How to Find Secondary Current in an Ideal Step-Up Transformer

Learn how to calculate secondary current using the turns ratio, power conservation, or load resistance. Follow worked HSC Physics examples, understand common mistakes, and test your reasoning with challenging practice questions and solutions.

An ideal step-up transformer raises an AC voltage from \(6.0\text{ V}\) to \(24\text{ V}\). Yet an ammeter on its secondary circuit reads zero when the output switch is open. Close the switch to connect a \(48\,\Omega\) resistor. Will the secondary current be zero, \(0.50\text{ A}\), or \(2.0\text{ A}\)?

It becomes \(0.50\text{ A}\). The higher voltage doesn’t automatically produce a particular current. The load connected to the transformer determines how much current flows.

To find the secondary current of an ideal step-up transformer when the primary current is known, use:

\[ I_s=I_p\frac{N_p}{N_s} \]

Alternatively, if you know the input and output voltages:

\[ I_s=\frac{V_pI_p}{V_s} \]

Here:

  • \(I_s\) is the secondary current, in amperes (A).
  • \(I_p\) is the primary current, in amperes (A).
  • \(N_s\) is the number of turns on the secondary coil.
  • \(N_p\) is the number of turns on the primary coil.
  • \(V_s\) is the secondary voltage, in volts (V).
  • \(V_p\) is the primary voltage, in volts (V).

For a step-up transformer, \(N_s>N_p\), so the secondary current is smaller than the primary current at the same operating condition, provided current is flowing.

But what if the primary current isn’t given? Then you need to investigate the secondary load instead.

01What an experiment with two ammeters would reveal

Imagine a low-voltage transformer demonstration.

On the left, an AC power supply is connected to a primary coil with 100 turns. On the right, a secondary coil with 400 turns is wound around the same magnetic core.

The coils are electrically separate. There is no conducting wire joining the primary circuit to the secondary circuit.

The secondary circuit contains a resistor, a switch, and an ammeter connected in series. A voltmeter is connected across the secondary coil.

First observation: voltage can exist without current

The AC supply produces a changing magnetic flux through the core. That changing flux links the secondary coil and induces an alternating voltage across it.

Because the secondary has four times as many turns, the ideal model predicts:

\[ \begin{aligned} V_s&=V_p\frac{N_s}{N_p}\\ &=6.0\times\frac{400}{100}\\ &=24\text{ V} \end{aligned} \]

Now leave the secondary switch open.

The secondary voltmeter can still indicate \(24\text{ V}\), but the secondary ammeter reads \(0\text{ A}\). There is no complete path through which charge can circulate.

A voltage is available, but no power is being delivered to the resistor.

This is the first weakness in the prediction that a step-up transformer must produce a particular output current. The turns ratio establishes the voltage relationship, not the amount of current demanded by a disconnected circuit.

Second observation: closing the circuit changes both currents

Close the switch.

The \(48\,\Omega\) resistor now has \(24\text{ V}\) across it. Ohm’s law predicts:

\[ \begin{aligned} I_s&=\frac{V_s}{R}\\ &=\frac{24\text{ V}}{48\,\Omega}\\ &=0.50\text{ A} \end{aligned} \]

Here, \(R\) is the load resistance in ohms (\(\Omega\)).

An ammeter in the secondary circuit should now register current. But the secondary ammeter alone cannot reveal how much extra power the primary source is supplying.

That suggests a better experimental design.

Add a second ammeter in series with the primary coil and a voltmeter across the primary. Keep the AC supply voltage constant, and repeat the test using different secondary resistors.

For an ideal transformer, the predicted readings are:

Secondary loadSecondary currentPrimary currentTransferred power
Open circuit\(0\text{ A}\)\(0\text{ A}\)\(0\text{ W}\)
\(96\,\Omega\)\(0.25\text{ A}\)\(1.0\text{ A}\)\(6.0\text{ W}\)
\(48\,\Omega\)\(0.50\text{ A}\)\(2.0\text{ A}\)\(12\text{ W}\)

These are calculated ideal-model predictions, not measurements from a performed experiment. The model assumes an ideal AC source, ideal meters, and no magnetising current or energy losses.

