Litz Wire: How Fine Strands Reduce High-Frequency AC Losses

Discover how litz wire uses fine, individually insulated and twisted copper strands to reduce skin-effect and proximity-effect losses. Explore the physics behind its design, worked examples, and why the best strand configuration depends on operating frequency and current.

Imagine two transformer windings carrying the same high-frequency alternating current. One uses a thick, solid copper wire. The other uses dozens of much thinner copper strands, each insulated from the others. Both carry the same RMS current, yet the second winding can produce considerably less unwanted heat.

Why should dividing one copper wire into many smaller wires make such a difference?

The answer involves two effects that become increasingly important as AC frequency rises: the skin effect and the proximity effect. A specially constructed conductor called litz wire uses many fine, insulated, twisted strands to reduce the losses caused by these effects.

This article builds on the Year 12 Electromagnetism content in the NSW Physics 11-12 (2025) syllabus. Litz wire is an extension beyond the required syllabus, not an assessment requirement. The generator model is the prerequisite; the conductor design is the additional physics.

01Start with the generator: what happens to the current?

Before looking at litz wire, recall how an AC generator produces a changing current.

Imagine a rectangular coil rotating at constant angular velocity in a uniform magnetic field. As the coil rotates, the magnetic flux through it changes. Faraday’s law tells us that this changing flux induces an electromotive force (emf).

For a coil with \(N\) turns, area \(A\), and angular velocity \(\omega\), rotating in a magnetic field of strength \(B\), the induced emf is:

\[ \varepsilon(t)=NBA\omega\sin(\omega t) \]

Here:

  • \(\varepsilon(t)\) is the instantaneous induced emf, in volts.
  • \(N\) is the number of turns in the coil.
  • \(B\) is the magnetic field strength, in tesla.
  • \(A\) is the area of one turn, in square metres.
  • \(\omega\) is angular velocity, in radians per second.
  • \(t\) is time, in seconds.

The important feature is the sine function. The induced emf changes continuously as the coil rotates.

Side-by-side AC and DC generators show rotating rectangular coils between north and south magnetic poles, their different ring-and-brush collectors, external resistive loads, and corresponding output waveforms.
An idealised rotating coil induces sinusoidal emf; slip rings preserve alternating output, while a split-ring commutator reverses the connections each half-turn to deliver one-way pulses.

Due to technical limitations, this figure may display incorrectly or contain inaccuracies. Please check key details against your course materials.

AC generators: current reverses direction

An AC generator uses two slip rings. Each ring maintains contact with one end of the rotating coil.

As the coil completes half a rotation, the direction of its induced emf reverses. The current in the external circuit therefore reverses direction as well.

For a purely resistive load with resistance \(R\), the current follows the sinusoidal emf:

\[ i(t)=\frac{\varepsilon_{\max}}{R}\sin(\omega t) \]

The current alternates between positive and negative values.

A positive current represents one direction of conventional current flow. A negative current represents the opposite direction.

One qualification: the generator’s induced emf is sinusoidal in this ideal model, but the actual current also depends on the external load. If the load is inductive, for example, the current can lag behind the voltage. This connects to AC impedance and phase differences.

DC generators: current keeps the same direction

A DC generator uses a split-ring commutator instead of two continuous slip rings.

The commutator swaps the coil’s connections to the external circuit every half-turn. This happens just as the induced emf in the coil reverses.

The result is that the external current continues in the same direction.

However, there is an important detail that students sometimes overlook.

A DC generator does not necessarily produce constant current.

For a simple generator with one rotating coil and a resistive load, the output current has a pulsating shape:

\[ i_{\mathrm{DC}}(t)=I_{\max}|\sin(\omega t)| \]

The current never becomes negative, but its magnitude rises and falls. It briefly reaches zero twice during each complete rotation.

Real DC generators can use multiple coils and commutator segments to produce a smoother output.

FeatureAC generatorDC generator
Coil’s induced emfAlternatingAlternating
External connectionSlip ringsSplit-ring commutator
Current directionReversesRemains the same
Current magnitudeVariesVaries in a simple generator
Output waveformAlternatingPulsating direct current

This gives us the foundation for understanding litz wire.

