumes real power. | Ideal leakage reactance stores and returns energy; winding resistance and core losses dissipate real power. |
| All primary current supplies the secondary load. | Some current supplies the magnetising and core-loss branches. |
| The turns ratio guarantees the loaded secondary terminal voltage. | The turns ratio predicts the ideal induced-emf relationship. Internal voltage drops affect terminal voltage. |
| Eddy currents occur only when a load is connected. | They are induced by changing core flux, even with the secondary open. |
| Doubling current doubles copper loss. | Copper loss increases by a factor of four if resistance stays constant. |
The most useful habit is to ask what physical process each circuit element represents before deciding whether it causes a voltage drop, a current draw, or a real power loss.
06Questions and solutions
Question 1
A real step-down transformer has 800 primary turns and 80 secondary turns. It operates from a 240 V AC supply.
The secondary supplies a resistive load with a current of 5.0 A and a measured terminal voltage of 23.6 V.
The primary winding resistance is \(0.50\,\Omega\), the secondary winding resistance is \(0.040\,\Omega\), and the core loss is 1.5 W.
Assume the primary current used in the copper-loss calculation is approximately the load current referred to the primary.
Calculate:
a) The ideal secondary voltage.
b) The primary load-current component.
c) The total copper loss.
d) The transformer’s efficiency.
Solution 1
The ideal secondary voltage is 24.0 V, the primary load-current component is 0.50 A, and the estimated transformer efficiency is 97.8%.
Part a: Ideal secondary voltage
The turns ratio is:
\[ a=\frac{800}{80}=10 \]
Therefore:
\[ V_s=\frac{240}{10} \]
\[ \boxed{V_s=24.0\text{ V}} \]
The actual terminal voltage is slightly lower because the real transformer has internal impedance.
Part b: Primary load-current component
Using the inverse current ratio:
\[ I_p=\frac{I_s}{a} \]
\[ I_p=\frac{5.0}{10} \]
\[ \boxed{I_p=0.50\text{ A}} \]
Part c: Total copper loss
Primary winding:
\[ P_p=I_p^2R_p \]
\[ P_p=(0.50)^2(0.50) \]
\[ P_p=0.125\text{ W} \]
Secondary winding:
\[ P_s=I_s^2R_s \]
\[ P_s=(5.0)^2(0.040) \]
\[ P_s=1.0\text{ W} \]
Total:
\[ P_{\text{copper}}=0.125+1.0 \]
\[ \boxed{P_{\text{copper}}=1.125\text{ W}} \]
Part d: Efficiency
The output power is:
\[ P_{\text{out}}=23.6(5.0) \]
\[ P_{\text{out}}=118\text{ W} \]
Total losses:
\[ P_{\text{loss}}=1.125+1.5 \]
\[ P_{\text{loss}}=2.625\text{ W} \]
Input power:
\[ P_{\text{in}}=118+2.625 \]
\[ P_{\text{in}}=120.625\text{ W} \]
Efficiency:
\[ \eta=\frac{118}{120.625}\times100\% \]
\[ \boxed{\eta=97.8\%} \]
The transformer loses 2.625 W through winding and core heating. The leakage effects contribute to the terminal voltage reduction, but should not be counted as an additional resistive power loss.
Question 2
A transformer is connected to a 240 V AC supply.
Its primary-referred equivalent circuit has:
- Core-loss resistance \(R_c=12\,000\,\Omega\).
- Magnetising reactance \(X_m=1200\,\Omega\).
- Primary winding resistance \(R_p=0.20\,\Omega\).
- Secondary winding resistance \(R_s=0.030\,\Omega\).
The turns ratio is \(4:1\), and the secondary supplies 8.0 A at unity power factor.
Assume the shunt branch voltage is approximately 240 V and neglect the small voltage drops when calculating its currents.
Calculate:
a) The core-loss current.
b) The magnetising current.
c) The no-load current magnitude.
d) The approximate total primary current when the load is connected.
e) The total winding copper loss.
Explain why the total primary current is not simply the arithmetic sum of the reflected load current and the magnitude of the no-load current.
Solution 2
The core-loss current is 0.020 A, the magnetising current is 0.200 A, and the no-load current is approximately 0.201 A. The loaded primary current is approximately 2.03 A, and the total copper loss is approximately 2.74 W.
Part a: Core-loss current
\[ I_c=\frac{V_p}{R_c} \]
\[ I_c=\frac{240}{12000} \]
\[ \boxed{I_c=0.020\text{ A}} \]
This current supplies the real power lost in the core.