Notice the pattern.

When the secondary resistance decreases, its current increases. The primary also draws more current from the source.

The transformer hasn’t changed its number of turns. The input voltage hasn’t changed either.

Only the load has changed.

That observation is the key to finding secondary current correctly: the turns ratio tells you how the two currents are related, but the load determines the operating current.

In a real demonstration, you would also check whether the voltages remain close to their ideal values. Real transformers draw some magnetising current even without a load, and their output voltage can fall under load because of internal resistance and imperfect magnetic coupling.

02Why stepping up voltage reduces current at a given power

The secondary current produces its own magnetic field, which interacts with the changing magnetic flux linking the coils.

By Lenz’s law, the induced current has a magnetic effect that opposes the change producing it. When the secondary draws more power, the primary source must supply the corresponding energy through the magnetic coupling.

An ideal transformer does not create electrical energy or lose any of it.

For a resistive load, electrical power is:

\[ P=VI \]

where \(P\) is power in watts (W), \(V\) is RMS voltage in volts, and \(I\) is RMS current in amperes.

Therefore, an ideal transformer satisfies:

\[ P_p=P_s \]

and hence:

\[ V_pI_p=V_sI_s \]

Rearranging gives:

\[ I_s=\frac{V_pI_p}{V_s} \]

This explains why the secondary current is smaller when voltage is stepped up.

If voltage becomes five times larger, current must become five times smaller for the same transferred power.

The transformer is changing how electrical power is delivered, not increasing the amount of power.

Connect the current ratio to the turns ratio

The voltage transformation follows:

\[ \frac{V_s}{V_p}=\frac{N_s}{N_p} \]

Substituting this into the power relationship gives:

\[ \frac{I_s}{I_p}=\frac{N_p}{N_s} \]

Notice that the current ratio is the inverse of the turns ratio.

Transformer propertyIdeal step-up transformer
Secondary turnsMore than primary
Secondary voltageHigher than primary
Secondary currentLower than primary at the same operating condition
Electrical powerEqual on both sides

The voltage relationship comes from electromagnetic induction. The current relationship follows from the ideal transformer’s transfer of power.

If the voltage relationship is unfamiliar, Ideal Transformer Voltage and Turns Ratio for HSC Physics explains how the shared changing magnetic flux determines the induced voltage.

Worked example: Find secondary current from primary current

An ideal transformer has 150 primary turns and 900 secondary turns. Its primary is connected to a \(20\text{ V}\) RMS AC supply and draws \(2.4\text{ A}\) while supplying a resistive load.

Calculate the secondary current and the resistance of the load.

Step 1

The secondary has six times as many turns:

\[ \frac{N_s}{N_p}=\frac{900}{150}=6 \]

Therefore:

\[ \begin{aligned} V_s&=20\times6\\ &=120\text{ V} \end{aligned} \]

The output voltage is six times the input voltage.

Step 2

\[ \begin{aligned} P_p&=V_pI_p\\ &=20\times2.4\\ &=48\text{ W} \end{aligned} \]

For an ideal transformer, the secondary also delivers \(48\text{ W}\).

Step 3

\[ \begin{aligned} I_s&=\frac{P_s}{V_s}\\ &=\frac{48}{120}\\ &=0.40\text{ A} \end{aligned} \]

We can check this directly using the inverse turns ratio:

\[ \begin{aligned} I_s&=2.4\times\frac{150}{900}\\ &=0.40\text{ A} \end{aligned} \]

Both methods agree.

Step 4

The resistor has \(120\text{ V}\) across it and carries \(0.40\text{ A}\).

\[ \begin{aligned} R&=\frac{V_s}{I_s}\\ &=\frac{120}{0.40}\\ &=300\,\Omega \end{aligned} \]

The secondary current is \(0.40\text{ A}\), and the connected resistor has a resistance of \(300\,\Omega\).

The current is one-sixth of the primary current because the secondary voltage is six times larger. The transformer still transfers \(48\text{ W}\).

03What if the primary current isn’t given?

Sometimes an exam question provides the secondary load resistance instead of the input current.

In that situation, you cannot begin with the inverse current ratio because \(I_p\) is unknown.