An alternating current continually changes its magnitude and direction. That means it produces a changing magnetic field around its conductor. At sufficiently high frequencies, this changing field affects how current is distributed throughout the wire.

That is where the extra losses begin.

02Why a thick wire becomes inefficient at high frequencies

At first, you might expect a thicker copper wire to be better.

After all, a thicker wire has more copper available to carry current. For a steady DC current, increasing the cross-sectional area reduces resistance.

But AC introduces a complication.

The skin effect

Imagine a thick copper wire carrying a sinusoidal alternating current.

As the current changes, it produces a changing magnetic field. The associated induced electric fields redistribute current within the conductor.

At sufficiently high frequencies, the current becomes concentrated towards the outside of the wire.

This is called the skin effect.

The important consequence is that the entire cross-sectional area of a thick conductor is no longer being used equally effectively.

The centre still carries current, but its contribution becomes much smaller as frequency increases.

We describe this behaviour using a quantity called the skin depth, represented by \(\delta\).

Skin depth is the distance below the conductor’s surface at which the current density has fallen to approximately 37% of its surface value, for a sinusoidal current in a uniform conductor.

It is not a sharp boundary. Current still exists deeper inside the conductor.

For a good conductor such as copper, the skin depth is:

\[ \delta=\sqrt{\frac{\rho}{\pi f\mu}} \]

where:

  • \(\delta\) is skin depth, in metres.
  • \(\rho\) is the electrical resistivity of the material, in \(\Omega\,\mathrm{m}\).
  • \(f\) is the frequency of the alternating current, in hertz.
  • \(\mu\) is the magnetic permeability of the material, in henries per metre.

For copper at approximately \(20^\circ\mathrm{C}\), a useful approximation is:

\[ \delta(\mathrm{mm})\approx \frac{66}{\sqrt{f(\mathrm{Hz})}} \]

Notice the relationship:

\[ \delta\propto\frac{1}{\sqrt f} \]

As frequency increases, skin depth decreases.

Consider these approximate values:

FrequencyCopper skin depth
50 Hz9.3 mm
1 kHz2.1 mm
10 kHz0.66 mm
100 kHz0.21 mm
1 MHz0.066 mm

At ordinary mains frequency, skin depth is relatively large compared with many small wires.

At 100 kHz, however, it is only about 0.21 mm. A thick conductor can therefore have a substantial amount of copper carrying relatively little current.

This is why high-frequency winding designers cannot simply keep increasing wire diameter.

For a more detailed treatment of this mechanism, see The Skin Effect.

Worked example: comparing conductor sizes at 25 kHz

A transformer winding carries a sinusoidal current at 25 kHz. Compare the skin depth in copper with:

  • A solid copper wire with a diameter of 3.0 mm.
  • A litz wire strand with a copper diameter of 0.30 mm.

Take the copper skin-depth approximation as \(\delta=66/\sqrt f\) mm.

Step 1

The operating frequency is:

\[ f=25\,000\ \mathrm{Hz} \]

Substitute into the approximation:

\[ \begin{aligned} \delta&=\frac{66}{\sqrt{25\,000}}\\ &=\frac{66}{158.1}\\ &=0.417\ \mathrm{mm} \end{aligned} \]

The copper skin depth is approximately 0.42 mm.

Step 2

The solid wire has a radius of:

\[ r=\frac{3.0}{2}=1.5\ \mathrm{mm} \]

Compare this with the skin depth:

\[ \frac{r}{\delta}=\frac{1.5}{0.417} \approx3.60 \]

The radius is approximately 3.6 skin depths.

This suggests substantial current crowding towards the outside of the solid conductor. The copper near its centre contributes much less effectively.

Step 3

The strand diameter is 0.30 mm, which is smaller than the calculated skin depth of 0.417 mm.

Its radius is only 0.15 mm.

This means current can penetrate much more effectively throughout the individual strand.

Conclusion: Dividing the thick conductor into sufficiently fine strands can make much more of its copper useful for carrying high-frequency current.