Part b: Magnetising current
\[ I_m=\frac{V_p}{X_m} \]
\[ I_m=\frac{240}{1200} \]
\[ \boxed{I_m=0.200\text{ A}} \]
This current establishes the alternating magnetic field.
Part c: No-load current
The two current components are approximately \(90^\circ\) apart.
We therefore use Pythagoras rather than adding their magnitudes.
\[ I_0=\sqrt{I_c^2+I_m^2} \]
\[ I_0=\sqrt{0.020^2+0.200^2} \]
\[ \boxed{I_0=0.201\text{ A}} \]
Part d: Total primary current
First, refer the secondary load current to the primary.
\[ I_p'=\frac{8.0}{4} \]
\[ I_p'=2.0\text{ A} \]
Because the load has unity power factor, this current is approximately in phase with the supply voltage.
The core-loss current is also in phase with the voltage, while the magnetising current lags by approximately \(90^\circ\).
The total in-phase component is:
\[ I_{\text{active}}=2.0+0.020 \]
\[ I_{\text{active}}=2.020\text{ A} \]
The reactive component is:
\[ I_{\text{reactive}}=0.200\text{ A} \]
Therefore:
\[ I_p=\sqrt{2.020^2+0.200^2} \]
\[ \boxed{I_p\approx2.03\text{ A}} \]
Adding \(2.0+0.201\) directly would be incorrect because the magnetising current does not point in the same phase direction as the load current.
Part e: Total copper loss
Primary winding loss:
\[ P_p=I_p^2R_p \]
\[ P_p=(2.03)^2(0.20) \]
\[ P_p\approx0.824\text{ W} \]
Secondary winding loss:
\[ P_s=I_s^2R_s \]
\[ P_s=(8.0)^2(0.030) \]
\[ P_s=1.92\text{ W} \]
Total:
\[ P_{\text{copper}}=0.824+1.92 \]
\[ \boxed{P_{\text{copper}}\approx2.74\text{ W}} \]
The important result is that the primary current contains several components. Only the reflected load-current component transfers power to the load, while the excitation branch accounts for the current needed to maintain the magnetic field and supply core losses.
Question 3
A transformer undergoes an open-circuit test with its secondary winding disconnected.
The primary is supplied with 240 V AC. Measurements show:
- No-load primary current: 0.12 A.
- Real input power: 18 W.
Assume primary winding losses are negligible during this test and the magnetising and core-loss current components are approximately \(90^\circ\) apart.
a) Calculate the core-loss current.
b) Calculate the magnetising current.
c) Estimate the values of \(R_c\) and \(X_m\).
d) When a load is subsequently connected, the secondary terminal voltage falls from 24.0 V to 22.5 V. Explain which parts of the equivalent circuit account for this voltage reduction.
e) Explain why the magnetising reactance is not responsible for the measured 18 W of real power loss in the simplified model.
Solution 3
The core-loss current is 0.075 A, the magnetising current is approximately 0.094 A, and the estimated equivalent parameters are \(R_c=3200\,\Omega\) and \(X_m\approx2560\,\Omega\).
Part a: Core-loss current
The real input power is attributed to core losses under the stated assumptions.
Using:
\[ P_{\text{core}}=V_pI_c \]
Rearrange:
\[ I_c=\frac{P_{\text{core}}}{V_p} \]
\[ I_c=\frac{18}{240} \]
\[ \boxed{I_c=0.075\text{ A}} \]
Part b: Magnetising current
The total no-load current is the vector combination of the core-loss and magnetising currents.
\[ I_0^2=I_c^2+I_m^2 \]
Rearranging:
\[ I_m=\sqrt{I_0^2-I_c^2} \]
Substitute:
\[ I_m=\sqrt{0.12^2-0.075^2} \]
\[ I_m=\sqrt{0.008775} \]
\[ \boxed{I_m\approx0.094\text{ A}} \]
Part c: Equivalent resistance and reactance
The core-loss resistance is:
\[ R_c=\frac{V_p^2}{P_{\text{core}}} \]
\[ R_c=\frac{240^2}{18} \]
\[ \boxed{R_c=3200\,\Omega} \]
The magnetising reactance is:
\[ X_m=\frac{V_p}{I_m} \]
\[ X_m=\frac{240}{0.0937} \]
\[ \boxed{X_m\approx2560\,\Omega} \]
These values describe the approximate no-load behaviour of the transformer at the test frequency and operating flux.