Instead, work from the load backwards:

  1. Calculate the secondary voltage from the turns ratio.
  2. Calculate the secondary current from the voltage and resistance.
  3. Calculate secondary power if required.
  4. Use ideal power conservation to find the primary current.

For a single resistor connected directly across the secondary:

\[ I_s=\frac{V_s}{R_L} \]

Here, \(R_L\) is the load resistance.

This means the current is determined by the complete secondary circuit. If the resistance changes while the secondary voltage stays constant, the secondary current changes too.

There is an important qualification: if the load is connected through resistive cables, not all of the secondary voltage appears across the load.

04Resistive line losses are not transformer losses

Suppose an ideal step-up transformer supplies a resistor through a long pair of wires.

The wires have resistance. They heat up when current passes through them.

This creates two separate questions:

  • How much current does the ideal transformer deliver?
  • How much power is lost in the external wires?

The first is determined by the secondary voltage and the total resistance in the secondary circuit.

The second uses:

\[ P_{\text{loss}}=I^2R \]

Here, \(I\) is the RMS current through the resistive wire, and \(R\) is that wire’s resistance.

You must not automatically subtract this loss from the transformer’s output power. If the transformer is ideal and the resistance belongs to an external cable, the transformer still has equal input and output power.

Worked example: Find secondary current with a resistive cable

An ideal step-up transformer has 200 primary turns and 800 secondary turns. Its primary is supplied with \(18\text{ V}\) RMS AC.

The secondary supplies a \(60\,\Omega\) resistor through connecting wires with a combined resistance of \(12\,\Omega\).

Calculate:

  • the secondary current,
  • the primary current,
  • the power dissipated in the wires, and
  • the power delivered to the load.

Step 1

The turns ratio is:

\[ \frac{N_s}{N_p}=\frac{800}{200}=4 \]

Therefore:

\[ V_s=18\times4=72\text{ V} \]

Step 2

The cable resistance and load resistance are in series, so:

\[ \begin{aligned} R_{\text{total}}&=R_{\text{line}}+R_L\\ &=12+60\\ &=72\,\Omega \end{aligned} \]

The same current passes through the cables and the load.

\[ \begin{aligned} I_s&=\frac{V_s}{R_{\text{total}}}\\ &=\frac{72}{72}\\ &=1.0\text{ A} \end{aligned} \]

Step 3

The ideal transformer delivers:

\[ \begin{aligned} P_s&=V_sI_s\\ &=72\times1.0\\ &=72\text{ W} \end{aligned} \]

Its primary must therefore receive \(72\text{ W}\).

\[ \begin{aligned} I_p&=\frac{P_p}{V_p}\\ &=\frac{72}{18}\\ &=4.0\text{ A} \end{aligned} \]

The secondary current is \(1.0\text{ A}\), exactly one-quarter of the primary current.

Step 4

The cable loses:

\[ \begin{aligned} P_{\text{line}}&=I_s^2R_{\text{line}}\\ &=(1.0)^2(12)\\ &=12\text{ W} \end{aligned} \]

The load receives:

\[ \begin{aligned} P_L&=I_s^2R_L\\ &=(1.0)^2(60)\\ &=60\text{ W} \end{aligned} \]

The power balance is:

\[ 72\text{ W}=12\text{ W}+60\text{ W} \]

The transformer transfers \(72\text{ W}\) without loss. The external cables dissipate \(12\text{ W}\), leaving \(60\text{ W}\) for the load.

Calling the transformer itself \(60/72=83.3\%\) efficient would be incorrect. The transformer is ideal; it is the complete transmission arrangement that loses power outside the transformer.

05Choosing the correct secondary-current calculation

Before substituting numbers, identify what the question actually gives you.

Given informationMethod
Primary current and both voltages\(I_s=V_pI_p/V_s\)
Primary current and both turn counts\(I_s=I_pN_p/N_s\)
Secondary power and voltage\(I_s=P_s/V_s\)
Secondary voltage and a directly connected resistor\(I_s=V_s/R_L\)
Secondary voltage and a series cable resistance\(I_s=V_s/(R_L+R_{\text{line}})\)

These methods are consistent. They simply begin with different known quantities.