However, this only addresses the skin effect within individual strands. Another mechanism can still increase the winding’s resistance.

03The second problem: proximity effect

Return to the transformer winding.

Its conductors do not sit in isolation. Each turn is surrounded by other turns carrying alternating current.

Every current-carrying conductor produces a magnetic field. When that current changes, its magnetic field changes too.

The magnetic fields produced by neighbouring turns affect the current distribution within each conductor.

This is called the proximity effect.

The proximity effect is different from the skin effect.

  • Skin effect describes current redistribution caused by the conductor’s own changing magnetic field.
  • Proximity effect describes current redistribution caused by changing magnetic fields from nearby conductors.

In a winding, these effects can occur simultaneously.

The proximity effect can be particularly troublesome because current may crowd towards one side of a conductor rather than simply towards its outer surface.

This creates additional losses, even when the conductor has been divided into small strands.

So we now have two problems:

  1. A thick conductor wastes some of its copper because of skin effect.
  2. Nearby conductors create additional current crowding because of proximity effect.

Simply using thinner wires helps with the first problem. It does not automatically solve the second.

04How litz wire tackles both effects

This brings us to litz wire.

Litz wire consists of many fine copper strands, each individually insulated, which are twisted or woven together in a carefully designed arrangement.

The insulation is usually a thin enamel coating.

There are three important features.

1. Each strand is thin

The individual copper strands are selected to have a diameter appropriate for the operating frequency.

If each strand is sufficiently small compared with the relevant skin depth, current can be distributed more evenly across its cross-section.

Instead of one large conductor with a relatively ineffective central region, we have many small conductors that make better use of their copper.

This reduces strand-level skin-effect losses.

2. Each strand is electrically insulated

Why bother coating every strand?

Wouldn’t it be simpler to bundle dozens of bare copper wires together?

The insulation is important because it keeps the strands electrically separate along their length.

Each strand acts as its own current path. The strands are connected in parallel at the ends of the cable, allowing current to divide between them.

Without individual insulation, current could transfer between touching strands along the cable. The bundle could then behave much more like a single large conductor, losing an important part of the advantage.

3. The strands are twisted and transposed

This is the part that makes properly constructed litz wire particularly useful.

Imagine several strands running next to one another through a transformer winding.

If one strand always occupies the same position, it may experience a different magnetic field from a strand on the opposite side of the bundle.

That means the strands can experience different induced voltages and different magnetic environments.

The result can be unequal current sharing and additional circulating currents.

To reduce this problem, litz wire uses a twisting or braiding arrangement in which each strand repeatedly changes its position within the bundle.

This process is called transposition.

Think of it as rotating positions in a queue. Instead of one strand permanently occupying the position with the strongest external field, every strand takes its turn in different positions.

The analogy is not exact: the strands do not exchange electrical connections as they move. They remain individually insulated. Their physical positions change, allowing their average exposure to the magnetic field to become more similar.

By combining fine strands, individual insulation, and transposition, litz wire can reduce both skin-effect and proximity-related winding losses.

It does not eliminate either effect completely. The external magnetic field, strand dimensions, twisting pattern, and winding geometry still matter.

05What does reducing AC resistance actually achieve?

We have discussed how litz wire changes the distribution of current. Now connect that to something measurable: power loss.

When current passes through a conductor, some electrical energy is converted into thermal energy.

For a sinusoidal AC current, the average copper power loss is:

\[ P_{\mathrm{cu}}=I_{\mathrm{rms}}^2R_{\mathrm{AC}} \]

where:

  • \(P_{\mathrm{cu}}\) is the average power dissipated as heat, in watts.
  • \(I_{\mathrm{rms}}\) is the root-mean-square current, in amperes.
  • \(R_{\mathrm{AC}}\) is the effective resistance at the operating frequency, in ohms.

The important point is that AC resistance can be considerably greater than DC resistance.

We can express this relationship as:

\[ R_{\mathrm{AC}}>R_{\mathrm{DC}} \]

when skin and proximity effects increase the effective resistance.

A correctly designed litz winding can reduce this AC resistance.