Part d: Loaded voltage reduction
The secondary voltage falls because the real transformer has internal series impedance.
Primary and secondary winding resistances produce resistive voltage drops. Primary and secondary leakage reactances produce additional AC voltage drops.
Together, these effects cause the loaded secondary terminal voltage to fall below its open-circuit value.
The shunt magnetising branch and core-loss resistance mainly describe the transformer’s no-load behaviour. They are not the primary explanation for the load-dependent voltage reduction.
Part e: Why magnetising reactance does not consume the 18 W
In the simplified model, the magnetising branch behaves as an ideal inductor.
Its current lags the voltage by \(90^\circ\), so its average real power is zero.
Energy is stored in the magnetic field and returned to the circuit.
The 18 W is represented by the core-loss resistance \(R_c\), which accounts for real energy dissipated through core losses.
This is why the two parallel branches must be treated separately.
Question 4
A transformer has an open-circuit secondary voltage of 48.0 V.
Its equivalent series parameters, referred to the secondary, are:
\[ R_{\text{eq}}=0.080\,\Omega \]
\[ X_{\text{eq}}=0.100\,\Omega \]
The core loss is 6.0 W and can be assumed constant over the operating conditions below.
The transformer supplies a lagging load with a power factor of 0.8.
Compare its performance when the secondary current is:
- 2.0 A.
- 6.0 A.
For both conditions, calculate:
a) The approximate secondary voltage drop.
b) The loaded secondary voltage.
c) The copper loss.
d) The output power.
e) The efficiency.
Use the small-voltage-drop approximation:
\[ \Delta V\approx I_s (R_{\text{eq}}\cos\phi+ X_{\text{eq}}\sin\phi) \]
Assume \(\cos\phi=0.8\) and \(\sin\phi=0.6\).
Solution 4
The 6.0 A condition produces a larger voltage drop and greater absolute power loss, but the transformer is more efficient at the higher load: approximately 96.2% compared with 92.4%.
Part a: Voltage drop
First calculate the combined voltage-drop contribution:
\[ R_{\text{eq}}\cos\phi =0.080(0.8)=0.064 \]
\[ X_{\text{eq}}\sin\phi =0.100(0.6)=0.060 \]
Therefore:
\[ \Delta V\approx I_s(0.064+0.060) \]
\[ \Delta V\approx0.124I_s \]
At 2.0 A:
\[ \Delta V=0.124(2.0) \]
\[ \boxed{\Delta V=0.248\text{ V}} \]
At 6.0 A:
\[ \Delta V=0.124(6.0) \]
\[ \boxed{\Delta V=0.744\text{ V}} \]
Part b: Loaded secondary voltage
At 2.0 A:
\[ V_s=48.0-0.248 \]
\[ \boxed{V_s=47.752\text{ V}} \]
At 6.0 A:
\[ V_s=48.0-0.744 \]
\[ \boxed{V_s=47.256\text{ V}} \]
The higher current produces a greater internal voltage drop.
Part c: Copper losses
The total winding loss is:
\[ P_{\text{copper}}=I_s^2R_{\text{eq}} \]
At 2.0 A:
\[ P_{\text{copper}}=(2.0)^2(0.080) \]
\[ \boxed{P_{\text{copper}}=0.32\text{ W}} \]
At 6.0 A:
\[ P_{\text{copper}}=(6.0)^2(0.080) \]
\[ \boxed{P_{\text{copper}}=2.88\text{ W}} \]
The copper loss increases by a factor of nine because the current triples.
Part d: Output power
The load has a power factor of 0.8.
At 2.0 A:
\[ P_{\text{out}}=47.752(2.0)(0.8) \]
\[ \boxed{P_{\text{out}}\approx76.40\text{ W}} \]
At 6.0 A:
\[ P_{\text{out}}=47.256(6.0)(0.8) \]
\[ \boxed{P_{\text{out}}\approx226.83\text{ W}} \]
Part e: Efficiency
Remember that core loss remains approximately constant at the same primary voltage and frequency.