All the calculations so far use RMS magnitudes for steady AC, purely resistive loads, and ideal transformer behaviour. The primary current is treated as entering the transformer from the source, while the secondary current leaves towards the load. These are positive magnitudes, not fixed instantaneous directions: AC reverses direction during each cycle.

The ideal model assumes:

  • perfect magnetic coupling between the coils,
  • zero winding resistance and no internal resistive heating,
  • no eddy-current or hysteresis losses in the core, and
  • negligible magnetising current.

Real transformers do not satisfy these assumptions exactly. The simple \(P=VI\) calculations here also rely on resistive loads, where voltage and current are in phase. With reactive loads, average power requires a power-factor term.

One final distinction is particularly useful.

The equation \(I_s=I_pN_p/N_s\) compares the currents through the two coils in one operating condition. It does not mean that replacing a transformer with a greater turns ratio must reduce the current through a resistor whose resistance stays fixed.

If the secondary voltage increases while that load resistance stays unchanged, Ohm’s law predicts that its current increases. The primary current then adjusts to provide the extra power.

That competing prediction becomes important in the questions below.

06Questions and solutions

Question 1

An ideal transformer has 250 primary turns and 1250 secondary turns. The primary is supplied with \(12\text{ V}\) RMS AC and draws \(1.5\text{ A}\) while supplying a resistive load.

Calculate the secondary voltage, secondary current, and power delivered to the load.

Solution 1

The secondary voltage is \(60\text{ V}\), the secondary current is \(0.30\text{ A}\), and the load receives \(18\text{ W}\).

The transformer is step-up because its secondary has more turns.

First calculate the turns ratio:

\[ \frac{N_s}{N_p}=\frac{1250}{250}=5 \]

Therefore:

\[ \begin{aligned} V_s&=12\times5\\ &=60\text{ V} \end{aligned} \]

The secondary current follows the inverse turns ratio:

\[ \begin{aligned} I_s&=I_p\frac{N_p}{N_s}\\ &=1.5\times\frac{250}{1250}\\ &=0.30\text{ A} \end{aligned} \]

The output power is:

\[ \begin{aligned} P_s&=V_sI_s\\ &=60\times0.30\\ &=18\text{ W} \end{aligned} \]

Checking against the input:

\[ P_p=12\times1.5=18\text{ W} \]

The two powers are equal, as expected.

The tempting mistake is to multiply the primary current by five because the transformer steps the voltage up by five. That would imply five times as much current and twenty-five times as much power, violating the ideal power relationship.

Question 2

An ideal step-up transformer has 200 primary turns and 800 secondary turns. It is connected to a constant \(12\text{ V}\) RMS AC supply.

A \(96\,\Omega\) resistor is permanently connected across the secondary.

A second resistor of unknown resistance can be connected in parallel using a switch.

With the switch open, the primary current is \(2.0\text{ A}\). When the switch closes, the primary current rises to \(5.0\text{ A}\).

Determine:

a. The secondary current before and after closing the switch.

b. The resistance of the second resistor.

c. The power delivered to each resistor after closing the switch.

d. Why the primary current increases even though the transformer is ideal.

Solution 2

The secondary current increases from \(0.50\text{ A}\) to \(1.25\text{ A}\). The added resistor is \(64\,\Omega\). After switching, the original resistor receives \(24\text{ W}\), and the new resistor receives \(36\text{ W}\).

The key constraint is that the supply maintains a constant voltage, not a constant power.

Find the secondary voltage.

The turns ratio is four:

\[ V_s=12\times\frac{800}{200}=48\text{ V} \]

Find the initial secondary current.

The input power with the switch open is:

\[ P_p=12\times2.0=24\text{ W} \]

Therefore:

\[ \begin{aligned} I_s&=\frac{24}{48}\\ &=0.50\text{ A} \end{aligned} \]

That agrees with Ohm’s law for the \(96\,\Omega\) resistor:

\[ I=\frac{48}{96}=0.50\text{ A} \]

Find the current after closing the switch.