For the same RMS current, a lower AC resistance means less heating.

Worked example: comparing winding losses at 100 kHz

A high-frequency inductor carries a sinusoidal current of 5.0 A RMS at 100 kHz.

Two winding designs fit into the same winding space. Their calculated resistance values are:

PropertySolid copper windingLitz winding
DC resistance0.18 Ω0.24 Ω
AC resistance at 100 kHz0.80 Ω0.32 Ω

Calculate the copper power loss in each winding and determine the percentage reduction achieved by using litz wire.

Step 1

The current is alternating at 100 kHz, so we must use the AC resistance rather than the DC resistance.

The relevant equation is:

\[ P_{\mathrm{cu}}=I_{\mathrm{rms}}^2R_{\mathrm{AC}} \]

Step 2

Substitute the given values:

\[ \begin{aligned} P_{\mathrm{solid}} &=5.0^2\times0.80\\ &=25\times0.80\\ &=20\ \mathrm{W} \end{aligned} \]

The solid copper winding dissipates 20 W as heat.

Step 3

Using its AC resistance:

\[ \begin{aligned} P_{\mathrm{litz}} &=5.0^2\times0.32\\ &=25\times0.32\\ &=8.0\ \mathrm{W} \end{aligned} \]

The litz winding dissipates 8.0 W.

Step 4

The reduction in power loss is:

\[ \Delta P=20-8=12\ \mathrm{W} \]

Therefore:

\[ \begin{aligned} \%\text{ reduction} &=\frac{12}{20}\times100\\ &=60\% \end{aligned} \]

Conclusion: The litz winding reduces the calculated copper loss by 60%.

Notice something interesting about the original data.

The litz winding actually has a higher DC resistance: 0.24 Ω compared with 0.18 Ω.

If we only measured DC resistance, we might conclude that the solid wire was better. But at the operating frequency of 100 kHz, the litz winding has considerably lower effective resistance.

This is precisely why high-frequency winding design must account for AC resistance rather than relying on DC resistance alone.

06When is litz wire actually useful?

It would be tempting to conclude that more strands always produce a better conductor.

That is not correct.

Litz wire involves a design trade-off.

The disadvantages of using more strands

Each strand requires its own insulation. This means some of the available winding space is occupied by non-conducting material rather than copper.

Twisting also increases the length of the individual strands compared with the overall cable length.

Both effects can increase DC resistance.

If we keep adding finer strands, the reduction in AC losses eventually becomes smaller than the increase in other losses.

Research by Charles Sullivan, published in IEEE Transactions on Power Electronics, demonstrates this trade-off and establishes why an optimum number of strands exists for a given transformer winding design.

Read Sullivan’s IEEE research on optimal litz-wire strand selection.

Frequency and winding geometry matter

Litz wire is particularly useful in medium- and high-frequency inductors and transformers.

Examples include:

  • High-frequency switching power supplies.
  • High-frequency transformers.
  • Induction heating systems.
  • Wireless power transfer coils.
  • Some specialised electric machines.

The appropriate design depends on several factors:

  • Operating frequency.
  • Individual strand diameter.
  • Total copper cross-sectional area.
  • Number of strands.
  • Twisting and transposition pattern.
  • Magnetic fields produced by neighbouring turns.
  • Available winding space.

A 50 Hz winding does not automatically need litz wire. Copper skin depth at this frequency is approximately 9.3 mm, so skin effect is often modest in ordinary small-diameter conductors.

At higher frequencies, the advantage can become much more significant.

Researchers have also measured real litz-wire constructions and found that imperfect strand transposition, bundle construction, and electrical connections can produce additional losses. An idealised model therefore does not always predict the performance of a manufactured winding perfectly.

See Rossmanith and colleagues’ IEEE research on high-frequency losses in nonideal litz wires.

The University of Manchester has also published research examining litz-wire performance and optimisation in electrical machine windings, demonstrating that the design problem extends beyond simply choosing a small strand diameter.

Read the research on litz-wire loss performance.

One final complication: real currents contain multiple frequencies

So far, we have mostly assumed a single sinusoidal current.