At 2.0 A, total losses are:
\[ P_{\text{loss}}=6.0+0.32 \]
\[ P_{\text{loss}}=6.32\text{ W} \]
Input power:
\[ P_{\text{in}}=76.40+6.32 \]
\[ P_{\text{in}}\approx82.72\text{ W} \]
Efficiency:
\[ \eta=\frac{76.40}{82.72}\times100\% \]
\[ \boxed{\eta\approx92.4\%} \]
At 6.0 A, total losses are:
\[ P_{\text{loss}}=6.0+2.88 \]
\[ P_{\text{loss}}=8.88\text{ W} \]
Input power:
\[ P_{\text{in}}=226.83+8.88 \]
\[ P_{\text{in}}\approx235.71\text{ W} \]
Efficiency:
\[ \eta=\frac{226.83}{235.71}\times100\% \]
\[ \boxed{\eta\approx96.2\%} \]
The interesting result is that the transformer becomes more efficient at the higher load, even though its absolute power losses increase.
Why?
The core loss remains approximately fixed, while the useful output power increases substantially. The fixed core loss therefore becomes a smaller fraction of the total input power.
This is one reason transformer efficiency depends on loading, rather than being a single fixed number.
Question 5
A transformer is designed to operate at 240 V and 50 Hz.
Its primary-to-secondary turns ratio is \(10:1\), and its core operates at a peak magnetic flux density equal to 80% of the material’s saturation flux density at its rated conditions.
Consider two changes to its operating conditions.
Situation A: The secondary is connected to a load while the primary supply remains at 240 V and 50 Hz.
Situation B: The transformer is supplied with 240 V at 25 Hz instead of 50 Hz, with the same load connected.
A student makes three claims:
- Connecting a load must increase the core flux because the secondary now draws energy.
- Reducing the frequency while maintaining the primary voltage will halve the secondary voltage because the supply frequency has halved.
- The transformer remains adequately described by the same linear equivalent circuit in both situations because its winding resistances and turns ratio have not changed.
Evaluate all three claims.
Your answer must explain:
- What happens to the core flux when the load is connected at rated frequency.
- Why the primary current increases even though the core flux remains approximately constant.
- What happens to the peak flux density when the supply frequency is halved.
- How saturation affects magnetising current and the validity of the equivalent circuit.
- Why the turns ratio alone cannot guarantee the loaded secondary terminal voltage.
- What happens to the interpretation of eddy-current and winding losses when the operating conditions change.
Assume the core cross-sectional area and winding turns remain unchanged. Before saturation, the peak flux density is proportional to \(V_p/f\). The transformer is designed close enough to its normal operating limit that a predicted flux density of 1.6 times the saturation value will cause substantial saturation.
Solution 5
Claim 1 is incorrect, claim 2 is incorrect, and claim 3 is only valid while the transformer remains within the approximate linear operating range.
The key is to distinguish the effect of changing the load from the effect of changing the supply frequency. These are physically different situations.
Situation A: Connecting the load at rated frequency
The core flux remains approximately constant.
The reason is that the secondary current produces a magnetic effect that opposes the original magnetic flux change.
According to Lenz’s law, the induced secondary current acts in a direction that opposes the change responsible for producing it.
The primary must therefore draw additional current to balance this opposing magnetic effect.
The extra primary current is mainly the load-current component referred to the primary.
It is not simply a large increase in magnetising current.
The primary current can be understood as a combination of:
- The magnetising current required to establish the core flux.
- The core-loss current required to supply energy dissipated in the core.
- The load-current component required to transfer energy to the secondary.
The primary voltage and frequency remain unchanged, so the core flux remains approximately at its original operating value.
This is why connecting a load does not automatically cause the core flux to increase in proportion to the load current.
The secondary terminal voltage can still fall because the primary and secondary winding resistances and leakage reactances produce internal voltage drops.
Situation B: Halving the frequency while keeping the voltage constant
This changes the magnetic conditions much more dramatically.
For a fixed transformer, the approximate relationship is:
\[ B_{\max}\propto\frac{V_p}{f} \]
Here:
- \(B_{\max}\) is peak magnetic flux density.
- \(V_p\) is the primary voltage.
- \(f\) is the supply frequency.
The original operating flux density is:
\[ B_{\max}=0.80B_{\text{sat}} \]
where \(B_{\text{sat}}\) is the saturation flux density.
The frequency is now halved while the voltage remains unchanged.
Therefore, the predicted flux density doubles:
\[ B_{\max,\text{new}}=2(0.80B_{\text{sat}}) \]
\[ \boxed{B_{\max,\text{new}}=1.60B_{\text{sat}}} \]
The core is now driven well beyond its saturation region.
The magnetic core can no longer respond proportionally to the magnetising current.
Its effective magnetising inductance falls, and the magnetising current can increase sharply.