The new input power is:

\[ P_p=12\times5.0=60\text{ W} \]

The ideal secondary delivers the same power:

\[ \begin{aligned} I_s&=\frac{60}{48}\\ &=1.25\text{ A} \end{aligned} \]

The original resistor still has \(48\text{ V}\) across it, so its current remains \(0.50\text{ A}\).

The new branch must carry:

\[ \begin{aligned} I_{\text{new}}&=1.25-0.50\\ &=0.75\text{ A} \end{aligned} \]

Therefore:

\[ \begin{aligned} R_{\text{new}}&=\frac{48}{0.75}\\ &=64\,\Omega \end{aligned} \]

Calculate the branch powers.

For the original resistor:

\[ P_{96}=48\times0.50=24\text{ W} \]

For the new resistor:

\[ P_{64}=48\times0.75=36\text{ W} \]

Total:

\[ 24+36=60\text{ W} \]

The result agrees with the new primary power.

The tempting argument is that the two resistors must share the original \(24\text{ W}\). But ideal transformers conserve power between their two sides; they do not force input power to stay constant.

Closing the switch adds another current path. The secondary supplies extra current, so the primary draws more power from the AC source.

Question 3

Two ideal step-up transformers are supplied separately by identical \(12\text{ V}\) RMS AC sources.

Transformer A has a secondary-to-primary turns ratio of \(3:1\).

Transformer B has a secondary-to-primary turns ratio of \(6:1\).

Both are initially connected directly to identical \(144\,\Omega\) resistors.

a. Calculate the secondary current and primary current for each transformer.

b. Explain why the transformer with the greater step-up ratio has the greater secondary current in this comparison.

c. Transformer B’s load is then replaced with another resistor so that its input power equals Transformer A’s original input power. Determine the new resistance and secondary current.

d. Explain why the direction of the current comparison changes between parts (a) and (c).

Solution 3

With identical \(144\,\Omega\) loads, Transformer B has twice the secondary current of Transformer A: \(0.50\text{ A}\) compared with \(0.25\text{ A}\). However, if both transfer \(9.0\text{ W}\), Transformer B’s secondary current becomes \(0.125\text{ A}\), which is smaller.

The distinction is what remains constant.

Transformer A: turns ratio \(3:1\).

Its secondary voltage is:

\[ V_{sA}=12\times3=36\text{ V} \]

Its load current is:

\[ I_{sA}=\frac{36}{144}=0.25\text{ A} \]

The ideal current transformation gives:

\[ I_{pA}=3\times0.25=0.75\text{ A} \]

The transferred power is:

\[ P_A=36\times0.25=9.0\text{ W} \]

Transformer B: turns ratio \(6:1\).

Its secondary voltage is:

\[ V_{sB}=12\times6=72\text{ V} \]

Its load current is:

\[ I_{sB}=\frac{72}{144}=0.50\text{ A} \]

Its primary current is:

\[ I_{pB}=6\times0.50=3.0\text{ A} \]

Its transferred power is:

\[ P_B=72\times0.50=36\text{ W} \]

Transformer B delivers four times as much power because doubling the voltage across the same resistance doubles the current.

Since \(P=VI\), the power increases by a factor of four.

Now hold the power constant instead.

Transformer B must deliver only \(9.0\text{ W}\), while its secondary voltage remains \(72\text{ V}\).

Therefore:

\[ \begin{aligned} I_{sB}&=\frac{9.0}{72}\\ &=0.125\text{ A} \end{aligned} \]

The new load resistance must be:

\[ \begin{aligned} R&=\frac{72}{0.125}\\ &=576\,\Omega \end{aligned} \]

The corresponding primary current is:

\[ I_{pB}=\frac{9.0}{12}=0.75\text{ A} \]

Now both transformers receive the same input power, and Transformer B has the smaller secondary current.

The tempting rule is that a greater step-up ratio always produces less secondary current.

That rule compares currents at a fixed primary current or fixed transferred power. In the first comparison, power was allowed to change because the same resistance was connected to a different voltage.

In the second comparison, power was fixed by changing the resistance. The higher voltage then required a smaller current.

Both results obey the ideal transformer equations. The difference is the condition being held constant.

Question 4

An ideal step-up transformer is connected to a constant \(20\text{ V}\) RMS AC supply. Its secondary-to-primary turns ratio is \(3:1\).