In practice, some electrical systems produce currents containing several frequency components.

For example, a winding might carry:

  • A DC component.
  • A fundamental AC component.
  • Higher-frequency harmonics.

This matters because skin depth changes with frequency.

Recall:

\[ \delta\propto\frac{1}{\sqrt f} \]

If the frequency triples, the skin depth becomes:

\[ \delta_{\mathrm{new}}= \frac{\delta_{\mathrm{old}}}{\sqrt3} \]

A strand that is sufficiently thin for the fundamental frequency may not be as effective for a higher-frequency harmonic.

For a current containing a DC component and several sinusoidal harmonics, the copper loss can be considered as the sum of their individual contributions:

\[ P_{\mathrm{cu}}= I_{\mathrm{DC}}^2R_{\mathrm{DC}} + \sum_n I_{n,\mathrm{rms}}^2R_{\mathrm{AC}}(nf) \]

Here:

  • \(I_{\mathrm{DC}}\) is the average DC component of the current.
  • \(I_{n,\mathrm{rms}}\) is the RMS current in harmonic \(n\).
  • \(f\) is the fundamental frequency.
  • \(R_{\mathrm{AC}}(nf)\) is the effective AC resistance at the frequency of harmonic \(n\).

This equation is a useful reminder: a conductor must be designed for the actual current spectrum, not just its fundamental frequency.

It also explains why litz wire is not automatically the best choice for every winding.

07Questions and solutions

Question 1

A copper winding operates at 100 kHz and uses litz strands with individual copper diameters of 0.15 mm.

At \(20^\circ\mathrm{C}\), use the approximation:

\[ \delta(\mathrm{mm})=\frac{66}{\sqrt{f(\mathrm{Hz})}} \]

Calculate the skin depth and explain what the comparison suggests about skin effect within each strand.

Solution 1

The skin depth is approximately 0.21 mm, which is greater than the individual strand diameter of 0.15 mm. This suggests that current can be distributed relatively evenly across each strand.

Step 1: Substitute the frequency into the skin-depth equation.

\[ \begin{aligned} \delta&=\frac{66}{\sqrt{100\,000}}\\ &=\frac{66}{316.23}\\ &=0.209\ \mathrm{mm} \end{aligned} \]

Step 2: Compare the strand diameter with the skin depth.

\[ d=0.15\ \mathrm{mm} \]

\[ d<\delta \]

The strand diameter is smaller than the skin depth.

This means the current can penetrate effectively through the individual strand rather than being strongly concentrated near its outer surface.

Step 3: Interpret the result.

The strand dimensions are suitable for limiting skin-effect losses at this frequency.

However, this does not mean the complete winding has negligible AC resistance. Proximity effects from neighbouring strands and turns can still contribute to heating.

A small strand diameter is an important design consideration, but it is not the entire solution.

Question 2

A transformer winding uses solid copper wire with a diameter of 3.0 mm. It operates at 50 kHz, and its turns are tightly packed.

A proposed replacement uses litz wire containing individually insulated strands, each with a copper diameter of 0.25 mm.

Assume the copper skin depth at 50 kHz is approximately 0.30 mm.

(a) Compare the solid conductor and individual strand dimensions with the skin depth.

(b) Explain why the litz replacement can reduce skin-effect losses without necessarily eliminating total AC winding losses.

(c) Identify the additional construction feature that helps reduce proximity-related losses.

Solution 2

The litz replacement should reduce strand-level skin-effect losses, but it cannot guarantee that total winding losses become negligible. The changing magnetic fields from neighbouring turns can still produce proximity losses.

Step 1: Compare the solid wire with the skin depth.

The solid wire has a radius of:

\[ r=\frac{3.0}{2}=1.5\ \mathrm{mm} \]

The skin depth is 0.30 mm.

Therefore:

\[ \frac{r}{\delta}=\frac{1.5}{0.30}=5 \]

The solid wire has a radius five times the skin depth.

This indicates substantial current crowding towards its outer surface.

Step 2: Compare the individual litz strands.