This current can become strongly distorted rather than remaining sinusoidal.
The transformer may consequently experience excessive primary current and winding heating.
Why the magnetising reactance model becomes unreliable
The simplified model assumes a reasonably constant magnetising inductance:
\[ X_m=2\pi fL_m \]
If \(L_m\) remained constant, halving the frequency would halve \(X_m\), causing the magnetising current to double at constant voltage.
However, the core is now saturated.
The magnetising inductance is no longer constant, so simply predicting twice the magnetising current would underestimate the actual change.
The fixed \(X_m\) used in the original equivalent circuit is no longer a reliable representation of the transformer.
What happens to the secondary voltage?
The student’s second claim is also incorrect.
The ideal turns ratio still describes the relationship between the induced emfs:
\[ \frac{E_p}{E_s}=\frac{N_p}{N_s} \]
If the primary induced emf were still 240 V, the ideal secondary emf would still be:
\[ E_s=\frac{240}{10} \]
\[ E_s=24\text{ V} \]
The turns ratio does not automatically halve the secondary voltage when the frequency is halved.
However, this does not guarantee that the real transformer will deliver 24 V at its terminals.
Once the core saturates, the magnetising current increases sharply. This increases the voltage drop across the primary winding resistance and leakage reactance.
The primary induced emf can therefore differ from the applied terminal voltage, and the secondary terminal voltage can fall.
The turns ratio predicts an ideal induced-emf relationship. It does not remove the internal limitations of a real transformer.
What happens to the losses?
The increased magnetising current can cause much greater winding resistive heating because:
\[ P_{\text{copper}}=I^2R \]
Even a moderate increase in current can produce a substantial increase in heating.
Eddy-current losses also need careful consideration.
A simplified sinusoidal model gives an eddy-current loss relationship of approximately:
\[ P_{\text{eddy}}\propto f^2B_{\max}^2 \]
If frequency halves while peak flux density doubles, these two changes approximately cancel in this simplified relationship.
However, once the core saturates, the flux waveform becomes distorted, and the simple prediction is no longer reliable.
Hysteresis losses also depend on the magnetic behaviour of the core material and the size of the flux excursion.
It would therefore be incorrect to conclude that lowering the frequency automatically reduces all core losses.
Final evaluation
The three claims can now be assessed:
| Claim | Evaluation | Reason |
|---|---|---|
| Connecting a load increases core flux. | Incorrect | The additional primary current approximately balances the opposing secondary magnetic effect. |
| Halving frequency halves secondary voltage. | Incorrect | The ideal induced-emf ratio is determined by turns ratio, while flux and internal voltage drops change with frequency. |
| The same linear equivalent circuit remains valid in both situations. | Incorrect | Substantial saturation changes the magnetising inductance and invalidates the constant-parameter approximation. |
The deeper lesson is that a transformer does not respond to every change in the same way.
Changing the load mainly changes the current required to transfer power. Changing the supply frequency at constant voltage changes the magnetic flux required in the core.
That distinction is essential when deciding whether an equivalent circuit is still a valid model.
07Source notes and further reading
The physical mechanisms and equivalent-circuit approach in this article are consistent with university teaching materials and the NSW Physics curriculum.
- NESA – Physics 11-12 Syllabus (2025): syllabus structure and implementation timeline. The 2025 syllabus is scheduled to reach Year 12 in Term 4 2027, with the first HSC examination in 2028.
- University of Sydney – School of Physics HSC Electromagnetism: ideal transformer relationships and qualitative limitations involving incomplete flux linkage, eddy currents, and resistive heating.
- Indian Institute of Technology Bombay – Transformer Equivalent Circuits: transformer equivalent circuits, excitation currents, and primary-referred parameters.
- Portland State University – Magnetic Circuits and Transformers: real transformer models, leakage inductance, magnetising inductance, core losses, and equivalent-circuit approximations.
The worked examples and practice questions in this article use original numerical scenarios.
08What to study next
Once you can interpret the equivalent circuit, the next useful step is understanding how its parameters are measured.
Two tests are particularly important:
- The open-circuit test helps estimate the magnetising branch and core losses.
- The short-circuit test helps estimate the equivalent winding resistance and leakage reactance.
Together, these tests allow engineers to predict transformer efficiency and voltage regulation without needing to operate the transformer at every possible load.
That is where the equivalent circuit becomes more than a diagram: it becomes a practical model for predicting how a transformer will perform.