A \(40\,\Omega\) resistor is connected to the secondary through a cable of unknown resistance.

The primary ammeter reads \(3.0\text{ A}\).

An ideal switch is then closed to bypass the entire resistive cable, connecting the \(40\,\Omega\) load directly across the secondary.

Determine:

a. The original cable resistance.

b. The original power dissipated in the cable and delivered to the load.

c. The new secondary and primary currents after the cable is bypassed.

d. Whether removing the cable resistance reduces the current drawn from the source. Explain the result using energy conservation.

Solution 4

The original cable resistance is \(20\,\Omega\), and bypassing it increases the primary current from \(3.0\text{ A}\) to \(4.5\text{ A}\), even though the cable loss falls to zero.

This happens because the load receives substantially more power once the cable voltage drop disappears.

Find the original secondary current.

The secondary voltage is:

\[ V_s=20\times3=60\text{ V} \]

Using the inverse turns ratio:

\[ \begin{aligned} I_s&=I_p\frac{N_p}{N_s}\\ &=3.0\times\frac13\\ &=1.0\text{ A} \end{aligned} \]

Find the unknown cable resistance.

The total secondary resistance is:

\[ \begin{aligned} R_{\text{total}}&=\frac{60}{1.0}\\ &=60\,\Omega \end{aligned} \]

Since the load is \(40\,\Omega\):

\[ \begin{aligned} R_{\text{line}}&=60-40\\ &=20\,\Omega \end{aligned} \]

Calculate the original power distribution.

The cable dissipates:

\[ \begin{aligned} P_{\text{line}}&=(1.0)^2(20)\\ &=20\text{ W} \end{aligned} \]

The load receives:

\[ \begin{aligned} P_L&=(1.0)^2(40)\\ &=40\text{ W} \end{aligned} \]

Together:

\[ 20+40=60\text{ W} \]

The primary also receives:

\[ P_p=20\times3.0=60\text{ W} \]

All the energy is accounted for.

Close the bypass switch.

The secondary still supplies \(60\text{ V}\), but its effective external resistance is now only \(40\,\Omega\).

\[ \begin{aligned} I_s&=\frac{60}{40}\\ &=1.5\text{ A} \end{aligned} \]

The new secondary power is:

\[ P_s=60\times1.5=90\text{ W} \]

Therefore, the new primary current is:

\[ \begin{aligned} I_p&=\frac{90}{20}\\ &=4.5\text{ A} \end{aligned} \]

All \(90\text{ W}\) now reaches the load.

The results are:

QuantityBefore bypassAfter bypass
Secondary current\(1.0\text{ A}\)\(1.5\text{ A}\)
Primary current\(3.0\text{ A}\)\(4.5\text{ A}\)
Cable heating\(20\text{ W}\)\(0\text{ W}\)
Load power\(40\text{ W}\)\(90\text{ W}\)

It seems reasonable to predict that eliminating wasted energy should reduce the primary current.

That prediction misses the changed load conditions.

Removing the cable resistance allows more current to reach the load. The extra useful power is greater than the eliminated cable heating, so the source actually supplies more total power.

The transformer remains ideal throughout both operating conditions.

Question 5

A \(20\text{ V}\) RMS AC source supplies a distant \(5.0\,\Omega\) resistive load. The connecting transmission cable has a total resistance of \(45\,\Omega\).

An engineer considers two arrangements.

Arrangement A: The source is connected directly to the cable and then to the load.

Arrangement B: An ideal step-up transformer at the sending end increases the voltage by a factor \(n\). At the receiving end, another ideal transformer reduces the voltage by the same factor \(n\), supplying the original \(5.0\,\Omega\) load.

Both transformers have zero internal loss. The source maintains exactly \(20\text{ V}\) regardless of how much current it supplies, and the cable is the only component that wastes electrical power.