Each strand has a diameter of 0.25 mm.

\[ 0.25\ \mathrm{mm}<0.30\ \mathrm{mm} \]

The individual strand diameter is smaller than the skin depth.

This allows current to be distributed more evenly within each strand, reducing skin-effect losses.

Step 3: Consider the neighbouring turns.

The winding contains closely packed conductors.

Their changing magnetic fields affect the current distribution within neighbouring conductors. This produces proximity losses.

Even if the individual strands are sufficiently thin to limit skin effect, the external magnetic field can still produce additional current redistribution.

Step 4: Explain the role of transposition.

The litz strands should be twisted or braided so that each strand repeatedly changes its position within the bundle.

This helps equalise their average magnetic exposure and induced voltages, reducing unequal current sharing and associated proximity-related losses.

However, transposition does not eliminate every effect of the external magnetic field.

The total improvement still depends on the winding geometry and operating conditions.

Question 3

A high-frequency inductor carries a sinusoidal current of 6.0 A RMS at 40 kHz.

Two possible winding designs have the following calculated AC resistances:

WindingAC resistance
Solid copper0.45 Ω
Litz wire0.20 Ω

(a) Calculate the copper power loss in each winding.

(b) Determine the maximum RMS current the litz winding could carry while producing the same copper loss as the solid winding at 6.0 A RMS.

Assume the resistance values remain constant over the current range, and ignore changes in cooling and other losses.

Solution 3

The solid winding dissipates 16.2 W, while the litz winding dissipates 7.2 W. The litz winding could carry 9.0 A RMS while maintaining the same copper loss as the solid winding carrying 6.0 A RMS.

Step 1: Calculate the solid winding’s power loss.

Use:

\[ P_{\mathrm{cu}}=I_{\mathrm{rms}}^2R_{\mathrm{AC}} \]

Substitute:

\[ \begin{aligned} P_{\mathrm{solid}} &=6.0^2\times0.45\\ &=36\times0.45\\ &=16.2\ \mathrm{W} \end{aligned} \]

Step 2: Calculate the litz winding’s power loss.

\[ \begin{aligned} P_{\mathrm{litz}} &=6.0^2\times0.20\\ &=36\times0.20\\ &=7.2\ \mathrm{W} \end{aligned} \]

The litz winding produces substantially less copper heating at the same current.

Step 3: Find the current that produces the same loss in the litz winding.

We want the litz winding to dissipate 16.2 W.

Rearrange the power equation:

\[ I_{\mathrm{rms}}= \sqrt{\frac{P_{\mathrm{cu}}}{R_{\mathrm{AC}}}} \]

Substitute:

\[ \begin{aligned} I_{\mathrm{litz}} &=\sqrt{\frac{16.2}{0.20}}\\ &=\sqrt{81}\\ &=9.0\ \mathrm{A} \end{aligned} \]

Step 4: Interpret the result.

The litz winding can carry:

\[ \frac{9.0-6.0}{6.0}\times100=50\% \]

more RMS current for the same calculated copper loss.

This illustrates the practical advantage of reducing AC resistance.

However, it does not mean every litz winding can carry 50% more current. The result depends on the specific resistance values, cooling conditions, insulation limits, and winding design.

Question 4

A transformer winding contains 40 individually insulated copper strands. Each strand has a diameter of 0.12 mm.

The strands are connected in parallel at both ends, but they remain in fixed positions within the bundle along the length of the winding.

The winding is positioned near an air gap in the transformer core. Assume the external alternating leakage field is stronger on one side of the winding than the other.

A redesign proposes twisting the strands so that every strand repeatedly moves through all positions in the bundle.

Explain:

(a) Why individual strand insulation does not automatically guarantee equal current sharing.

(b) How transposition changes the magnetic environment experienced by each strand.

(c) Why transposition reduces some losses without eliminating every proximity-related loss.

Solution 4

Transposition helps equalise the induced voltages and magnetic exposure of the strands, reducing unequal current sharing and circulating currents. It does not remove the external magnetic field or all the eddy-current losses it can produce.

Step 1: Consider the fixed strand positions.

Each strand remains in a different position within the bundle.

Because the external magnetic field is non-uniform, different strands can experience different magnetic flux linkages along their lengths.

This can produce different induced voltages in the parallel paths.

The insulation prevents current from transferring directly between strands along the cable. However, all strands are connected at their common terminals.

Consequently, the complete parallel circuit can still support circulating currents between strands through those connections when their induced voltages differ.

Individual insulation alone does not guarantee equal current sharing.

Step 2: Introduce transposition.

When the strands are twisted, each strand repeatedly changes its position within the bundle.

A strand that previously occupied the position closest to the air gap will later occupy other positions.

Over a sufficient length, each strand experiences a more similar average magnetic environment.

This helps equalise the induced voltages along the parallel paths.

Step 3: Explain the reduction in losses.

More equal induced voltages reduce circulating currents between parallel strands.

More balanced current sharing also reduces the tendency for particular strands to carry disproportionately large currents.

This helps control proximity-related losses at the bundle level.

Step 4: Identify the limitation.

Transposition does not make the external magnetic field disappear.

Each individual strand can still experience changing magnetic fields, producing local current redistribution and eddy-current losses.

The strength and distribution of the external field still affect the final winding resistance.

Therefore, transposition improves the conductor’s behaviour, but does not make it immune to proximity effects.

Question 5

A high-frequency transformer operates with a primary current containing a DC component, a fundamental AC component, and a third harmonic.

The current is:

\[ \begin{aligned} i(t)={}&1.0\\ &+4.0\sin(2\pi 50\,000t)\\ &+2.0\sin(2\pi150\,000t) \end{aligned} \]

The current is measured in amperes and time \(t\) is measured in seconds.

Two possible litz-wire designs fit into the same transformer winding window and have the same nominal total copper cross-sectional area.

  • Design A uses 0.12 mm strands and a shorter transposition pitch.
  • Design B uses 0.20 mm strands and a longer transposition pitch.

A winding model provides the following effective resistance values for the two designs. Assume these values already account for the relevant winding geometry and frequency-dependent losses.

ResistanceDesign ADesign B
DC resistance0.16 Ω0.13 Ω
AC resistance at 50 kHz0.22 Ω0.18 Ω
AC resistance at 150 kHz0.60 Ω0.95 Ω

(a) Calculate the total copper power loss for each design at the stated current waveform.

(b) Determine which design produces less copper heating.

(c) Keeping the DC component and fundamental unchanged, calculate the peak amplitude of the third harmonic at which the two designs produce equal copper losses.

(d) Explain why selecting the design with the lowest DC resistance and lowest fundamental-frequency resistance would give an incorrect decision for the stated waveform.

Solution 5

Design A produces less copper heating at the stated current waveform. Its total copper loss is 3.12 W, compared with 3.47 W for Design B. The designs have equal losses when the third-harmonic peak current is approximately 1.41 A.

The key is that the winding does not carry a single-frequency current. Each frequency component experiences a different effective resistance.

Step 1: Separate the current into its components.

The current contains three components:

  • DC component: 1.0 A.
  • Fundamental component: 4.0 A peak at 50 kHz.
  • Third harmonic: 2.0 A peak at 150 kHz.

For a sinusoidal component, RMS current is:

\[ I_{\mathrm{rms}}=\frac{I_{\max}}{\sqrt2} \]

Therefore, the fundamental RMS current is:

\[ I_{1,\mathrm{rms}}= \frac{4.0}{\sqrt2} \]

The third-harmonic RMS current is:

\[ I_{3,\mathrm{rms}}= \frac{2.0}{\sqrt2} \]

Their squared RMS values are:

\[ I_{1,\mathrm{rms}}^2=8.0\ \mathrm{A^2} \]

\[ I_{3,\mathrm{rms}}^2=2.0\ \mathrm{A^2} \]

Step 2: Calculate the total loss in Design A.

The DC component produces ordinary resistive heating. The two AC components must use their respective frequency-dependent resistances.