For the transformer arrangement, \(n\) must be a whole number greater than 1.

a. Find the cable current, cable heating, and load power in Arrangement A.

b. For Arrangement B with \(n=2\), calculate the cable current, cable heating, load current, and current drawn from the original source. Does the higher transmission voltage reduce the cable loss?

c. Determine a non-trivial turns ratio \(n>1\) for which the cable current is exactly the same as in Arrangement A. Compare the load power in the two arrangements.

d. Find the smallest permitted integer value of \(n>1\) that actually reduces cable heating below Arrangement A. Explain why this result does not contradict the usual reason for using high-voltage electricity transmission.

Solution 5

Arrangement A has a cable current of \(0.40\text{ A}\) and a cable loss of \(7.2\text{ W}\).

Surprisingly, Arrangement B with \(n=2\) has a larger cable current of approximately \(0.615\text{ A}\) and a larger cable loss of \(17.0\text{ W}\). At \(n=9\), cable heating becomes equal to Arrangement A. Only integer ratios of 10 or greater reduce it.

The central constraint is that the source voltage and load resistance are fixed, but the power delivered to the load is not.

Part (a): Direct transmission.

The cable and load resistances are in series.

\[ \begin{aligned} R_{\text{total}}&=45+5\\ &=50\,\Omega \end{aligned} \]

Therefore:

\[ \begin{aligned} I_A&=\frac{20}{50}\\ &=0.40\text{ A} \end{aligned} \]

The cable loss is:

\[ \begin{aligned} P_{\text{line},A}&=(0.40)^2(45)\\ &=7.2\text{ W} \end{aligned} \]

The load receives:

\[ \begin{aligned} P_{L,A}&=(0.40)^2(5.0)\\ &=0.80\text{ W} \end{aligned} \]

The source supplies \(20\times0.40=8.0\text{ W}\), exactly the sum of the load power and cable heating.

Part (b): Step up by a factor of two, then step down by two.

The sending transformer produces:

\[ V_{\text{send}}=20\times2=40\text{ V} \]

The receiving transformer has a step-down ratio of \(2:1\).

This creates a subtle effect: if the cable delivers a current \(I_{\text{line}}\) into the receiving transformer’s primary, the load current is twice as large.

\[ I_L=2I_{\text{line}} \]

The load voltage is:

\[ V_L=5I_L=10I_{\text{line}} \]

The voltage on the receiving transformer’s primary must be twice its secondary voltage:

\[ V_{\text{receive}}=20I_{\text{line}} \]

The cable also has a voltage drop of:

\[ V_{\text{drop}}=45I_{\text{line}} \]

Together, these voltages must equal the sending voltage:

\[ 40=20I_{\text{line}}+45I_{\text{line}} \]

Therefore:

\[ \begin{aligned} I_{\text{line}}&=\frac{40}{65}\\ &\approx0.615\text{ A} \end{aligned} \]

The cable heating is:

\[ \begin{aligned} P_{\text{line}}&=(0.61538)^2(45)\\ &\approx17.0\text{ W} \end{aligned} \]

This is greater than the original \(7.2\text{ W}\).

The receiving load current is:

\[ \begin{aligned} I_L&=2(0.61538)\\ &\approx1.23\text{ A} \end{aligned} \]

The sending transformer also has a \(2:1\) voltage step-up, so its primary current is twice the cable current:

\[ I_{\text{source}}\approx1.23\text{ A} \]

The source now supplies approximately:

\[ P_{\text{source}}=20(1.23077)\approx24.6\text{ W} \]

The load receives:

\[ \begin{aligned} P_L&=(1.23077)^2(5.0)\\ &\approx7.57\text{ W} \end{aligned} \]

And:

\[ 17.04+7.57\approx24.61\text{ W} \]

The power balance is correct.

The source supplies much more power than it did with direct transmission, so the increased cable loss is not a violation of energy conservation.

Part (c): Find the ratio that gives the original cable current.

For a general ratio \(n\), the sending transformer produces a voltage of \(20n\).

The receiving transformer delivers a load current of:

\[ I_L=nI_{\text{line}} \]

Since the load resistance is \(5.0\,\Omega\), its voltage is:

\[ V_L=5nI_{\text{line}} \]

The receiving transformer’s input voltage is \(n\) times that value:

\[ V_{\text{receive}}=5n^2I_{\text{line}} \]

Adding the cable voltage drop:

\[ 20n=45I_{\text{line}}+5n^2I_{\text{line}} \]

Hence:

\[ I_{\text{line}}=\frac{20n}{45+5n^2} \]

This gives the cable current for any positive ratio \(n\) under the stated assumptions.

We want it to equal the direct-transmission current of \(0.40\text{ A}\).

\[ \begin{aligned} \frac{20n}{45+5n^2}&=0.40\\ 50n&=45+5n^2\\ n^2-10n+9&=0\\ (n-1)(n-9)&=0 \end{aligned} \]

There are two solutions:

\[ n=1\quad\text{or}\quad n=9 \]

The \(n=1\) solution involves no voltage transformation. The non-trivial answer is \(n=9\).

At \(n=9\), the cable still carries \(0.40\text{ A}\), so its heating is still \(7.2\text{ W}\).

But the receiving transformer multiplies that current by nine:

\[ I_L=9(0.40)=3.6\text{ A} \]

The load now receives:

\[ \begin{aligned} P_L&=(3.6)^2(5.0)\\ &=64.8\text{ W} \end{aligned} \]

Compare that with just \(0.80\text{ W}\) under direct transmission.

The line current and line loss are identical, yet the useful load power is 81 times greater.

The primary current at the sending transformer is also \(3.6\text{ A}\), so the source supplies:

\[ P_{\text{source}}=20(3.6)=72\text{ W} \]

Again:

\[ 64.8+7.2=72\text{ W} \]

This is the surprising part. Knowing the cable current alone does not tell you how much power arrives at the load when a second transformer changes the voltage and current at the receiving end.

Part (d): Find when the cable loss finally decreases.

Because the cable resistance remains \(45\,\Omega\), reducing its heating requires a cable current smaller than \(0.40\text{ A}\).

Using the general expression:

\[ \frac{20n}{45+5n^2}<0.40 \]

For positive \(n\), rearranging gives:

\[ (n-1)(n-9)>0 \]

Since the permitted step-up ratios have \(n>1\), the cable current is smaller than its original value only when:

\[ n>9 \]

The smallest allowed integer ratio is therefore:

\[ n=10 \]

At this ratio:

\[ \begin{aligned} I_{\text{line}}&=\frac{20(10)}{45+5(10)^2}\\ &=\frac{200}{545}\\ &\approx0.367\text{ A} \end{aligned} \]

The cable heating is:

\[ \begin{aligned} P_{\text{line}}&=(0.367)^2(45)\\ &\approx6.06\text{ W} \end{aligned} \]

That is finally smaller than \(7.2\text{ W}\).

However, the source current is approximately \(10(0.367)=3.67\text{ A}\). It remains much larger than the original \(0.40\text{ A}\), because the system is now delivering far more useful power to the load.

Why doesn’t this contradict high-voltage transmission?

The usual statement is that transmitting a given amount of power at higher voltage allows a lower current, reducing \(I^2R\) heating in a line of fixed resistance.

That statement is correct.

But this question did not hold delivered power constant. It held the original source voltage and physical load resistance constant.

Adding transformers changed the voltage across the load and therefore changed how much power the load demanded.

The higher transmission voltage did not automatically mean lower cable current.

The important distinction is:

  • At fixed transmitted power, a higher voltage allows a lower current.
  • At fixed source voltage and load resistance, changing transformer ratios can change the total power being transferred.

The two situations impose different constraints and can produce different results.

07What to decide before your next transformer calculation

When finding secondary current, first identify exactly which current the question is asking about.

The secondary current of a transformer, the current in a transmission cable, and the current delivered by a receiving transformer are not necessarily the same.

If the question gives primary current and the turns ratio, use the inverse turns ratio. If it gives the load, work from secondary voltage and circuit resistance. If a cable has resistance, include its voltage drop and calculate its heating separately from transformer power.

And whenever a question says that a higher voltage produces a lower current, ask what is being held constant: the transferred power, the primary current, or the resistance of the connected load.

That decision is the bridge to understanding why high-voltage transmission can reduce resistive losses without suggesting that a transformer creates extra energy. For a more detailed treatment of the underlying power relationship, see Ideal Transformer Current and Power for HSC Physics.