Therefore:

\[ \begin{aligned} P_A={}&I_{\mathrm{DC}}^2R_{\mathrm{DC}}\\ &+I_{1,\mathrm{rms}}^2R_{\mathrm{AC}}(50\,\mathrm{kHz})\\ &+I_{3,\mathrm{rms}}^2R_{\mathrm{AC}}(150\,\mathrm{kHz}) \end{aligned} \]

Substitute the values for Design A:

\[ \begin{aligned} P_A={}&1.0^2(0.16)\\ &+8.0(0.22)\\ &+2.0(0.60) \end{aligned} \]

\[ P_A=0.16+1.76+1.20 \]

\[ \boxed{P_A=3.12\ \mathrm{W}} \]

Step 3: Calculate the total loss in Design B.

Use the same method:

\[ \begin{aligned} P_B={}&1.0^2(0.13)\\ &+8.0(0.18)\\ &+2.0(0.95) \end{aligned} \]

\[ P_B=0.13+1.44+1.90 \]

\[ \boxed{P_B=3.47\ \mathrm{W}} \]

Step 4: Compare the results.

The difference in copper losses is:

\[ \Delta P=3.47-3.12 \]

\[ \Delta P=0.35\ \mathrm{W} \]

Design A produces 0.35 W less copper heating.

Although Design B has lower DC resistance and lower resistance at the fundamental frequency, its substantially higher resistance at the third harmonic makes it less efficient for this particular current waveform.

Step 5: Find the third-harmonic amplitude at which the losses become equal.

Let the unknown peak amplitude of the third harmonic be \(I_3\), measured in amperes.

Keep the DC component and fundamental unchanged.

For Design A:

\[ \begin{aligned} P_A &=0.16+8(0.22)+\frac{I_3^2}{2}(0.60)\\ &=1.92+0.30I_3^2 \end{aligned} \]

For Design B:

\[ \begin{aligned} P_B &=0.13+8(0.18)+\frac{I_3^2}{2}(0.95)\\ &=1.57+0.475I_3^2 \end{aligned} \]

At the point where both designs produce equal losses:

\[ 1.92+0.30I_3^2 = 1.57+0.475I_3^2 \]

Rearrange:

\[ 0.35=0.175I_3^2 \]

Therefore:

\[ I_3^2=2 \]

\[ \boxed{I_3=1.41\ \mathrm{A}} \]

The third-harmonic peak amplitude is approximately 1.41 A at the crossover point.

Above this amplitude, Design A produces less copper loss. Below it, Design B produces less copper loss, assuming the other current components and resistance values remain unchanged.

Step 6: Explain why the fundamental frequency alone gives the wrong answer.

At 50 kHz, copper skin depth is approximately:

\[ \delta_{50}=\frac{66}{\sqrt{50\,000}} =0.295\ \mathrm{mm} \]

At 150 kHz:

\[ \delta_{150}=\frac{66}{\sqrt{150\,000}} =0.170\ \mathrm{mm} \]

The third harmonic has three times the frequency of the fundamental, so its skin depth is smaller.

Design A’s 0.12 mm strands are smaller than both skin depths.

Design B’s 0.20 mm strands are smaller than the fundamental skin depth but larger than the third-harmonic skin depth.

This helps explain why Design B performs well at the fundamental but experiences greater losses at the higher frequency.

There is another tempting mistake here.

You might calculate the total RMS current and multiply its square by one AC resistance value.

The total RMS current is indeed:

\[ I_{\mathrm{total,rms}}=\sqrt{1+8+2} \]

\[ I_{\mathrm{total,rms}}=\sqrt{11} =3.32\ \mathrm{A} \]

However, using one resistance for this entire current would be incorrect because the DC component, fundamental, and third harmonic experience different effective resistances.

Each component must be treated separately.

The deeper lesson: the best litz-wire design is not necessarily the one with the lowest DC resistance, the finest strands, or the lowest resistance at the fundamental frequency. It is the design that minimises total winding losses across the actual current spectrum and magnetic environment.

The next step in transformer design is to balance these copper losses against magnetic core losses, leakage fields, available winding space, and temperature limits. That is where conductor selection becomes part of the design of the entire electromagnetic system.